Schneider Electric TSXETG100 Modbus TCP/IP Filtering, TCP/IP Filtering Check Enable Filtering

Page 12

ENGLISH

ConneXiumEthernet Gateway

Setup

Modbus TCP/IP Filtering

63230-319-211A1 2/2006

This function allows the administrator to specify Modbus TCP/IP client devices that have or do not have access to serial slave devices connected to the ETG.

NOTE: There is an anonymous Modbus TCP/IP address (***.***.***.***) that can be set to Read-only or None. Setting it to Read-onlyallows any Modbus TCP/IP client not in the filtered list to access serial slave devices with read-only access. Setting it to None blocks all Modbus TCP/IP clients not in the filtered list.

 

Action

Result

 

 

 

1.

From the Setup page, click Modbus

Opens the Modbus TCP/IP Filtering page.

 

TCP/IP Filtering.

 

 

 

 

2.

Check Enable Filtering.

Activates filtering.

 

 

 

3.

In the IP address column, enter the

Enters an IP address for a Modbus TCP/IP

 

Modbus TCP/IP client address

client that will have access to the serial devices

 

 

connected to the ETG.

 

 

 

4.

In the Access Level column, select Read-

Selects the access level for the corresponding

 

only or Full.

IP address. When set to Read-only, only the

 

 

following Modbus TCP/IP function codes are

 

 

allowed:

 

 

Decimal: 1, 2, 3, 4, 7, 8, 11, 12, 17, 20, 24,

 

 

43, 100

 

 

Hexadecimal: 01, 02, 03, 04, 07, 08, 0B, 0C,

 

 

11, 14, 18, 2B, 64

 

 

 

5.

Repeat steps 3 and 4 to add more IP

Continues adding IP addresses for filtering.

 

addresses.

 

 

 

 

6.

Click Apply.

Saves the Modbus TCP/IP address filtering list.

 

 

 

Figure 10: Modbus TCP/IP Filtering Page

12

© 2006 Schneider Electric. All Rights Reserved.

Image 12
Contents Table of Contents ConneXium Ethernet Gateway TSXETG100Address Resolution Protocol ARP ARP is used to convert IP IntroductionSupported Ethernet Protocols HardwareAccessing the ETG Over a Network Additional ResourcesLogging into the ETG Logging OutSetup DiagnosticsETG User Interface Overview ETG static web pagesSetup Ethernet and TCP/IP Settings63230-319-211A1 ConneXium Ethernet Gateway 2006 Setup Option Description SettingConneXium Ethernet Gateway 63230-319-211A1 Setup 2006 Scenario Duplicate IP Detected Power/Status LEDDuplicate IP Address Detection Duplicate IP Detection Scenarios2006 Setup Default MasterDefault Even Default 3 secondsFor master mode usage of the COM port Master Mode Device List Setup Master Mode TopologyDevice List Before you begin, keep in mind the followingSlave Mode Device List Setup Slave Mode TopologyEthernet Connection ETG RS485ETG accounts and passwords ConneXium Ethernet Gateway SetupAccount Default Password User AccountsWeb Page Access Group AccessGroup Access AccessTCP/IP Filtering Check Enable Filtering Modbus TCP/IP FilteringSnmp Parameters ParametersDiagnostics ConneXium Ethernet Gateway 63230-319-211A1 Diagnostics 2006Statistics Menu bar2006 Diagnostics Interpreting StatisticsStatistic Description EthernetConneXium Ethernet Gateway Diagnostics Serial PortGateway Information ETG Read Device Register Settings Option Description DefaultRead Device Registers Firmware Finding the Firmware VersionGetting New Firmware Updating the Firmware FileDeutsch