Chapter 2 Preparing for Installation

Site Requirements

Verify that the enclosed or partially enclosed rack allows an adequate flow of air through the switch chassis as follows:

If the difference between the measured intake air temperature and the exhaust air temperature does not exceed 50°F (10°C), there is sufficient airflow in the rack.

If the difference in air temperature exceeds 50°F (10°C), there is insufficient airflow to cool the chassis.

Note A Cisco ME 6524 Ethernet switch that is currently installed in an enclosed or partially enclosed rack might meet ambient air temperature and air flow requirements now. However, if you add more chassis, the additional heat generated might cause the ambient air temperature within the rack to exceed 104°F (40°C) and can cause minor alarms.

If an individual fan within the assembly fails, the FAN STATUS LED turns red. Individual fans cannot be replaced.

Refer to your software configuration guide for information on environmental monitoring.

Humidity

High-humidity conditions can cause moisture migration and penetration into the system. This moisture can cause corrosion of internal components and degradation of properties such as electrical resistance, thermal conductivity, and physical strength. Extreme moisture buildup inside the system can result in electrical shorts, which can cause serious damage to the system. Each system is rated to operate at 8 to 80 percent relative humidity, with a humidity gradation of 10 percent per hour. In storage, a system can withstand from 5 to 95 percent relative humidity.

Buildings in which climate is controlled by air-conditioning in the warmer months and by heat during the colder months usually maintain an acceptable level of humidity for system equipment. However, if a system is located in an unusually humid location, a dehumidifier can be used to maintain the humidity within an acceptable range.

Altitude

Operating a system at high altitude (low pressure) reduces the efficiency of forced and convection cooling and can result in electrical problems related to arcing and corona effects. This condition can also cause sealed components with internal pressure, such as electrolytic capacitors, to fail or perform at reduced efficiency. The system is certified for operation from 0 to 6500 feet (0 to 2000 m). The system is designed and tested for operation from –200 to 10,000 feet (–60 to 3000 m).

Cisco ME 6500 Series Ethernet Switch Installation Guide

2-4

OL-8900-03

 

 

