1Serial Port Connection

Using the serial cable provided, connect the serial port on your computer to the serial port of your UPS. Install on your computer the PowerAlert UPS monitoring software pro- gram (included on CD-ROM) appropriate for your operating system. See Communications in the Basic Operation section of this manual to determine how to monitor and manage your UPS using this port.

2External Battery Pack Connection

Check to ensure that the external batteries you are connecting match the voltage listed on your UPS's battery connector. Plug either end of the battery connection cable (supplied with the battery pack) into the UPS’s External Battery Connector and the other end into the Battery Output Connector on the rear panel of the external battery pack. Since your UPS has internal batteries, external batteries are only needed to extend runtime. Adding external batteries will increase recharge time as well as runtime. Make sure that each end of the cable is fully inserted into its connector. Several small sparks may result during battery connection; this is normal.

1

SU2200XL shown

SU2200XL shown

SU1000T shown

 

2

 

ImportantBasicOperationSafety Instructions

Front Panel Switches

“ON/TEST” Switch: This switch controls four separate UPS functions:

UPS Power ON: To turn the UPS on, press this switch, hold it for several seconds until you hear a beep, then release it. The “ON LINE” LED will illuminate.

UPS Self-Test: During normal on-line operation, press this switch and hold it until you hear a beep. This initiates a 10-second self-test of the battery. The UPS will shift to battery power (the “ON BATT” and “BATTACTIVE METER” LEDs will illuminate) for ten seconds.

Alarm Silence: To silence the UPS “on-battery” alarm, press this switch and hold it until you hear a beep.

UPS Cold Start: To use your UPS as a stand-alone power source when AC power is unavailable (i.e. during a blackout), press this switch and hold it until you hear a beep. The UPS will then provide bat- tery power to its outlets.*

*The “ON BATT” Indicator Light will be illuminated since your UPS will be operating from battery power.

“OFF” Switch: This switch turns power OFF at the UPS receptacles. Press this switch, hold it until you hear a beep, then release it. The UPS will continue charging and the fan will continue to cool internal components even after you turn the UPS receptacles off. To turn the UPS OFF completely, including the charger, disconnect the UPS’s power cord after pressing the “OFF” switch.

Front Panel Indicator Lights

“ON LINE” LED: This green light will be lit when the UPS is in normal on-line operation (filtering and resynthesizing incoming AC line voltage to provide pure sine wave output). When this light is illuminated, you can monitor the load level of your UPS on the “LOAD ACTIVE METER” LEDs.

“LINE” LED: This green light will be lit when the utility-supplied AC line voltage at your wall outlet is nominal. It will flash if the line voltage or frequency is outside the nominal range (either too low or too high). No action is required on your part when the LED flashes; the UPS continuously and automatically filters AC line power to pro- vide your equipment with pure sine wave AC power, regardless of brownout or overvoltage conditions. If this light is off, then AC line voltage is not present (blackout) or is at an extremely high voltage.

4

5

Image 3
Contents SmartOnline Turn your UPS on Important Safety InstructionsPlug your UPS into an electrical outlet Plug your equipment into your UPSFront Panel Indicator Lights ImportantBasicOperationSafety InstructionsExternal Battery Pack Connection Front Panel SwitchesRear Panel Check the utility line for wiring problems Restart the UPS. If the problem persistsCommunications Or low for the UPS to operate in Bypass This indicates that utility power is too highProperly. Restart the UPS. If the problem ServiceManual del usuario Encienda su sistema UPS on Importantes instrucciones de seguridadConecte su UPS en un tomacorriente Enchufe su equipo al sistema UPSLuces indicadoras del panel frontal Conexión de puerto serialConexión del paquete de baterías externas Interruptores del panel frontalOperación básica continuación Luces indicadoras del panel frontal continuaciónPanel posterior Condición Reemplazar batería Condición Error de EepromPanel posterior continuación ComunicacionesAlmacenamiento y servicio continuación Localización de fallas continuaciónImportantes consignes de sécurité Guide de lutilisateurInstallation suite Voyants du panneau avant OrtantImExploitationtySafde baseInstructionsExploitation de base suite Commutateurs du panneau avantPanneau arrière suite Panneau arrièreDépannage suite Entretien Entreposage

SU3000XL, SU1000XL, SU2200XL specifications

Tripp Lite is known for its reliable power protection solutions, and the SU3000XL, SU2200XL, and SU1000XL series of uninterruptible power supplies (UPS) exemplify this commitment. Each model is designed to provide high-performance power protection for servers, networking equipment, and critical electronic devices, ensuring that operational continuity is maintained even during power interruptions.

The SU3000XL is a robust solution offering 3000VA / 2400W capacity. It features sine wave output, which is essential for the safe functioning of sensitive electronics. With multiple output options, including a variety of outlets, the SU3000XL supports a wide range of devices. This model also incorporates advanced technologies like Automatic Voltage Regulation (AVR), which stabilizes voltage levels, ensuring connected devices receive clean and consistent power. Additionally, the UPS is equipped with an LCD display, providing real-time monitoring of power conditions, battery status, and load levels.

The SU2200XL presents a versatile 2200VA / 1980W capacity. Similar to the SU3000XL, it offers sine wave output and AVR technology. Its compact design makes it suitable for smaller setups without compromising power availability. The SU2200XL is an ideal choice for businesses or home environments that require dependable backup power for vital systems while maintaining energy efficiency. Built-in USB and serial connectivity allow users to integrate with management software, enabling seamless power management and monitoring.

For environments with lower power needs, the SU1000XL delivers a capacity of 1000VA / 800W. This model is particularly well-suited for desktops, workstations, and smaller network devices. Despite its smaller capacity, the SU1000XL does not skimp on features. It also includes sine wave output and AVR technology, providing the essential power protection that Tripp Lite is known for. An easy-to-read LED display presents vital information at a glance, making it user-friendly.

All three models boast hot-swappable batteries, allowing for easy maintenance without downtime. Furthermore, they come with a variety of safety features, including surge protection and short circuit protection, enhancing their reliability. With a focus on durability, Tripp Lite’s UPS systems are built to last, backed by a solid warranty and customer support. Overall, the SU3000XL, SU2200XL, and SU1000XL ensure that users can trust their power sources, no matter the requirements.