Ethernet Communication Module DVPEN01-SL 
6.12 Application of Data Exchange (5)
Application
Network requirement
Writing the time in RTC in PLC_B directly into D0 ~ D6 of PLC_A without writing in ladder diagram into PLC_A.
(1)Adopting static IP.
(2)IP of PLC_A: 192.168.0.4
(3)IP of PLC_B: 192.168.0.5
(4)Update from PLC_B to PLC_A.
1.See 6.1 for how to set up communication.
2.Compile the ladder diagram in the MPU and download it to PLC_B. We do not need to write any corresponding ladder diagram into PLC_A.
M1000
M1013 M2 M1
M1
M2
 = D14 K2 ![]()
= D14 K3 ![]()
TRD | D100  | 
  | 
  | 
  | 
SET  | M1  | 
  | 
  | 
  | 
TOP  | K100  | K28  | K0  | K1  | 
TOP  | K100  | K26  | HC0A8  | K1  | 
TOP  | K100  | K25  | H4  | K1  | 
TOP  | K100  | K81  | H1000  | K1  | 
TOP  | K100  | K84  | H1000  | K1  | 
TOP  | K100  | K85  | K7  | K1  | 
TOP  | K100  | K86  | H1064  | K1  | 
TOP  | K100  | K14  | K0  | K1  | 
TOP  | K100  | K13  | K1  | K1  | 
SET  | M2  | 
  | 
  | 
  | 
RST  | M1  | 
  | 
  | 
  | 
FROM  | K100  | K14  | D14  | K1  | 
RST M2
RST M2
END
Explanations:
•The data exchange will be executed every one second.
52  |