Xantrex Technology XDI2048 User Diagnostics, Emergency Shutdown, Unusual or Erratic Operation

Page 76

Troubleshooting

User Diagnostics

If your XDI is not performing as described in this manual, run through the procedures and checks in this section before calling your service technician. These procedures are confined to operator-level functions only and do not require cover-off servicing.

Emergency Shutdown

In an emergency, carry out both of these steps:

1.Shut the inverter off immediately.

2.Isolate the power source by turning off the input and output breakers.

Unusual or Erratic Operation

If the inverter displays any unusual or erratic operation, follow these steps:

1.Shut the inverter off immediately.

2.Disconnect the load by turning off the output breaker or load switch.

3.Test the inverter with no load. Check front panel LED status against Table 3-1 on page 3–6 and “Protections and Alarms” on page 3–7.

4.If the tests show that the power supply is functioning normally, check that load, programming, and monitoring connections and circuits.

Refer to Table 5-1, “Inverter Diagnostics” on page 5–3 and Table 5-2, “Ethernet Diagnostics” on page 5–4 for more detailed user diagnostics.

If the problem is not solved by following this procedure, or if the unit fails to operate correctly after additional diagnostics in Table 5-1 and Table 5- 2, call your service technician.

5-2

TM-DIOP-01XN-01

Image 76
Contents XDI2048 2kVA/1.5kW Page Xantrex Datacom Inverter Date and Revision Purpose ScopeAudience OrganizationConventions Used Related InformationImportant Safety Instructions Page Contents Inverter Module Installation and Operation Troubleshooting Remote Communication & MonitoringSpecifications Warranty and Product InformationFigures Xii Tables Xiv Introduction Inverter Information Features and OptionsDescription Features and Functions Ethernet InformationPart Number and Ordering Information XDI2048HV-RMAssembly Initial Inspection Packing ListPackaging for Shipping or Storage 2Shipping or Storage Carton LabelIntroduction Rack Mount Frame Rear ViewInstallation Into Cabinet Style Equipment Racks Location, Mounting and VentilationInstallation into Relay Racks Installing into Relay RacksInput Connector and Cables DC Input PowerDC Input Wire Connection Connecting the Input Wires AC Load and Signal Line Connection AC Output ConnectorLoad Wiring AC Output Voltage WireLoad Connection User Line Connection OverviewUser Line Connector User Line WiringUser Line Connection User Line ConnectionSpecifications CAN/SYNC ConnectorCAN/SYNC Connection CAN/SYNC Pin-out CAN/SYNC WiringTerminals Function Connection Schemes Stand-Alone OperationParallel Operation ConnectionParallel Operation Split-Phase Operation Split Phase OperationLoad Terminal Voltage Three Phase Operation 33-Phase ConfigurationsWiring Output Configuration Terminals Model VoltagePhase Synchronization and Signal Wiring 103-Phase Sync ConnectionPhase, 3-Wire Delta Output Wiring Phase, 3-Wire Y-Connection Output WiringPhase, 4-Wire Y-Connection Output Wiring Ethernet PortPage Operation Installation into Rack Mount Frame Installing an Inverter into a Rack 2Inverter Front PanelTheory of Operation Operation of Inverter ModuleSystem Startup Standby Mode Cooling Fans2User Line Pins User InterfaceFront Panel User LinesProtections and Alarms OverviewInput Voltage Protection Output Voltage ProtectionOverload Protection 3Overload curveOver Temperature Protection OTP Internal DiagnosticsShort-circuit Protection Over-Current protectionFuses and Grounding Output AC AlarmIncorrect Connection Protection Maintenance To Clear an Alarm4Replacing the Fan Filters Monitoring Web-enabled User Interface Initial SetupInitial Setup Ethernet Interface PCBHow to Setup For the First Time Hardware Setup1Default Settings Ethernet SetupSetting Default Value 2User Configured Settings ResettingSettingValue Setting Reset Value 3Reset SettingsRemoving Unit’s Top Cover Ethernet Reset Jumper Operating Instructions Network Connection5Network Setup Using Dhcp What Power On DoesPassword 6Password Confirmation BoxesAutomatic Power-On Email How to Use the Web InterfaceManage Object DescriptionSetup 8Setup Page of Web Interface5Setup Page of Web Interface Monitor 9Monitor Page of Web Interface6Monitor Page of Web Interface Automatic Shutdown Email Code Fault Description Shutdown Code TM-DIOP-01XN-01 Troubleshooting Emergency Shutdown User DiagnosticsUnusual or Erratic Operation 1Inverter Diagnostics Diagnostic GuideSymptom Check 2Ethernet Diagnostics Specifications Inverter Specifications Electrical SpecificationsInverter Specifications Environmental Specifications Regulatory ApprovalsMechanical Specifications Inverter and Rack Mount Frame Dimensions Figure A-1Ethernet Specifications Page Warranty and Product Information WarrantyDisclaimer ProductReturn Material Authorization Policy ExclusionsOut of Warranty Service Return ProcedureInformation About Your System Page Xantrex Technology Inc