6-6 Compaq R6000 UPS Series Operation and Reference Guide
Caution Audible Alarm
Table
Caution Audible Alarm
Audible Alarm Group | Audible Alarm Sound | Cause(s) | Action |
|
|
|
|
Caution | Beeps every five | On battery | Prepare for UPS shutdown. |
| seconds |
|
|
|
|
|
|
|
| Load is greater than | Check manual Bypass |
|
| 105%, and the manual | switch on back of UPS. Turn |
|
| Bypass switch is turned | to Normal position. Reduce |
|
| to Bypass position. | load. |
|
|
|
|
|
| Ambient over- | Check air intake is not |
|
| temperature | blocked and ambient room |
|
|
| temperature is correct. If the |
|
|
| problem still exists, contact |
|
|
| an authorized service |
|
|
| provider. |
|
|
|
|
|
| Button is still being held | Let go of button. Make sure |
|
| after action is | the button travels freely, or |
|
| completed. | is not lodged. |
|
|
|
|
|
| The UPS performs a | Turn off the UPS and call an |
|
| authorized service provider. | |
|
| memory location error. |
|
Site-wiring fault. (Only if the site-wiring is enabled.)
Use the Front Panel controls and LCD display to examine information on the warning. If necessary, contact a licensed electrician to check input wiring, or contact an authorized service provider.
A self-test fails, indicated on the LCD display
Shut off Mains, wait until UPS shuts down, then turn breaker back ON and test again. If
continued