Schneider Electric 5000, 3000 Replacing the Battery Module, X Yz, Maintenance And Transport

Page 14
MAINTENANCE AND TRANSPORT

MAINTENANCE AND TRANSPORT

Replacing the Battery Module

This UPS has an easy to replace, hot-swappable battery module. Replacement is a safe procedure, isolated from electrical hazards. You may leave the UPS and connected equipment on during the procedure. See your dealer or contact APC at the Web site, www.apc.com for information on replacement battery modules.

The battery replacement procedure must include replacing all battery modules in the UPS and connected external battery pack(s).

Once the battery(s) are disconnected, the connected equipment is not protected from power outages.

Be careful during battery replacement, the battery modules are heavy.

Be sure to deliver spent batteries to a recycling facility or ship to the manufacturer in the replacement battery packing material.

REMOVING BATTERY MODULES

X YZ

[\

12

Image 14
Contents Smart-UPS RT Uninterruptible Power Supply3000/5000/6000 VA 200-240 Vac Tower/Rack Mount 3U User ManualPage Read the Safety Guide before installing the UPS SpecificationsINSTALLATION IntroductionWiring and Connecting the UPS CONNECTING THE BATTERY MODULES AND ATTACHING THE FRONT BEZEL power outlet connectorWhen connecting grounding cable, disconnect the unit from the utility Use only interface kits supplied or approved by APC2. Avoid using extension cords OPERATION does not affect the voltage display On Battery OperationThe UPS starts a self-test as part of this procedure. The self-test FUNCTION USER CONFIGURABLE ITEMSDEFAULT FACTORYAdhere to National and local electrical codes when wiring the EPO 9 flow control - none Services9 bits per second 9 data - bits 9 parity - none 9 stop bit 5000/6000 VA models Be careful during battery replacement, the battery modules are heavy Replacing the Battery ModuleMAINTENANCE AND TRANSPORT X YZ \REPLACING BATTERY MODULES Disconnecting the Battery for TransportThe batterys may remain in the UPS SOLUTION TROUBLESHOOTING, SERVICE, AND WARRANTY INFORMATIONPROBLEM AND POSSIBLE CAUSEREPLACE BATTERY LED ILLUMINATES FAULT AND OVERLOAD LEDS ILLUMINATE, UPS EMITS A SUSTAINED ALARM TONEFAULT LED ILLUMINATES UPS OPERATES ON BATTERY ALTHOUGH NORMAL LINE VOLTAGE EXISTSService Limited WarrantyREGULATORY APC Worldwide Customer SupportRadio Frequency Warnings