Xantrex Technology XDI2048 Fuses and Grounding, Incorrect Connection Protection, Output AC Alarm

Page 52

Inverter Module Installation and Operation

Fuses and Grounding

The inverter is equipped with non-user replaceable, internal fuses for fault protection. The input fuse (fuse F1) is rated at 60 A, 170 Vdc, 100 kA 1R and positioned in the return path. Both L1 and L2 output ports are protected with slow acting fuses (fuses F2 and F3). The fuse ratings are model dependant and as follows:

XDI2048 120 V output: 20 A 250 V

XDI2048 230 V output: 12 A 250 V

Grounding studs are provided adjacent to the DC input and AC output ports. The equipment must be grounded at these locations as required by end applications and local regulations. See Chapter 2, “Rack Mount Frame Assembly and Installation” for connection details.

Incorrect Connection Protection

Input contactor will not close for normal startup with reverse polarity input connection.

The output contactor will not close if AC back feed is detected on power up or if a unit is unable to synchronize to the AC bus.

The output fuse will open for output faults not covered by internal protection circuitry.

Output (AC) Alarm

The following conditions will cause an output alarm:

Output overload

Output short circuit

Output Over-voltage

Over-temperature

Module failure

When such a condition exists,

1.The red FAULT indicator located on the front panel is turned on,

2.The open collector “Fault” alarm output is energized,

3.The output contactor is opened and the inverter output is disabled. Except in the case of an Output Overload when the module will continue to run for a short period, depending on the overload power, prior to shutdown.

3-10

TM-DIOP-01XN-01

Image 52
Contents XDI2048 2kVA/1.5kW Page Xantrex Datacom Inverter Date and Revision Purpose ScopeAudience OrganizationConventions Used Related InformationImportant Safety Instructions Page Contents Inverter Module Installation and Operation Troubleshooting Remote Communication & MonitoringSpecifications Warranty and Product InformationFigures Xii Tables Xiv Introduction Inverter Information Features and OptionsDescription Features and Functions Ethernet InformationPart Number and Ordering Information XDI2048HV-RMAssembly Initial Inspection Packing ListPackaging for Shipping or Storage 2Shipping or Storage Carton LabelIntroduction Rack Mount Frame Rear ViewInstallation Into Cabinet Style Equipment Racks Location, Mounting and VentilationInstallation into Relay Racks Installing into Relay RacksInput Connector and Cables DC Input PowerDC Input Wire Connection Connecting the Input Wires AC Load and Signal Line Connection AC Output ConnectorLoad Wiring AC Output Voltage WireLoad Connection User Line Connection OverviewUser Line Connector User Line WiringUser Line Connection User Line ConnectionSpecifications CAN/SYNC ConnectorCAN/SYNC Connection CAN/SYNC Pin-out CAN/SYNC WiringTerminals Function Connection Schemes Stand-Alone OperationParallel Operation ConnectionParallel Operation Split-Phase Operation Split Phase OperationLoad Terminal Voltage Three Phase Operation 33-Phase ConfigurationsWiring Output Configuration Terminals Model VoltagePhase Synchronization and Signal Wiring 103-Phase Sync ConnectionPhase, 3-Wire Delta Output Wiring Phase, 3-Wire Y-Connection Output WiringPhase, 4-Wire Y-Connection Output Wiring Ethernet PortPage Operation Installation into Rack Mount Frame Installing an Inverter into a Rack 2Inverter Front PanelTheory of Operation Operation of Inverter ModuleSystem Startup Standby Mode Cooling Fans2User Line Pins User InterfaceFront Panel User Lines Protections and Alarms Overview Input Voltage Protection Output Voltage ProtectionOverload Protection 3Overload curveOver Temperature Protection OTP Internal DiagnosticsShort-circuit Protection Over-Current protectionFuses and Grounding Output AC AlarmIncorrect Connection Protection Maintenance To Clear an Alarm4Replacing the Fan Filters Monitoring Web-enabled User Interface Initial SetupInitial Setup Ethernet Interface PCBHow to Setup For the First Time Hardware Setup1Default Settings Ethernet SetupSetting Default Value 2User Configured Settings ResettingSettingValue Setting Reset Value 3Reset SettingsRemoving Unit’s Top Cover Ethernet Reset Jumper Operating Instructions Network Connection5Network Setup Using Dhcp What Power On DoesPassword 6Password Confirmation BoxesAutomatic Power-On Email How to Use the Web InterfaceManage Object DescriptionSetup 8Setup Page of Web Interface5Setup Page of Web Interface Monitor 9Monitor Page of Web Interface6Monitor Page of Web Interface Automatic Shutdown Email Code Fault DescriptionShutdown Code TM-DIOP-01XN-01 Troubleshooting Emergency Shutdown User DiagnosticsUnusual or Erratic Operation 1Inverter Diagnostics Diagnostic GuideSymptom Check 2Ethernet Diagnostics Specifications Inverter Specifications Electrical SpecificationsInverter Specifications Environmental Specifications Regulatory ApprovalsMechanical Specifications Inverter and Rack Mount Frame Dimensions Figure A-1Ethernet Specifications Page Warranty and Product Information WarrantyDisclaimer ProductReturn Material Authorization Policy ExclusionsOut of Warranty Service Return ProcedureInformation About Your System Page Xantrex Technology Inc