Schneider Electric TSXETG100 manual ConneXium Ethernet Gateway Diagnostics, Serial Port

Page 16

ConneXiumEthernet Gateway

Diagnostics

ENGLISH

 

63230-319-211A1

 

2/2006

 

 

Statistic

Description

 

 

Serial Port

 

 

 

Frames Sent

A counter that increments each time a frame is

 

sent.

 

 

Frames Received

A counter that increments each time a frame is

 

received.

 

 

CRC Errors

A counter that increments each time a

 

message is received that has a CRC that does

 

not match what is calculated. Typically the

 

result of wiring issues.

 

 

Protocol Errors

A counter that increments each time an ill-

 

formed message is received.

 

 

Timeouts

A counter that increments each time a request

 

message is sent without receiving a

 

corresponding response message within the

 

allowed time. Timeouts are typically the result

 

of configuration errors or a non-responsive

 

device.

 

 

Inbound Read Messagesd

A counter that increments each time a read

 

request message is received.

 

 

Outbound Read Messagesc

A counter that increments each time a read

 

request message is sent.

 

 

Inbound Write Messagesd

A counter that increments each time a write

 

request message is received.

 

 

Outbound Write Messagesc

A counter that increments each time a write

 

request message is sent.

 

 

Gateway Information

 

 

 

Firmware Version

The firmware version that is installed on the

 

ETG.

 

 

System Idle Time

A percentage from 0% to 100% indicating the

 

average processor time that is not being used.

 

 

MAC Address

The unique Ethernet hardware address of an

 

ETG.

 

 

Serial Number

The serial number of the ETG.

 

 

Model Number

The ETG model number (100).

 

 

Hardware Version

ETG hardware version.

 

 

Manufacture Date

Date the ETG was manufactured.

 

 

cAvailable when the serial port is in Master mode.

dAvailable when the serial port is in Slave mode

16

© 2006 Schneider Electric. All Rights Reserved.

Image 16
Contents Table of Contents ConneXium Ethernet Gateway TSXETG100Address Resolution Protocol ARP ARP is used to convert IP IntroductionSupported Ethernet Protocols HardwareAccessing the ETG Over a Network Additional ResourcesLogging into the ETG Logging OutSetup DiagnosticsETG User Interface Overview ETG static web pagesSetup Ethernet and TCP/IP Settings63230-319-211A1 ConneXium Ethernet Gateway 2006 Setup Option Description SettingConneXium Ethernet Gateway 63230-319-211A1 Setup 2006 Scenario Duplicate IP Detected Power/Status LEDDuplicate IP Address Detection Duplicate IP Detection Scenarios2006 Setup Default MasterDefault Even Default 3 secondsFor master mode usage of the COM port Master Mode Device List Setup Master Mode TopologyDevice List Before you begin, keep in mind the followingSlave Mode Device List Setup Slave Mode TopologyEthernet Connection ETG RS485ETG accounts and passwords ConneXium Ethernet Gateway SetupAccount Default Password User AccountsWeb Page Access Group AccessGroup Access AccessTCP/IP Filtering Check Enable Filtering Modbus TCP/IP FilteringSnmp Parameters ParametersDiagnostics ConneXium Ethernet Gateway 63230-319-211A1 Diagnostics 2006Statistics Menu bar2006 Diagnostics Interpreting StatisticsStatistic Description EthernetSerial Port ConneXium Ethernet Gateway DiagnosticsGateway Information Option Description Default ETG Read Device Register SettingsRead Device Registers Firmware Finding the Firmware VersionGetting New Firmware Updating the Firmware FileDeutsch