Emerson OpenComms-485 manual Bit0 =. Reset state

Page 38

REV. 5 7/6/2007

Liebert Monitoring Group –Development

Free cooling run

30146

-

1

Hour

S505

hours

 

 

 

 

 

Electrical Heaters

30147

-

1

Hour

S507

#1 run hours

 

 

 

 

 

Electrical Heaters

30148

-

1

Hour

S508

#2 run hours

 

 

 

 

 

Electrical Heaters

30149

-

1

Hour

S509

#3 run hours

 

 

 

 

 

Hot Water / Hot

30150

-

1

Hour

S506

Gas run hours

 

 

 

 

 

Daily High

30151

-

x10

S313

Temperature

 

 

 

 

 

Daily High Temp

30152

-

x1

Hh:mm

S313

Time

 

 

 

 

 

Daily Low

30153

-

x10

S314

Temperature

 

 

 

 

 

Daily Low Temp

30154

-

x1

Hh:mm

S314

Time

 

 

 

 

 

Daily High

30155

-

x1

%RH

S315

Humidity

 

 

 

 

 

Daily High Hum

30156

-

x1

Hh:mm

S315

Time

 

 

 

 

 

Daily Low

30157

-

x1

%RH

S316

Humidity

 

 

 

 

 

Daily Low Hum

30158

-

x1

Hh:mm

S316

Time

 

 

 

 

 

 

 

 

 

 

 

[1]Any non-recognized alarm code by current firmware received from the DS control will trigger this event.

[2]Timer mode: 0 = no, 1= yes.

[3]Type of DT Room-Glycol: 0 = no, 1=contact, 2=value.

[4]Predictive Hum Control: 0=relative, 1=compensated, 2=predictive.

[5]Temp Control Algorithm: 0=proportional, 1=PD, 2=PDI; 3=intelligent;

[6]When VFD is set to manual mode(coil 22), the host can control the VFD by the value of register 40019. The Manual VSD Timer will start to count down. Once it reaches 0, the VFD control mode will switch to auto. The host will need to periodically reset this timer in order to maintain the manual mode. Consult factory for BMS timer information.

[7]Operating State: Bit 0-1: 00 unit off, 01 unit on, 10 unit standby

Bit 2-3: 00 auto, 01 manual

Bit 4-7:

0000 none,

 

0001 local user,

 

0010 alarm,

 

0011 schedule,

 

0100 remote user,

 

0101 external device,

 

0110 local display

[8] Alarm state bit map:

Bit0 =. Reset state

 

bit1 =

Active state ;

 

bit2 =

Acknowledge state,

bit3-7 = Alarm Type,:

00000: Message

 

00001: Warning

 

00010: Alarm

[9] Free-cool state: 0= Off, 1= Start, 2= On.

35

Image 38
Contents Monitoring Revision Level Updates Table of Contents Connectivity to OpenComms-485 using Modbus Modbus CommunicationsModbus Packet Format RTU Framing Liebert Nfinity Status Coil Scale RegInput Holding Register Scale REV 7/6/2007 Liebert Monitoring Group -Development Liebert Nx Data Point Status Coil # of Reg ScaleREV 7/6/2007 Liebert Monitoring Group -Development Data Point Input Register Holding Register # of Reg Scale Data Point Register Coil # of Reg Scale 100 VAR Liebert PowerSure Interactive Data Point Status Coil # of RegInput Holding Data Point Register # of Reg Scale REV 7/6/2007 Liebert Monitoring Group -Development Supported Modbus Points Data Point Input Register Holding Register # of Reg Scale REV 7/6/2007 Liebert Monitoring Group -Development Liebert GXT2 Status Coil # of Reg ScaleREV 7/6/2007 Liebert Monitoring Group -Development Input Register Holding Register # of Reg Scale REV 7/6/2007 Liebert Monitoring Group -Development # of Reg Scale Liebert HiNetInput Holding Register Liebert UPS Series Data PointInput Holding Scale Register REV 7/6/2007 Liebert Monitoring Group -Development Liebert UPS Series Battery Charger Fail 10234 REV 7/6/2007 Liebert Monitoring Group -Development Liebert DS Data points Mapped to Input Status and CoilsMain FAN Overload Sensor a Failure Data Points Mapped to Input and Holding Registers HourMinute Sleep Interval 30042 40042 MSBHr Events/Alarm Bit0 =. Reset state Technical Support/Service