Image 32
Contents Cisco ME 6500 Series Ethernet Switch Installation Guide Americas HeadquartersPage N T E N T S Where to Go Next Power Supply Specifications OL-8900-03 Chapter Title Description AudienceOrganization Conventions Convention DescriptionStatement 1071-Warning Definition Bewaar Deze InstructiesAviso Instruções Importantes DE Segurança Warnung Wichtige SicherheitshinweiseAvvertenza Importanti Istruzioni Sulla Sicurezza Spara Dessa Anvisningar GEM Disse Anvisninger Xiii Related Documentation Obtaining Documentation and Submitting a Service Request Xvi Cisco ME 6524 Ethernet Switch ME-C6524GS-8S Product OverviewFeature Cisco ME 6524 Ethernet Switch ME-C6524GS-8S-Rear ViewFeature Description Status LED Specification Operational-5 G 30 ms, half-sine IEC Cisco ME 6524 Ethernet Switch ME-C6524GT-8S Cisco ME 6524 Ethernet Switch ME-C6524GT-8S-Front ViewCisco ME 6524 Ethernet Switch ME-C6524GT-8S-Rear View Cisco ME 6524 Ethernet Switch ME-C6524GT-8S Features Status LED Cisco ME 6524 Ethernet Switch ME-C6524GT-8S Specifications Operational-5 G 30 ms, half-sine IEC Preparing for Installation SafetyPreparing for Installation Safety Temperature and Air Circulation Site RequirementsHumidity AltitudeElectromagnetic and Radio Frequency Interference Dust and ContaminationCorrosion Shock and Vibration System GroundingElectromagnetic Environment Grounding RecommendationsPreventing Electrostatic Discharge Damage Preparing for Installation Site Requirements Power Requirements Power Connection Guidelines for AC-Powered Systems Power Connection Guidelines for DC-Powered SystemsSite Preparation Checklist Cabling RequirementsTask No. Planning Activity Verified By Time Installing the Switch Preparing for InstallationOL-8900-03 Installing the Switch Preparing for Installation Required Tools Verifying Package ContentsRack-Mounting Installing the Rack-Mount Brackets Attaching L Brackets to the ChassisInstalling the Chassis in the Rack Installing the Chassis in the Rack Desk-Top MountingInstalling the System Ground Installing the Rubber FeetConnecting Source Power to the Chassis Installing the System GroundConnecting Source DC to the DC-Input Power Supply Connecting the Console Port Connecting Source AC to the AC-Input Power SupplyInstalling the SFP Transceivers Receive optical bore Transmit optical bore Bail claspInstalling an SFP Transceiver into an SFP Transceiver Socket Installing the Switch Installing the SFP Transceivers Powering Up the Chassis Where to Go NextOL-8900-03 Removal and Replacement Procedures Removing and Installing the DC-Input Power SupplyRemoving the DC-Input Power Supply Removing the DC-Input Power Supply Installing the DC-Input Power Supply Page Removing and Installing the AC-Input Power Supply Installing the DC-Input Power SupplyRemoving the AC-Input Power Supply IEC 60320 C15 connectorRemoving and Installing the Fan Tray Installing the AC-Input Power SupplyInstalling the Fan Tray Removing the Fan TrayUpgrading the Memory Location of SP and RP Dram DIMMs Connector edge of the Dimm into the socket connector Installing the Dram Dimm in the Dimm Socket OL-8900-03 Power Supply Specifications DC-Input Power SupplyFAN OK AC-Input Power Supply Specification DescriptionGreen-Source AC voltage is OK. Input voltage is 82 VAC or Power Supply AC Power Cords Locale Power CordFigure A-4 CAB-ACA Australia and New Zealand Power Cord Figure A-7 CAB-ACE Continental Europe Power Cord Figure A-10 CAB-ACU United Kingdom Power Cord SFP Transceiver Specifications Modal SFP TransceiverCore Size Bandwidth Type Fiber Type Micron MHz/km Cable DistanceMB SFP Transceiver Transmit dBm Receive dBm Product Number GB SFP Transceiver Transmit dBm Receive dBm Product NumberColor Code Cwdm Gbic Wavelength Dwdm SFP Description ITU Channel Product NumberDwdm SFP Numerics IN-2 IN-3 IN-4
Related manuals
Manual 14 pages 28.35 Kb

ME 6500 specifications

The Cisco Systems ME 6500 is a sophisticated Ethernet switch designed to cater to the demanding needs of service providers and large enterprises. Engineered to deliver high performance and reliability, the ME 6500 series is ideal for both metro Ethernet applications and data center environments. One of its standout features is the ability to handle massive bandwidth, making it suitable for high-capacity networks. The switch supports a range of Ethernet services that facilitate seamless connectivity and network expansion.

At the core of the ME 6500 is its ability to provide Layer 2 and Layer 3 functionalities, which allows for flexibility in network design. This dual-layer capability enhances the switch's efficiency in managing traffic and ensures optimal forwarding of data packets. In addition, the ME 6500 series supports a wide range of Ethernet interfaces, including 10 Gigabit and 1 Gigabit Ethernet ports, which are essential for accommodating diverse bandwidth requirements.

One of the defining characteristics of the Cisco ME 6500 is its scalability. It supports up to 192 10 Gigabit Ethernet ports within a single chassis, enabling organizations to expand their network without compromising performance. Furthermore, the switch includes advanced Quality of Service (QoS) features that allow for traffic prioritization, which is crucial for maintaining the performance of voice and video services across the network.

The ME 6500 switch is also equipped with robust security features, including Access Control Lists (ACLs) and secure management protocols. These features protect sensitive data as it traverses the network, ensuring that only authorized users have access to critical resources. Management of the switch is simplified through Cisco’s management tools, allowing network administrators to monitor, configure, and troubleshoot the device efficiently.

Additionally, the switch supports various redundancy protocols, including Rapid Spanning Tree Protocol (RSTP) and Link Aggregation Control Protocol (LACP), ensuring high availability and minimizing downtime.

Overall, the Cisco ME 6500 is a powerful and versatile solution that meets the heavy demands of modern network environments, delivering outstanding performance, security, and scalability for both service providers and large enterprises. Its advanced features make it a go-to choice for organizations looking to future-proof their networking infrastructure.