Emerson OpenComms-485 manual Liebert UPS Series

Page 29

REV. 5 7/6/2007

Liebert Monitoring Group –Development

Liebert UPS Series 300

Supported Modbus Points

Data Point

Status

Coil

# of

Scale

Notes / Units

 

 

 

Reg.

 

 

Automatic Restart

10001

1

1

1

 

Enabled

 

 

 

 

 

Battery Charge

10046

 

1

1

 

Compensation

 

 

 

 

 

Inverter Ready

10047

 

1

1

 

Load Circuit 1 State

10057

 

1

1

 

Load Circuit 2 State

10058

 

1

1

 

Load Circuit 3 State

10059

 

1

1

 

Load Circuit 4 State

10060

 

1

1

 

Load Circuit 5 State

10061

 

1

1

 

Load Circuit 6 State

10062

 

1

1

 

Load Circuit 7 State

10063

 

1

1

 

Load Circuit 8 State

10064

 

1

1

 

Load Circuit 9 State

10065

 

1

1

 

Load Circuit 10 State

10066

 

1

1

 

Load Circuit 11 State

10067

 

1

1

 

Load Circuit 12 State

10068

 

1

1

 

Load Circuit 13 State

10069

 

1

1

 

Load Circuit 14 State

10070

 

1

1

 

Load Circuit 15 State

10071

 

1

1

 

Load Circuit 16 State

10072

 

1

1

 

Load On Inverter

10073

 

1

1

 

Bypass Active

10074

 

1

1

 

Buck On

10076

 

1

1

 

Replace Battery

10081

 

1

1

 

Battery Under Test

10082

 

1

1

 

Load On Battery

10128

 

1

1

 

Low Battery -

10152

 

1

1

 

Shutdown Imminent

 

 

 

 

 

Output Overload

10154

 

1

1

 

Over Temperature

10171

 

1

1

 

Warning

 

 

 

 

 

Battery Over

10172

 

1

1

 

Temperature CB Trip

 

 

 

 

 

Input Power Supply

10186

 

1

1

 

Fail

 

 

 

 

 

Input Over Voltage

10187

 

1

1

 

Input Under Voltage

10188

 

1

1

 

Bad Input Frequency

10190

 

1

1

 

Bypass Input

10202

 

1

1

 

Voltage/Frequency

 

 

 

 

 

Fault

 

 

 

 

 

Output Under Voltage

10218

 

1

1

 

Output Over Voltage

10219

 

1

1

 

26

Image 29
Contents Monitoring Revision Level Updates Table of Contents Modbus Communications Connectivity to OpenComms-485 using ModbusModbus Packet Format RTU Framing Status Coil Scale Reg Liebert NfinityInput Holding Register Scale REV 7/6/2007 Liebert Monitoring Group -Development Data Point Status Coil # of Reg Scale Liebert NxREV 7/6/2007 Liebert Monitoring Group -Development Data Point Input Register Holding Register # of Reg Scale Data Point Register Coil # of Reg Scale 100 VAR Data Point Status Coil # of Reg Liebert PowerSure InteractiveInput Holding Data Point Register # of Reg Scale REV 7/6/2007 Liebert Monitoring Group -Development Supported Modbus Points Data Point Input Register Holding Register # of Reg Scale REV 7/6/2007 Liebert Monitoring Group -Development Status Coil # of Reg Scale Liebert GXT2REV 7/6/2007 Liebert Monitoring Group -Development Input Register Holding Register # of Reg Scale REV 7/6/2007 Liebert Monitoring Group -Development # of Reg Scale Liebert HiNetInput Holding Register Data Point Liebert UPS SeriesInput Holding Scale Register REV 7/6/2007 Liebert Monitoring Group -Development Liebert UPS Series Battery Charger Fail 10234 REV 7/6/2007 Liebert Monitoring Group -Development Data points Mapped to Input Status and Coils Liebert DSMain FAN Overload Sensor a Failure Data Points Mapped to Input and Holding Registers HourMinute Sleep Interval 30042 40042 MSBHr Events/Alarm Bit0 =. Reset state Technical Support/Service