Emerson OpenComms-485 manual REV 7/6/2007 Liebert Monitoring Group -Development

Page 28

REV. 5 7/6/2007

Liebert Monitoring Group –Development

Battery Temperature

30117

1

1

deg C

PFC Temperature

30118

1

1

deg C

Ambient Temperature

30119

1

1

deg C

Local 1 Temperature

30118

1

1

deg C

Local 2 Temperature

30119

1

1

deg C

Input Voltage L1

30153

1

1

V

Input Current L1

30154

1

1

A

Bypass Voltage L1

30159

1

1

V

Bypass Current L1

30160

1

1

A

Output Voltage L1

30163

1

1

V

Output Current L1

30164

1

1

A

Input Max. Voltage L1

30180

1

1

V

Input Min. Voltage L1

30181

1

1

V

Output Max. Voltage

30182

1

1

V

L1

 

 

 

 

Output Mini. Voltage

30183

1

1

V

L1

 

 

 

 

Input Voltage L2

30203

1

1

V

Input Current L2

30204

1

1

A

Bypass Voltage L2

30209

1

1

V

Bypass Current L2

30210

1

1

A

Output Voltage L2

30213

1

1

V

Output Current L2

30214

1

1

A

Input Max. Voltage L2

30230

1

1

V

Input Min. Voltage L2

30231

1

1

V

Output Max. Voltage

30232

1

1

V

L2

 

 

 

 

Output Min. Voltage L2

30233

1

1

V

Input Voltage L3

30253

1

1

V

Input Current L3

30254

1

1

A

Bypass Voltage L3

30259

1

1

V

Bypass Current L3

30260

1

1

A

Output Voltage L3

30263

1

1

V

Output Current L3

30264

1

1

A

Input Max. Voltage L3

30280

1

1

V

Input Min. Voltage L3

30281

1

1

V

Output Max. Voltage

30282

1

1

V

L3

 

 

 

 

Output Min. Voltage L3

30283

1

1

V

25

Image 28
Contents Monitoring Revision Level Updates Table of Contents Connectivity to OpenComms-485 using Modbus Modbus CommunicationsModbus Packet Format RTU Framing Liebert Nfinity Status Coil Scale RegInput Holding Register Scale REV 7/6/2007 Liebert Monitoring Group -Development Liebert Nx Data Point Status Coil # of Reg ScaleREV 7/6/2007 Liebert Monitoring Group -Development Data Point Input Register Holding Register # of Reg Scale Data Point Register Coil # of Reg Scale 100 VAR Liebert PowerSure Interactive Data Point Status Coil # of RegInput Holding Data Point Register # of Reg Scale REV 7/6/2007 Liebert Monitoring Group -Development Supported Modbus Points Data Point Input Register Holding Register # of Reg Scale REV 7/6/2007 Liebert Monitoring Group -Development Liebert GXT2 Status Coil # of Reg ScaleREV 7/6/2007 Liebert Monitoring Group -Development Input Register Holding Register # of Reg Scale REV 7/6/2007 Liebert Monitoring Group -Development Input Holding Register Liebert HiNet# of Reg Scale Liebert UPS Series Data PointInput Holding Scale Register REV 7/6/2007 Liebert Monitoring Group -Development Liebert UPS Series Battery Charger Fail 10234 REV 7/6/2007 Liebert Monitoring Group -Development Liebert DS Data points Mapped to Input Status and CoilsMain FAN Overload Sensor a Failure Data Points Mapped to Input and Holding Registers HourMinute Sleep Interval 30042 40042 MSBHr Events/Alarm Bit0 =. Reset state Technical Support/Service