Power control port

The MC5-IP models provide a serial port for connection to one or more optional power control units. This allows you to control the mains power being supplied to the connected computer(s) so that an authorised user can, if necessary, perform a complete remote cold reboot on a failed system.

LOCAL

REMOTE

GLOBAL

USER

USER

USER

 

U S

IP

POWER

 

MODEM

IN

 

/ISDN

CAM

 

 

COMPUTER

POWER

SYSTEM

SWITCH

To connect and address the switch boxes

Note: The MC5-IP unit can be powered on during this procedure, however, the switch boxes should be switched off.

1Mount up to four switch boxes in positions where they are close to the computer systems that they will control and not too distant from the MC5-IP unit (preferably within 2.5 metres).

2 Use a serial cable with an RJ9 and a 9-pin D-type connector (see Appendix

7 for specification). Attach the RJ9 plug to the socket marked IN on the first

switch box. Attach the other end to the socket marked POWER CONTROL on



The control connector of the first power switch is attached, via serial cable, to the rear panel of the MC5-IP. Any additional power switches are then attached via a ‘daisy-chain’ arrangement to the first power switch. Each power switch box is then given a unique address and access to each power port (8 ports on each power switch box) is gained using a combination of the switch box address and the port number.

‘Daisy-chain’

 

 

 

 

 

 

 

 

Power

control

 

 

KVM Switch

 

 

 

 

switch

connections

 

 

 

 

 

 

 

 

boxes

 

IN

1

2

3

4

5

6

7

8

Box 1

 

 

 

 

 

 

 

 

 

 

 

OUT

 

 

 

 

 

 

 

 

 

IN

1

2

3

4

5

6

7

8

Box 2

 

 

 

 

 

 

 

 

 

 

OUT

Power to computer

Box 2, port 6 - address: 26

IN

1

2

3

4

5

6

7

8

Box 3

 

 

 

 

 

 

 

 

OUT

 

 

 

 

 

 

 

 

IN

1

2

3

4

5

6

7

8

Box 4

 

 

 

 

 

 

 

 

The power ports are connected to the power inputs of each computer system and the power switch box(es) are then connected to a mains power supply.

IMPORTANT: Power switching devices have a maximum current rating. It is essential to ensure that the total current drawn by the equipment connected to the power switching device does not exceed the current rating of the power switching device. You must also ensure that the current drawn from any mains socket does not exceed the current rating of the mains socket.

Setting up, configuring and using power switching requires three main steps:

Connect and address the switch boxes ð

Configure the power strings

Operate power switching via configuration menu or via viewer

the MC5-IP.

MC5 rear panel

Serial cable to first power switch box

3For each of the remaining switch boxes (if used), use a serial cable with RJ9 connectors at both ends (see Appendix 7 for specification). Attach one end to the socket marked OUT of the previous box and the other end to the socket marked IN of the next box.

4

Set the addressing switches on each switch

Box

Switch 1

Switch 2

 

box using the two micro switches marked

 

1

Off

Off

 

‘Slct’ on the front panel. The box connected

 

directly to the MC5-IP is Box 1 and so on,

2

On

Off

 

down the daisy-chain line to Box 4 at the

3

Off

On

 

end.

 

4

On

On

5

Attach IEC to IEC power leads between

 

 

 

each port and the power input socket of each computer system that requires power switching. Carefully note to which power

ports, on which boxes, each computer system is connected. If computer systems have multiple power inputs, then each input must be connected via separate ports, which can be on the same, or different boxes.

6 Connect each box to a suitable mains power input.

Now proceed to the configuration stage covered in the Power switching configuration section within the Configuration chapter.

  



