Schneider Electric 3000, 5000 user manual On Battery Operation, does not affect the voltage display

Page 9
The UPS starts a self-test as part of this procedure. The self-test

Feature

Function

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Cold Start

When there is no utility power and the UPS is off, press and hold the

 

button to

 

 

 

 

 

 

 

power up the UPS and connected equipment.

 

 

 

 

 

The UPS will emit two beeps. During the second beep, release the button.

 

 

 

 

 

 

 

 

 

 

 

 

 

Self-Test

Automatic: The UPS performs a self-test automatically when turned on, and every

 

 

 

two weeks thereafter (by default). During the self-test, the UPS briefly operates the

 

 

 

connected equipment on battery.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Manual: Press and hold the

 

button for a few seconds to initiate the self-test.

 

 

 

 

 

 

 

 

 

 

 

 

Diagnostic Utility Voltage

The UPS has a diagnostic feature that displays the utility voltage. Plug

 

 

 

 

 

the UPS into the normal utility power.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

The UPS starts a self-test as part of this procedure. The self-test

 

 

 

 

 

does not affect the voltage display.

 

 

 

 

 

 

 

Press and hold the

 

button to view the utility voltage bar graph

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

display. After a few seconds the five-LED, Battery Charge

 

display

 

 

 

 

 

 

 

 

 

 

 

on the right of the front panel shows the utility input voltage.

 

 

 

 

 

Refer to the figure at left for the voltage reading (values are not listed

 

 

 

 

 

on the UPS).

 

 

 

 

 

 

 

 

 

 

The display indicates the voltage is between the displayed value on the

 

 

 

 

 

list and the next higher value.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

On Battery Operation

The UPS switches to battery operation automatically if the utility power fails. While running on battery, an alarm beeps four times every 30 seconds.

Press the does not affect the voltage display. button to silence this alarm. If the utility power does not return, the UPS continues to supply power to the connected equipment until the battery is fully discharged.

When 2 minutes of run time remain the UPS emits a continuous beeping. If PowerChute is not being used, files must be manually saved and the computer must be turned off before the UPS fully discharges the battery.

The UPS battery life differs based on usage and environment. Refer to www.apc.com, for on battery runtimes.

.

7

Image 9
Contents 3000/5000/6000 VA 200-240 Vac Tower/Rack Mount 3U Uninterruptible Power SupplySmart-UPS RT User ManualPage INSTALLATION SpecificationsRead the Safety Guide before installing the UPS IntroductionWiring and Connecting the UPS CONNECTING THE BATTERY MODULES AND ATTACHING THE FRONT BEZEL When connecting grounding cable, disconnect the unit from the utility connectorpower outlet Use only interface kits supplied or approved by APC2. Avoid using extension cords OPERATION On Battery Operation The UPS starts a self-test as part of this procedure. The self-testdoes not affect the voltage display DEFAULT USER CONFIGURABLE ITEMSFUNCTION FACTORYAdhere to National and local electrical codes when wiring the EPO Services 9 bits per second 9 data - bits 9 parity - none 9 stop bit9 flow control - none 5000/6000 VA models MAINTENANCE AND TRANSPORT Replacing the Battery ModuleBe careful during battery replacement, the battery modules are heavy X YZ \Disconnecting the Battery for Transport The batterys may remain in the UPSREPLACING BATTERY MODULES PROBLEM AND POSSIBLE TROUBLESHOOTING, SERVICE, AND WARRANTY INFORMATIONSOLUTION CAUSEFAULT LED ILLUMINATES FAULT AND OVERLOAD LEDS ILLUMINATE, UPS EMITS A SUSTAINED ALARM TONEREPLACE BATTERY LED ILLUMINATES UPS OPERATES ON BATTERY ALTHOUGH NORMAL LINE VOLTAGE EXISTSLimited Warranty ServiceAPC Worldwide Customer Support Radio Frequency WarningsREGULATORY