5000/6000 VA XLI MODELS ONLY: HARDWIRING INSTRUCTIONS

Wiring must be performed by a qualified electrician.

Install a high magnetic 30/32 A utility circuit breaker.

Adhere to all national and local electrical codes.

Use #10 AWG gauge (5 mm2) wire.

1.Switch the utility circuit breaker OFF.

2.Remove the input access panel.

3.Remove circular knockout.

4.Run #10 AWG gauge (5 mm2) wire through the access panel, and connect the wires to the terminal block (green: ground, brown: hot, blue: neutral). Use an appropriate strain relief (not included).

5.Switch the utility circuit breaker ON.

6.Check line voltages.

7.Replace the access panel.

2

Image 4
Contents Uninterruptible Power Supply 3000/5000/6000 VA 200-240 Vac Tower/Rack Mount 3USmart-UPS RT User ManualPage Specifications INSTALLATIONRead the Safety Guide before installing the UPS IntroductionWiring and Connecting the UPS CONNECTING THE BATTERY MODULES AND ATTACHING THE FRONT BEZEL connector When connecting grounding cable, disconnect the unit from the utilitypower outlet Use only interface kits supplied or approved by APC2. Avoid using extension cords OPERATION The UPS starts a self-test as part of this procedure. The self-test On Battery Operationdoes not affect the voltage display USER CONFIGURABLE ITEMS DEFAULTFUNCTION FACTORYAdhere to National and local electrical codes when wiring the EPO 9 bits per second 9 data - bits 9 parity - none 9 stop bit Services9 flow control - none 5000/6000 VA models Replacing the Battery Module MAINTENANCE AND TRANSPORTBe careful during battery replacement, the battery modules are heavy X YZ \The batterys may remain in the UPS Disconnecting the Battery for TransportREPLACING BATTERY MODULES TROUBLESHOOTING, SERVICE, AND WARRANTY INFORMATION PROBLEM AND POSSIBLESOLUTION CAUSEFAULT AND OVERLOAD LEDS ILLUMINATE, UPS EMITS A SUSTAINED ALARM TONE FAULT LED ILLUMINATESREPLACE BATTERY LED ILLUMINATES UPS OPERATES ON BATTERY ALTHOUGH NORMAL LINE VOLTAGE EXISTSService Limited WarrantyRadio Frequency Warnings APC Worldwide Customer SupportREGULATORY
Related manuals
Manual 17 pages 55.36 Kb