Compaq R6000 manual Causes Action Shutdown within, Seconds

Page 88

Troubleshooting 6-3

Shutdown within 30 seconds Audible Alarm

Table 6-3

Shutdown within 30 seconds Audible Alarm

Audible Alarm Group

Audible Alarm Sound

Cause(s)

Action

 

 

 

 

Shutdown within 30

Accelerated beeping.

Over-temperature.

Check the ambient

seconds

Begins slowly, and gains

 

temperature in the

 

speed as the UPS

 

room. Refer to Appendix

 

approaches shutdown.

 

C, “Environmental

 

UPS shuts down 30 sec

 

Specifications”

 

 

 

 

after audible alarm

 

If the ambient

 

begins.

 

temperature is within

 

 

 

range and the over

 

 

 

temperature alarm is

 

 

 

chronic, contact an

 

 

 

authorized service

 

 

 

provider.

 

 

 

 

 

 

Overload.

Reduce the load. See

 

 

 

section “Connecting

 

 

 

Loads” in Chapter 2

 

 

 

 

 

 

Low battery.

Check the LCD display

 

 

 

(Meters, Battery Volts)

 

 

 

 

 

 

If a shutdown delay has

No action needed.

 

 

been programmed, the

 

 

 

accelerated alarm begins

 

 

 

before the last segment

 

 

 

shutoff.

 

 

 

 

 

 

 

Occurs during the last

No action needed.

 

 

minute of sleep timer if

 

 

 

the Sleep mode is

 

 

 

enabled.

 

 

 

 

 

Image 88
Contents Compaq R6000 Series UPS Operation and Reference Guide Page Contents Operation Configuration Appendix B About This Guide Symbols in TextText Conventions Symbols on Equipment Viii Compaq R6000 Series UPS Operation and Reference GuideGetting Help Rack StabilityCompaq Technical Support Compaq Website Compaq Authorized Reseller Introduction Compaq R6000 UPS Series ModelsCompaq R6000 UPS Series Models UPS Model Part Number CommentsFront Panel R6000 front panelRear Panel Compaq R6000 UPS Features Communication PortsFront Panel LEDs LED MeaningSolid green means normal operation Flashing green means StandbyFront Panel Controls and LCD Display Control Name FunctionPower Management Software Compaq Power Management SoftwareHardware Options Hardware OptionsUPS Option Cards Option Part NumberCase Option Card MatrixScalable Compaq Multi-Server UPS Card Multi-Server UPS CardCompaq Scalable UPS Card Scalable UPS CardCompaq SNMP-EN Adapter SNMP-EN AdapterPower Distribution Units PDUs Extended Runtime Modules ERMsRemote Emergency Power Off Repo Port Warranty$25,000 Computer Load Protection Guarantee Pre-Failure Battery Warranty Installation Important Safety Instructions About This DeviceWeight Installation ConsiderationsPosition Outline of Installation Procedure Unpacking the UPS Check Battery Recharge LabelPreparing the Rack Assembling the Compaq R6000 UPS Placing UPS in rackPlacing chassis in rack Wiring the Compaq R6000 UPS 8Compaq R6000 Series UPS Operation and Reference Guide Risk of Fire Notice Electrical Safety Requirements Connecting the Compaq R6000 UPS to AC Branch CircuitHigh Leakage Current Procedure RecommendationInput Wiring Removing terminal input block coverInstall and connect the battery packs Sliding battery packs into chassisConnect cables 11. Connecting battery packs to the Compaq R6000 UPS Attaching Front Top Bezel 12. Attaching the top front bezelInstalling Extended Runtime Modules ERMs Connecting Communications Ports Connecting Communication Ports to Other DevicesInstalling and Connecting Communication Options Connecting LoadsLoad Segments Description Ordering Extra Power Cords Configuring Load SegmentsLoad Effect on Backup Time Attaching the Load SegmentsCompleting the Assembly R6000 UPS in the Rack 16. Placing the battery circuit breaker in the on positionPowering up the R6000 UPS Turning on the Main Circuit BreakerPressing the on button Shutting Down the SystemInstallation is Now Complete Charging BatteriesOperation Front Panel Controls Front Panel Indicators Front Panel LCDFront Panel LEDs Ref # Description Standby Mode Modes of OperationBattery Mode Audible Alarm Initiating a Self-testSilencing an Audible Alarm Silencing an audible alarmConfiguration Changing Configuration ParametersVoltage Ranges VAC Matching the Utility VoltageRange Configuring the Compaq R6000 UPS Using the LCD Display Menu LCD display, showing the three buttons that control itInitial Power-Up Display LCD Display Menu StructureTop Level Main Menu Sub-Menu ChoicesStatus UPS Status + Load Segment statusUPS Status + Active Alarm Count On BatteryLoad Power Off Load Power OnMeters OverloadInput Volts Output VoltsActive Alarms Output PowerBattery Volts Output FrequencyInput AC Over Voltage Input AC Under VoltageInput Over or Under Frequency Output OverloadInverter Fault Battery LowBattery Totally Discharged UPS on BatteryBattery Test Failed Battery DataSite Wiring Fault Firmware Version Load Control Display TestSystem Setup Set Hardware HW ConfigurationBattery Setup Set LanguageSet Alarm Horn Set PasswordCommunications Setup Set Sync Range ±HertzSerial Port Baud RateData Bits Stop BitsParity Set Sleep Mode Set Site FaultSet Voltage Battery Maintenance Precautions When to Replace Batteries Obtaining New BatteriesRemoving the Battery Packs How to Replace BatteriesBefore Replacing Batteries Place the battery circuit breaker in the OFF position Disconnecting the battery cables Slide out the Compaq R6000 UPS battery packs Installing New Batteries Test/Reset Alarm button Care and Storage of Batteries Disposing of Used BatteriesExtended Runtime Module ERM Batteries Troubleshooting Audible Alarm Group Responding to Audible AlarmsCauses Action Shutdown Imminent Causes Action Shutdown within SecondsLoads in Jeopardy Audible Alarm Causes Action Low, refer to Chapter6Compaq R6000 UPS Series Operation and Reference Guide Responding to Audible Alarms Audible Alarm Group Battery breaker is in the onCompaq R6000 UPS Trouble Indicators Trouble IndicatorsLED Alarm Configurations Repairing the UPS Regulatory Compliance Notices Federal Communications Commission NoticeClass a Equipment Class B EquipmentCanadian Notice Avis Canadien European Union NoticeTaiwanese Notice Japanese NoticeClass A/B Equipment Battery Replacement Notice Electrostatic Discharge Grounding Methods Specifications Physical Specifications Input SpecificationsTable C-1 Physical Characteristics Table C-2 Input SpecificationsOutput Specifications II. Output Voltage IV. Additional FeaturesRegulation Battery Specifications Battery RuntimeBattery Specifications Table C-4Environmental Specifications Table C-6 Environmental SpecificationsIndex Battery cable connectors Button controls Index Compaq 6000 Series UPS Operation and Reference Guide See Compaq 6000 Series UPS Operation and Reference Guide Replacement battery kit part Compaq 6000 Series UPS Operation and Reference Guide Options tabulated Compaq 6000 Series UPS Operation and Reference Guide