Schneider Electric Comprehensive TSXETG100 Manual and ETG100 Installation Guide

Page 2

ENGLISH

ConneXiumEthernet Gateway

63230-319-211A1

Introduction

2/2006

 

 

INTRODUCTION

This manual is to be used with a ConneXiumETG100 with firmware

 

version 2.0 or higher. For installation information, see the installation guide.

 

The ETG100 is a communications device that provides connectivity

 

between Ethernet (Modbus TCP/IP) and serial line devices, allowing

 

Modbus TCP/IP clients to access information from serial slave devices. It

 

also allows serial master devices to access information from slave devices

 

distributed across an Ethernet network.

Supported Ethernet Protocols

The ETG supports the following Ethernet protocols:

 

Modbus TCP/IP: Modbus TCP/IP is a combination of the Modbus

 

protocol, which provides master-slave communication between devices,

 

and TCP/IP, which provides communications over an Ethernet

 

connection. Modbus TCP/IP is used to exchange data between the ETG

 

and other compatible Modbus TCP/IP devices via TCP port 502.

 

Hypertext Transfer Protocol (HTTP): HTTP is a network protocol that

 

handles the delivery of files and data on the World Wide Web. It

 

provides web server functionality via TCP port 80. Remote configuration

 

of the ETG and the viewing of diagnostic data is possible using a web

 

browser.

 

File Transfer Protocol (FTP): FTP is a network protocol that provides

 

the ability to transfer files over the Internet from one computer to

 

another. FTP is used to transfer firmware updates to the ETG via TCP

 

port 21.

 

Simple Network Management Protocol (SNMP): Based on MIB2

 

format, SNMP provides the ability to store and send identifying and

 

diagnostic information used for network management purposes via UDP

 

port 161 .

 

Address Resolution Protocol (ARP): ARP is used to convert IP

 

addresses to Ethernet addresses. ARP requests are sent by the ETG to

 

determine if its address is a duplicate IP address (see “Duplicate IP

 

Address Detection” on page 6).

Hardware

 

RJ45 Ethernet port

Control power

LEDs for Ethernet and serial communications

Power and Status LED

Reset button

RS485 serial port

Bias, termination, and 2-wire/4-wire jumper switches

RS232 serial port (RJ45 connector)

2

© 2006 Schneider Electric. All Rights Reserved.

Image 2
Contents Table of Contents ConneXium Ethernet Gateway TSXETG100Supported Ethernet Protocols Address Resolution Protocol ARP ARP is used to convert IPIntroduction HardwareLogging into the ETG Accessing the ETG Over a NetworkAdditional Resources Logging OutETG User Interface Overview SetupDiagnostics ETG static web pages63230-319-211A1 ConneXium Ethernet Gateway 2006 Setup SetupEthernet and TCP/IP Settings Option Description SettingDuplicate IP Address Detection ConneXium Ethernet Gateway 63230-319-211A1 Setup 2006Scenario Duplicate IP Detected Power/Status LED Duplicate IP Detection ScenariosDefault Even 2006 SetupDefault Master Default 3 secondsDevice List For master mode usage of the COM portMaster Mode Device List Setup Master Mode Topology Before you begin, keep in mind the followingEthernet Connection ETG Slave Mode Device List SetupSlave Mode Topology RS485Account Default Password ETG accounts and passwordsConneXium Ethernet Gateway Setup User AccountsGroup Access Web Page AccessGroup Access AccessTCP/IP Filtering Check Enable Filtering Modbus TCP/IP FilteringSnmp Parameters ParametersStatistics DiagnosticsConneXium Ethernet Gateway 63230-319-211A1 Diagnostics 2006 Menu barStatistic Description 2006 DiagnosticsInterpreting Statistics EthernetGateway Information ConneXium Ethernet Gateway DiagnosticsSerial Port Read Device Registers ETG Read Device Register SettingsOption Description Default Getting New Firmware FirmwareFinding the Firmware Version Updating the Firmware FileDeutsch