REV. 5 7/6/2007
Liebert Monitoring Group
Input Current L2 | 30204 | 1 | 1 | A |
Input Voltage L3 | 30253 | 1 | 1 | V |
Input Current L3 | 30254 | 1 | 1 | A |
|
|
|
|
|
Liebert UPS Series 600
Supported Modbus Points
Data Point | Status | Coil | # of | Scale | Notes / Units |
|
|
| Reg. |
|
|
Battery Charger On | 10044 |
| 1 | 1 |
|
Battery Charge | 10046 |
| 1 | 1 |
|
Compensation |
|
|
|
|
|
Inverter Ready | 10047 |
| 1 | 1 |
|
Auto Retransfer | 10049 |
| 1 | 1 |
|
Primed |
|
|
|
|
|
Load On Inverter | 10073 |
| 1 | 1 |
|
Load On Bypass | 10074 |
| 1 | 1 |
|
Buck On | 10076 |
| 1 | 1 |
|
Battery data Buffer Full | 10084 |
| 1 | 1 |
|
Shutdown Reason – | 10096 |
| 1 | 1 |
|
Hardware |
|
|
|
|
|
Load On Battery | 10128 |
| 1 | 1 |
|
Manual Reset Transfer | 10130 |
| 1 | 1 |
|
Load On Bypass | 10133 |
| 1 | 1 |
|
Permanent |
|
|
|
|
|
Load On | 10134 |
| 1 | 1 |
|
fault |
|
|
|
|
|
Battery Switch Open | 10136 |
| 1 | 1 |
|
Input Switch Open | 10137 |
| 1 | 1 |
|
Output Switch open | 10138 |
| 1 | 1 |
|
Emergency Load | 10145 |
| 1 | 1 |
|
Transfer to Inverter |
|
|
|
|
|
Transfer inhibited – | 10146 |
| 1 | 1 |
|
Asynchronous |
|
|
|
|
|
Sources |
|
|
|
|
|
Transfer inhibited – | 10147 |
| 1 | 1 |
|
over predefined limit |
|
|
|
|
|
SBS SCR Open | 10149 |
| 1 | 1 |
|
SBS SCR Short | 10150 |
| 1 | 1 |
|
Low Battery - | 10152 |
| 1 | 1 |
|
Shutdown Imminent |
|
|
|
|
|
Output Overload | 10154 |
| 1 | 1 |
|
Over Temperature | 10171 |
| 1 | 1 |
|
Warning |
|
|
|
|
|
Battery Over | 10172 |
| 1 | 1 |
|
Temperature CB Trip |
|
|
|
|
|
Input Power Supply | 10186 |
| 1 | 1 |
|
Fail |
|
|
|
|
|
Input Under Voltage | 10188 |
| 1 | 1 |
|
Input Brown Out | 10189 |
| 1 | 1 |
|
|
|
|
|
|
|
23