Troubleshooting
Table
Problem | Possible Cause | Solution |
|
|
|
No output voltage; OVER | Thermal shutdown. | Allow the unit to cool off. |
TEMP indicator on; load is |
| Reduce the load if continuous |
more than 1000 W / 8 A |
| operation is required. |
output current. The AMPS |
|
|
indicator is showing high |
|
|
battery current. |
|
|
|
|
|
No output voltage; the OVER | Thermal shutdown. | Improve ventilation; make sure the |
TEMP indicator is on; the |
| inverter’s ventilation openings are not |
load is less than 1000 W / 8 A |
| obstructed; reduce the ambient |
output current. |
| temperature. |
|
|
|
No output voltage; the OVER | Short circuit or wiring error. | Check the AC wiring for a short circuit |
LOAD indicator is on. |
| or improper polarity (hot and neutral |
|
| reversed). |
| Very high power load. | Remove the load. |
|
|
|