Delta DVPEN01-SL operation manual Rtu, „ The settings

Page 28

Ethernet Communication Module DVPEN01-SL

receiving register

In data exchange, DVPEN01-SL will execute Write (Æ) first before Read (Å).

Quantity: A slave is able to send and receive at the same time maximum 100 consecutive data.

fFor data exchange, D register is parted into 2 sections, D0000 ~ D4095 and D4096 ~ D9999. Please DO NOT use different sections for the consecutive sent and received data (start address + number of data).

5.See “Application Examples Section 6.11” for more details.

5.6RTU

Use the “RTU” function to conduct mapping between Delta’s network modules DVPEN01-SL and RTU-EN01.Set up the mapping information first, and you will be able to use WPLSoft in DVPEN01-SL to save and retrieve the mapped bit (M) and register (D) in order to operate the remote RTU-EN01.

„The settings

1.Enable Remote I/O Mapping:

Check the box to enable the remote I/O mapping. The mapping with remote RTU-EN01 will be enabled according to the settings.

2.Communication Parameters:

Set up “Communication Timeout” (ms) and “Update Cycle” (ms) here.

3.PLC I/O Mapping:

Set up the start address of the mapped bit and analog register (RCR) of digital input (X) and digital output (Y) on remoter RTU-EN01. The bit starts from M2000, and read/write register starts from D2000/D3000. The software will automatically calculate the end address according to the settings below.

4.Remote Device Mapping:

Check “Enable” and enter the remote RTU-EN01 ID (Slave ID), IP Address, number of digital input points (RX), number of digital output points (RY), number of mapped read registers (Read) and write register (Write).

DVPEN01-SL offers 4 slaves for mapping. Max. number of digital and analog points for mapping

26

DVP-PLC Operation Manual

Image 28
Contents DVPEN01-SL Page Table of Contents Application Examples Specifications FunctionsDimension Product ProfilesInstallation LED IndicatorsRJ-45 PIN Definition Control Register CR Control Registers in DVPEN01-SLEthernet Communication Module DVPEN01-SL Explanations on CR „ E-mail Functions„ Data Exchange Ethernet Communication Module DVPEN01-SL „ Sending Modbus TCP Instruction Ethernet Communication Module DVPEN01-SL Numbering of Left-Side Modules „ RTU MappingSetting up Communication & Searching for Modules „ Communication settings„ Broadcast search „ Designating model to search Ethernet Communication Module DVPEN01-SL „ Searching by IP address „ Opening DVPEN01-SL setup page by RS-232 Basic Settings „ Setting up DVPEN01-SL basicsNetwork Settings „ Setting up static IP of the PCEthernet Communication Module DVPEN01-SL „ Setting up DVPEN01-SL Network DhcpSetting up E-Mails „ Setting up DVPEN01-SL mail„ Setting up DVPEN01-SL data exchange Data Exchange„ The settings RTUIP Filter „ Setting up IP filterStatic ARP Table „ Setting up static ARP table Setting up Password„ Setting up DVPEN01-SL password Returning to Default Setting „ DVPEN01-SL returning to default settingSetting up IP and Communicating through WPLSoft Application ExamplesEthernet Communication Module DVPEN01-SL Open Basic setup Switch to Network setup Connecting the PC with DVPEN01-SL through LAN DVPEN01 DVP-PLC Ethernet Communication Module DVPEN01-SL Ethernet Communication Module DVPEN01-SL Setting up Password and Clearing Password Ethernet Communication Module DVPEN01-SL After the password is cleared, you can modify the parameters IP Filter Protection Ethernet Communication Module DVPEN01-SL Setting up Static ARP Table Ethernet Communication Module DVPEN01-SL Application of E-Mail Application of Data Exchange ExplanationsEthernet Communication Module DVPEN01-SL TRD Application of Data Exchange Ethernet Communication Module DVPEN01-SL Ethernet Communication Module DVPEN01-SL From Explanations Data exchange will be executed every one second Application of Modbus TCP Master RTU Mapping Ethernet Communication Module DVPEN01-SL Ethernet Communication Module DVPEN01-SL