Data centers frequently devote a separate subnet to system management. If your data center has such a configuration, connect the network management port to this subnet.
Note – The network management port is a
▼To Activate the Network Management Port
1.Connect an Ethernet cable to the network management port.
2.Log in to the ALOM system controller through the serial management port.
For more information about connecting to the serial management port, see “Accessing the System Controller” on page 16.
3.Type one of the following commands:
■ If your network uses static IP addresses, type:
sc> setsc if_network true
sc> setsc netsc_ipaddr
■If your network uses Dynamic Host Configuration Protocol (DHCP), type:
sc> setsc netsc_dhcp
4.Enter the following so that the new settings will take affect:
sc> resetsc
5.To verify the network settings, type:
sc> shownetwork
6. Log out of the ALOM system controller session.
18 Netra 440 Server System Administration Guide • August 2004