15

Image 16
Contents MC5-IP KVM Switch Contents Further information Index Local user One user can be connected directly to the MC5  Many computers CAM formatsMC5 features front and rear IndicatorsPower control port Upgrade port Modem port IP models only Front panel buttonsWhat’s in the box What you may additionally need SwitcMounting Rack bracketsConnections   To connect the local user port Local userMC5 rear panel Cable lengths for remote user locations Remote user via User StationTo connect a remote user To connect the Global user IP network port Global user IP network portIP network link To connect a computer system Access ModuleCategory 5, 5e or Cable from CAM To connect a modem or Isdn adapter Modem/ISDN portMC5 rear panel Cable from modem Or Isdn adapter To connect the power supply Power in connectionOutput lead from Power adapter Power control port To connect and address the switch boxesSee also Cascading multiple unitsCascade tree How cascade connections operate Addressing computers in a cascade 43 41Tips for successful cascading Connecting MC5 units in cascadeTo connect units in cascade Testing specific links to cascaded computers Using cascaded computersTo test a specific link Multiple video head connections Slave MC5Master MC5 Slave monitor Master monitorConfiguration Overall initial configurationConfiguration menus To access the configuration menu local and remote usersTo access the configuration menu global users HotkeysGeneral security and configuration steps Configuration menus layoutTo enable general security To set an Admin passwordAccess to all computers Press Access to no computers Press Registering users edit user listTo create/edit user accounts Cross markers indicate whichRegistering computers edit computer list Tips when creating/editing computer entriesTo create/edit computer entries See Remote user skew adjustment for details Video compensationComputer video compensation To apply computer video compensationCompensation will not be applied Currently selected cable lengthRemote user video compensation To display a suitable high contrast imageTo apply remote user video compensation If the image controls cannot provide a crisp imageRemote user skew adjustment To use skew adjustmentUsing the supplied skew pattern Creating a skew test patternConfiguration mode and permanently save all settings To select an autoscan mode AutoscanningTo select an autoscan period To define an autoscan listSaving and restoring configuration settings Preparations for configuration save/loadTo reset MC5 models What to do if the Admin password has been forgottenTo reset the MC5-IP models Which restore setting do I use? To restore mouse operation when hot pluggingHot plugging and mouse restoration Recognising an IntelliMouse-style mouseTo use the initial IP-configuration sequence Initial IP configurationTo configure IP-specific settings IP configuration by global user To configure IP details from a global user locationMC5-IP encryption settings Encryption settingsViewer encryption settings Positioning the MC5-IP in the network Networking issues   Port settings Placing the MC5-IP behind a router or firewallAddressing Firewall/router addressTo discover a DHCP-allocated IP address DNS addressingEnsuring sufficient security Placing the MC5-IP alongside the firewallPorts Power switching configuration Power control sequencesTo configure the power sequences for each host computer To control two or more ports simultaneouslyKvmadmin utility Kvmadmin command ip address parametersKvmadmin -getconfig kvm1.cfg Kvmadmin -setusers users.csvPerforming upgrades Items required to use the upgrade utilityUpgrading MC5 models and CAMs To use the KVM Firmware Uploader utilitySelect the items to be upgraded Select the upgrade file to be usedWhere Vxxx is the upgrade file version number Commence the upgradeTo upgrade MC5-IP models Upgrading MC5-IP modelsAccessing the MC5 Front panel controlsMC5 models MC5-IP modelsLocal and remote user access To gain access as a local or remote userTo select a computer using the front panel controls Selecting a computerTo select a computer using hotkeys Standard hotkeysAbove or for even longer cascaded computers Keep Pressed down until all other Numbers have been enteredTo select a computer using mouse buttons To select a computer using the on-screen menuTo select a computer using mouse buttons Advanced method Selecting cascaded computers Logging in and outConfirmation box To change banner colours or disable the banner To use the Routing status featureReminder banner Routing statusTo switch a computer on or off Power switching via configuration menuUser preferences and functions Global user access Global user access via VNC viewer To access via the VNC viewerTo download the VNC viewer 1 Open your Web browser Enter the MC5 address here and click OKGlobal user access via web browser To access via your web browserWhen using the viewer window Using the viewer windowMenu bar Mouse pointers ConfigureTo select a host Access mode shared/private Power switching via viewerAuto calibrate Re-synchronise mouseSingle Mouse Mode ControlsMouse Control Resync MouseKVM switch menu When entering codesVideo Settings Keyboard Control InfoUsing automatic configurations Increased by 50% when a slow link is detectedDetect such noise and adjust the threshold accordingly Setting the Threshold manuallyAccess via dial up modem or Isdn link If you need to enter a port numberTo initiate a dial up link To enter a port number in a Web browserViewer encryption settings Supported web browsersWindows LinuxTroubleshooting Getting assistanceAppendix 1 Configuration menus To access the configuration menusFunctions User Preferences Mouse Switching Autoscan ModeGlobal Preferences Screen SaverUser Timeout OSD Dwell TimeRS232 Mouse Type Mouse TypeSetup Options Keypads ControlsLanguage Exclusive UseAutomatic Logout DDC Source Settings AUTO, LOCAL, Default DDC Refresh Settings AT START, DisabledAdvanced Options DDC OptionsConfigure IP port Unit ConfigurationUnit Name Time and DateNetwork Configuration Modem Configuration Reset ConfigurationWhat is IP access control? Clearing IP access controlTo clear IP access control To access the remote configuration pages Appendix 2 Configuration pages via viewerMain configuration Logged on users User accounts Unit configuration Admin PasswordHardware Version Firmware VersionAdvanced unit configuration Time & date configuration Network configuration IP Access ControlMAC address IP Network MaskSetting IP access control To define a new IP access control entryTo reorder access control entries To edit/remove access control entriesPower control port Serial port configurationModem port Host configuration Erase Host ConfigurationAdd entry for unrecognised host To create a new host entryPort Direct Port/host addressing using Port DirectExamples Logging and status To copy and paste the logSyslog Server IP Address For further details To get hereClick here to access the options Colour/EncodingAuto select Preferred encodingEnable all inputs Disable all inputs view-only modeInputs CustomiseScaling MiscDefaults Reload Defaults SaveIdentities Load / SaveAppendix 4 VNC viewer window options Encoding and colour level Appendix 5 Browser viewer optionsSecurity IP addresses Appendix 6 Addresses, masks and portsNet masks Net masks the binary explanation Inside a bit-wise and functionBinary equivalent Binary octet afterCalculating the mask for IP access control Single locationsAll locations Address rangesPorts Security issues with portsRouter/firewall address Power switch to power switch daisy chain cable RS232 serial flash upgrade cable6pin mini-DIN Female 9pin D-type FemaleMulti-head synchronisation cable SLAVE2 end 9pin D-type malePermissible key presses Appendix 8 Hotkey sequence codesCreating macro sequences Appendix 9 Supported video modes Warranty Safety informationSafety considerations when using power switches with MC5 General Public License LinuxEnd user licence agreement European EMC directive 89/336/EEC Radio Frequency EnergyFCC Compliance Statement United States USA Germany France ItaliaIndex 109 110

