Delta DVPEN01-SL operation manual „ Data Exchange

Page 11

Ethernet Communication Module DVPEN01-SL

CR#7 ~ 8: Status of E-Mail 1 ~ 4

Explanations:

1.CR#7_b0 ~ b7: current status of E-Mail 2; CR#7_b8 ~ b15: current status of E-Mail 1.

2.CR#8_b0 ~ b7: current status of E-Mail 4; CR#8_b8 ~ b15: current status of E-Mail 3.

3.Table of E-Mail status

CR value

E-Mail status

0

Not been sent

 

 

1

Being processed

 

 

2

E-Mail sending is successful

 

 

10

Fail to connect to SMTP-Server

 

 

11

Incorrect recipient E-Mail address

 

 

12

SMTP-Server communication error

 

 

13

Exceeding the max. number of TCP connection

 

 

3 ~ 9, 14 ~ 255

Reserved

 

 

CR#9 ~ 12: E-Mail 1 ~ 4 Additional Message

Explanations:

The user fills in the code, and the code will be stored in the title of the E-Mail and sent out with the E-Mail.

„Data Exchange

CR#13: Data Exchange Trigger

Explanations:

When the CR is set as “0”, the data in data exchange area will not be transmitted. When the CR is set as “1”, the data in data exchange area will be transmitted.

fWhen the Execute Mode in the software is set to “Program Control” (See 5.5), set CR#13 to 2, and the data exchange will continue to execute. Set CR#13 to 0 to stop the data exchange.

fWhen the Execute Mode in the software is set to “Always Enable”, the data exchange will

continue to execute whatever the setting in CR#13 is.

(Firmware V2.0 and later versions support continuous execution of data exchange.)

CR#14: Data Exchange Status

Explanations:

When the CR is set as “0”, the data have not yet been received. When the CR is set as “1”, the data exchange is in progress. When the CR is set as “2”, the data exchange is successful. When the CR is set as “3”, the data exchange fails.

DVP-PLC Operation Manual

9

Image 11
Contents DVPEN01-SL Page Table of Contents Application Examples Functions SpecificationsProduct Profiles DimensionRJ-45 PIN Definition LED IndicatorsInstallation Control Registers in DVPEN01-SL Control Register CREthernet Communication Module DVPEN01-SL „ E-mail Functions Explanations on CR„ Data Exchange Ethernet Communication Module DVPEN01-SL „ Sending Modbus TCP Instruction Ethernet Communication Module DVPEN01-SL „ RTU Mapping Numbering of Left-Side Modules„ Communication settings Setting up Communication & Searching for Modules„ Broadcast search „ Designating model to search Ethernet Communication Module DVPEN01-SL „ Searching by IP address „ Opening DVPEN01-SL setup page by RS-232 „ Setting up DVPEN01-SL basics Basic Settings„ Setting up static IP of the PC Network SettingsEthernet Communication Module DVPEN01-SL Dhcp „ Setting up DVPEN01-SL Network„ Setting up DVPEN01-SL mail Setting up E-MailsData Exchange „ Setting up DVPEN01-SL data exchangeRTU „ The settingsStatic ARP Table „ Setting up IP filterIP Filter „ Setting up DVPEN01-SL password Setting up Password„ Setting up static ARP table „ DVPEN01-SL returning to default setting Returning to Default SettingApplication Examples Setting up IP and Communicating through WPLSoftEthernet Communication Module DVPEN01-SL Open Basic setup Switch to Network setup Connecting the PC with DVPEN01-SL through LAN DVPEN01 DVP-PLC Ethernet Communication Module DVPEN01-SL Ethernet Communication Module DVPEN01-SL Setting up Password and Clearing Password Ethernet Communication Module DVPEN01-SL After the password is cleared, you can modify the parameters IP Filter Protection Ethernet Communication Module DVPEN01-SL Setting up Static ARP Table Ethernet Communication Module DVPEN01-SL Application of E-Mail Explanations Application of Data ExchangeEthernet Communication Module DVPEN01-SL TRD Application of Data Exchange Ethernet Communication Module DVPEN01-SL Ethernet Communication Module DVPEN01-SL From Explanations Data exchange will be executed every one second Application of Modbus TCP Master RTU Mapping Ethernet Communication Module DVPEN01-SL Ethernet Communication Module DVPEN01-SL