ConneXium™ Ethernet Gateway
Setup
Modbus TCP/IP Filtering
63230-319-211A1 2/2006
This function allows the administrator to specify Modbus TCP/IP client devices that have or do not have access to serial slave devices connected to the ETG.
NOTE: There is an anonymous Modbus TCP/IP address (***.***.***.***) that can be set to
| Action | Result |
|
|
|
1. | From the Setup page, click Modbus | Opens the Modbus TCP/IP Filtering page. |
| TCP/IP Filtering. |
|
|
|
|
2. | Check Enable Filtering. | Activates filtering. |
|
|
|
3. | In the IP address column, enter the | Enters an IP address for a Modbus TCP/IP |
| Modbus TCP/IP client address | client that will have access to the serial devices |
|
| connected to the ETG. |
|
|
|
4. | In the Access Level column, select Read- | Selects the access level for the corresponding |
| only or Full. | IP address. When set to |
|
| following Modbus TCP/IP function codes are |
|
| allowed: |
|
| Decimal: 1, 2, 3, 4, 7, 8, 11, 12, 17, 20, 24, |
|
| 43, 100 |
|
| Hexadecimal: 01, 02, 03, 04, 07, 08, 0B, 0C, |
|
| 11, 14, 18, 2B, 64 |
|
|
|
5. | Repeat steps 3 and 4 to add more IP | Continues adding IP addresses for filtering. |
| addresses. |
|
|
|
|
6. | Click Apply. | Saves the Modbus TCP/IP address filtering list. |
|
|
|
Figure 10: Modbus TCP/IP Filtering Page