MC5-IP specifications

The Lindy MC5-IP is an innovative and versatile presentation switcher designed for a variety of audiovisual settings, making it ideal for professional environments such as conferences, classrooms, and event spaces. Its primary objective is to provide seamless connectivity and efficient management of multiple video sources, enhancing the overall user experience in presentations and broadcasts.

One of the standout features of the MC5-IP is its capability to handle multiple input formats. It supports HDMI, DisplayPort, and VGA connections, allowing users to easily switch between various devices such as laptops, projectors, and media players. This flexibility promotes a smooth transition during presentations, minimizing downtime and interruptions.

The device is equipped with cutting-edge video processing technology, which ensures high-quality output at resolutions up to 4K. This high definition support is crucial in today’s digital landscape, as it provides crystal-clear images and vibrant colors, essential for impactful presentations. Furthermore, the MC5-IP employs advanced scaling technology that adjusts the output resolution to match the capabilities of the connected display, ensuring optimal visual quality.

Integration capabilities are another highlight of the MC5-IP. It can be easily integrated into existing AV systems and works seamlessly with popular control systems, such as Crestron and AMX. This compatibility allows for centralized control, making it easier for operators to manage video sources, adjust settings, and coordinate multiple displays without the need for complex setups.

In addition, the Lindy MC5-IP features an intuitive user interface that simplifies operation. The device can be controlled via a touch screen, remote control, or web-based application, providing users with convenient options to manage their presentations. The user-friendly design minimizes the learning curve, making it accessible for individuals who may not be tech-savvy.

The MC5-IP also prioritizes reliability and durability. It is built with high-quality components that ensure long-term performance, making it a dependable choice for frequently used environments. Finally, its compact form factor allows for easy transport and installation, catering to the dynamic needs of modern presentation scenarios.

In summary, the Lindy MC5-IP is a robust presentation switcher designed with professionalism in mind. Its versatility, high-resolution support, integration options, user-friendly interface, and durability make it an essential tool for anyone looking to enhance their AV presentations.