Compaq manual Wiring the Compaq R6000 UPS

Page 32

Installation 2-7

Wiring the Compaq R6000 UPS

WARNING: To reduce the risk of electrical shock or personal injury while performing this procedure, use a Lockout/Tagout procedure to isolate the Compaq R6000 UPS from the AC Branch Circuit (AC Mains). The Lockout/Tagout procedure should conform to local occupational safety and health regulations for the facility.

Code Compliance Information

WARNING: The Compaq R6000 UPS requires a direct connection to a dedicated AC Branch Circuit (AC Mains). Connection should only be performed by a licensed electrician in accordance with National Electrical Code (NFPA70 ) Article 310 in North America or in the equivalent local and national wiring regulations.

WARNING: If the Compaq R6000 UPS is to be installed in a computer equipment Room, it must also be connected to a Remote Emergency Power Off (REPO) circuit. The REPO port is designed to meet the requirements stated in National Electrical Code (NFPA 70) Article 645-10 and 11.

Connecting the Remote Emergency Power Off

Switch (REPO) Port

The Compaq R6000 UPS includes a Remote Emergency Power Off (REPO) port. When properly wired, the REPO port allows the power at the UPS output receptacles to be switched off from a remote location. Local or national wiring regulations may require REPO capabilities.

The R6000 UPS must be disconnected from utility power to wire the REPO port.

WARNING: To reduce risk of personal injury or damage to equipment, the REPO port must be wired by a licensed electrician.

WARNING: In North America, the REPO port must meet the NEC (NFPA 70, Article 725) standards. The REPO port wiring must also meet all other national and local standards in the area in which it is installed.

The Compaq R6000 UPS REPO circuit is an IEC950 Secondary Extra Low Voltage (SELV) circuit. The computer room Emergency Power shutdown circuit conductors that connect to the REPO terminals must meet the requirements of an NEC Class 2 circuit or IEC950 Secondary Extra Low

Image 32
Contents Compaq R6000 Series UPS Operation and Reference Guide Page Contents Operation Configuration Appendix B Text Conventions Symbols in TextAbout This Guide Symbols on Equipment Viii Compaq R6000 Series UPS Operation and Reference GuideCompaq Technical Support Rack StabilityGetting Help Compaq Website Compaq Authorized Reseller Introduction Compaq R6000 UPS Series ModelsCompaq R6000 UPS Series Models UPS Model Part Number CommentsFront Panel R6000 front panelRear Panel Compaq R6000 UPS Features Communication PortsFront Panel LEDs LED MeaningSolid green means normal operation Flashing green means StandbyFront Panel Controls and LCD Display Control Name FunctionPower Management Software Compaq Power Management SoftwareHardware Options Hardware OptionsUPS Option Cards Option Part NumberScalable Option Card MatrixCase Compaq Multi-Server UPS Card Multi-Server UPS CardCompaq Scalable UPS Card Scalable UPS CardCompaq SNMP-EN Adapter SNMP-EN AdapterPower Distribution Units PDUs Extended Runtime Modules ERMs$25,000 Computer Load Protection Guarantee WarrantyRemote Emergency Power Off Repo Port Pre-Failure Battery Warranty Installation Important Safety Instructions About This DevicePosition Installation ConsiderationsWeight Outline of Installation Procedure Preparing the Rack Check Battery Recharge Label Unpacking the UPS Assembling the Compaq R6000 UPS Placing UPS in rackPlacing chassis in rack Wiring the Compaq R6000 UPS 8Compaq R6000 Series UPS Operation and Reference Guide High Leakage Current Connecting the Compaq R6000 UPS to AC Branch CircuitRisk of Fire Notice Electrical Safety Requirements Procedure RecommendationInput Wiring Removing terminal input block coverInstall and connect the battery packs Sliding battery packs into chassisConnect cables 11. Connecting battery packs to the Compaq R6000 UPS Attaching Front Top Bezel 12. Attaching the top front bezelInstalling Extended Runtime Modules ERMs Connecting Communications Ports Connecting Communication Ports to Other DevicesLoad Segments Description Connecting LoadsInstalling and Connecting Communication Options Ordering Extra Power Cords Configuring Load SegmentsLoad Effect on Backup Time Attaching the Load SegmentsCompleting the Assembly R6000 UPS in the Rack 16. Placing the battery circuit breaker in the on positionPowering up the R6000 UPS Turning on the Main Circuit BreakerPressing the on button Shutting Down the SystemInstallation is Now Complete Charging BatteriesOperation Front Panel Controls Front Panel Indicators Front Panel LCDFront Panel LEDs Ref # Description Standby Mode Modes of OperationBattery Mode Audible Alarm Initiating a Self-testSilencing an Audible Alarm Silencing an audible alarmConfiguration Changing Configuration ParametersRange Matching the Utility VoltageVoltage Ranges VAC Configuring the Compaq R6000 UPS Using the LCD Display Menu LCD display, showing the three buttons that control itInitial Power-Up Display LCD Display Menu StructureTop Level Main Menu Sub-Menu ChoicesStatus UPS Status + Load Segment statusUPS Status + Active Alarm Count On BatteryLoad Power Off Load Power OnMeters OverloadInput Volts Output VoltsActive Alarms Output PowerBattery Volts Output FrequencyInput AC Over Voltage Input AC Under VoltageInput Over or Under Frequency Output OverloadInverter Fault Battery LowBattery Totally Discharged UPS on BatterySite Wiring Fault Battery DataBattery Test Failed Firmware Version Load Control Display TestSystem Setup Set Hardware HW ConfigurationBattery Setup Set LanguageSet Alarm Horn Set PasswordCommunications Setup Set Sync Range ±HertzSerial Port Baud RateData Bits Stop BitsParity Set Voltage Set Site FaultSet Sleep Mode Battery Maintenance Precautions When to Replace Batteries Obtaining New BatteriesBefore Replacing Batteries How to Replace BatteriesRemoving the Battery Packs Place the battery circuit breaker in the OFF position Disconnecting the battery cables Slide out the Compaq R6000 UPS battery packs Installing New Batteries Test/Reset Alarm button Extended Runtime Module ERM Batteries Disposing of Used BatteriesCare and Storage of Batteries Troubleshooting Causes Action Shutdown Imminent Responding to Audible AlarmsAudible Alarm Group Causes Action Shutdown within SecondsLoads in Jeopardy Audible Alarm Causes Action Low, refer to Chapter6Compaq R6000 UPS Series Operation and Reference Guide Responding to Audible Alarms Audible Alarm Group Battery breaker is in the onCompaq R6000 UPS Trouble Indicators Trouble IndicatorsLED Alarm Configurations Repairing the UPS Regulatory Compliance Notices Federal Communications Commission NoticeClass a Equipment Class B EquipmentCanadian Notice Avis Canadien European Union NoticeClass A/B Equipment Japanese NoticeTaiwanese Notice Battery Replacement Notice Electrostatic Discharge Grounding Methods Specifications Physical Specifications Input SpecificationsTable C-1 Physical Characteristics Table C-2 Input SpecificationsOutput Specifications Regulation IV. Additional FeaturesII. Output Voltage Battery Specifications Battery RuntimeBattery Specifications Table C-4Environmental Specifications Table C-6 Environmental SpecificationsIndex Battery cable connectors Button controls Index Compaq 6000 Series UPS Operation and Reference Guide See Compaq 6000 Series UPS Operation and Reference Guide Replacement battery kit part Compaq 6000 Series UPS Operation and Reference Guide Options tabulated Compaq 6000 Series UPS Operation and Reference Guide