Troubleshooting
Shutdown within 30 seconds Audible Alarm
Table
Shutdown within 30 seconds Audible Alarm
Audible Alarm Group | Audible Alarm Sound | Cause(s) | Action |
|
|
|
|
Shutdown within 30 | Accelerated beeping. | Check the ambient | |
seconds | Begins slowly, and gains |
| temperature in the |
| speed as the UPS |
| room. Refer to Appendix |
| approaches shutdown. |
| C, “Environmental |
| UPS shuts down 30 sec |
| Specifications” |
|
|
| |
| after audible alarm |
| If the ambient |
| begins. |
| temperature is within |
|
|
| range and the over |
|
|
| temperature alarm is |
|
|
| chronic, contact an |
|
|
| authorized service |
|
|
| provider. |
|
|
|
|
|
| Overload. | Reduce the load. See |
|
|
| section “Connecting |
|
|
| Loads” in Chapter 2 |
|
|
|
|
|
| Low battery. | Check the LCD display |
|
|
| (Meters, Battery Volts) |
|
|
|
|
|
| If a shutdown delay has | No action needed. |
|
| been programmed, the |
|
|
| accelerated alarm begins |
|
|
| before the last segment |
|
|
| shutoff. |
|
|
|
|
|
|
| Occurs during the last | No action needed. |
|
| minute of sleep timer if |
|
|
| the Sleep mode is |
|
|
| enabled. |
|
|
|
|
|