Installation and Configuration
IEEE-488 Primary Address Selection
1.Assign a primary address to each power supply: Choose a number between 0 and 30 which is unique to your
2.Locate switch S1 on the GPIB interface rear panel. See “GPIB Interface Subplate” on page 17 for the interface subplate drawing.
3.Use switch positions A1 to A5 to set the primary address for the power supply. See Table 2.2,
Switch 0 = (OFF, OPEN) Switch 1 = (ON, CLOSED)
Table 2.2
Address | A5 | A4 | A3 | A2 | A1 | Address | A5 | A4 | A3 | A2 | A1 |
0 | 0 | 0 | 0 | 0 | 0 | 16 | 1 | 0 | 0 | 0 | 0 |
1 | 0 | 0 | 0 | 0 | 1 | 17 | 1 | 0 | 0 | 0 | 1 |
2 | 0 | 0 | 0 | 1 | 0 | 18 | 1 | 0 | 0 | 1 | 0 |
3 | 0 | 0 | 0 | 1 | 1 | 19 | 1 | 0 | 0 | 1 | 1 |
4 | 0 | 0 | 1 | 0 | 0 | 20 | 1 | 0 | 1 | 0 | 0 |
5 | 0 | 0 | 1 | 0 | 1 | 21 | 1 | 0 | 1 | 0 | 1 |
6 | 0 | 0 | 1 | 1 | 0 | 22 | 1 | 0 | 1 | 1 | 0 |
7 | 0 | 0 | 1 | 1 | 1 | 23 | 1 | 0 | 1 | 1 | 1 |
8 | 0 | 1 | 0 | 0 | 0 | 24 | 1 | 1 | 0 | 0 | 0 |
9 | 0 | 1 | 0 | 0 | 1 | 25 | 1 | 1 | 0 | 0 | 1 |
10 | 0 | 1 | 0 | 1 | 0 | 26 | 1 | 1 | 0 | 1 | 0 |
11 | 0 | 1 | 0 | 1 | 1 | 27 | 1 | 1 | 0 | 1 | 1 |
12 | 0 | 1 | 1 | 0 | 0 | 28 | 1 | 1 | 1 | 0 | 0 |
13 | 0 | 1 | 1 | 0 | 1 | 29 | 1 | 1 | 1 | 0 | 1 |
14 | 0 | 1 | 1 | 1 | 0 | 30 | 1 | 1 | 1 | 1 | 0 |
15 | 0 | 1 | 1 | 1 | 1 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Note: Ensure you assign one address to each GPIB controller board as well.
20 | Operating Manual for GPIB for XPD Series Power Supply |