5000/6000 VA models:

Terminal Mode is a menu driven interface that enables enhanced configuration of the UPS. Connect the serial cable to the serial port on the back of the UPS.

1.Open a terminal program. Example: HyperTerminal

From the Desktop, go to Start => Programs => Accessories => Communication =>HyperTerminal.

2.Double-click on the HyperTerminal icon.

Follow the prompts to choose a name and select an icon. Disregard the message, “...must install a modem,” if it is displayed. Click OK.

Select the COM port that is connected to your UPS. The port settings are:

9bits per second - 2400

9data - bits 8

9parity - none

9stop bit - 1

9flow control - none

Press ENTER

3.Example for setting the number of external battery packs (SURT192XLBP):

Once the blank terminal window is open, follow these steps to enter the number of battery packs:

Press ENTER to initiate terminal mode. Press ENTER multiple times, until the prompt User Name: is displayed. Follow the prompts. Type slowly, waiting until each character appears on the screen prior to typing the next character.

Network Management Card defaults:

User Name: apc

Password: apc

Press 1 and ENTER to select Device Manager.

Select the model by entering the corresponding number, then press ENTER.

Press 3 and ENTER to select Configuration.

Press 1 and ENTER to select Battery.

Press 2 and ENTER to change the Battery Settings.

Type in the number of external battery packs (four battery modules per pack), then press ENTER. (Number of packs: 1= internal battery module,

2 = 1 SURT192XLBP, 3 = 2 SURT192XLBP, etc.)

Press 3 and ENTER to accept the changes.

Press ESC multiple times (5) to return to the main menu.

Press 4 and ENTER to log out.

.

11

Image 13
Contents 3000/5000/6000 VA 200-240 Vac Tower/Rack Mount 3U Uninterruptible Power SupplySmart-UPS RT User ManualPage INSTALLATION SpecificationsRead the Safety Guide before installing the UPS IntroductionWiring and Connecting the UPS CONNECTING THE BATTERY MODULES AND ATTACHING THE FRONT BEZEL When connecting grounding cable, disconnect the unit from the utility connectorpower outlet Use only interface kits supplied or approved by APC2. Avoid using extension cords OPERATION The UPS starts a self-test as part of this procedure. The self-test On Battery Operationdoes not affect the voltage display DEFAULT USER CONFIGURABLE ITEMSFUNCTION FACTORYAdhere to National and local electrical codes when wiring the EPO 9 bits per second 9 data - bits 9 parity - none 9 stop bit Services9 flow control - none 5000/6000 VA models MAINTENANCE AND TRANSPORT Replacing the Battery ModuleBe careful during battery replacement, the battery modules are heavy X YZ \The batterys may remain in the UPS Disconnecting the Battery for TransportREPLACING BATTERY MODULES PROBLEM AND POSSIBLE TROUBLESHOOTING, SERVICE, AND WARRANTY INFORMATIONSOLUTION CAUSEFAULT LED ILLUMINATES FAULT AND OVERLOAD LEDS ILLUMINATE, UPS EMITS A SUSTAINED ALARM TONEREPLACE BATTERY LED ILLUMINATES UPS OPERATES ON BATTERY ALTHOUGH NORMAL LINE VOLTAGE EXISTSLimited Warranty ServiceRadio Frequency Warnings APC Worldwide Customer SupportREGULATORY