7. GENERAL PRODUCT SPECIFICATIONS
| XRT600 |
| XRT1000 | XRT1500 | XRT2000 |
| XRT2001 | XRT2002 |
| (XRT600/2) | (XRT1000/2) |
| (XRT2000/2) |
|
|
| |
Acceptable input |
|
| ||||||
volts |
| N/A |
|
|
| |||
Output Voltage | 120v |
| 120v | 120v | 120v |
| 120v/240v | 120/208v |
(230v) |
| (230v) | N/A | (230v) |
|
|
| |
Nominal input | 60 Hz |
| 60 Hz | 60 Hz | 60 Hz |
| 60 Hz | 60 Hz |
frequency | (50 Hz) |
| (50 Hz) | N/A | 50 Hz |
|
|
|
Input protection |
|
|
|
|
| |||
Frequency limits |
|
|
| 60 Hz. +/- 3 Hz |
|
| ||
(online) |
|
|
| (50 Hz. +/- 3 Hz. ) |
|
| ||
Transfer time |
|
|
| 4 ms Typical |
|
| ||
Max load | 600 /600 |
| 1000 / 1000 | 1500 / 1500 | 2000 / 2000 |
| 2000 / 2000 | 2000 / 2000 |
(VA/watts) |
|
|
|
|
|
|
|
|
On Battery | 120v |
| 120v | 120v (N/A) | 120v (230v) |
| 120v / | 120v / |
Output Voltage | (230v) |
| (230v) |
|
|
| 240v | 208v |
|
|
|
|
|
|
| ||
On Battery | 60 Hz | |||||||
frequency | (50 Hz +/- 0.1 Hz. Unless synchronized to utility during brownout) | |||||||
On Battery |
|
|
| Low distortion sine wave |
|
| ||
waveform |
|
|
|
|
|
|
|
|
Protection | ||||||||
Surge energy |
| 480 joules: one time 10 to 1000μ s waveform ( 120 VAC units ) | ||||||
rating |
|
|
|
|
|
|
|
|
Surge current | 6500A maximum: one time 8 to 20 μ s waveform (120 VAC units ) | |||||||
capability |
|
|
|
|
|
|
|
|
Surge response |
|
| 0 Ns (instantaneous) normal mode, <5 Ns common mode |
| ||||
time |
|
|
|
|
|
|
|
|
Surge volts let |
|
|
| < .2% |
|
|
| |
thru |
|
|
|
|
|
|
|
|
Noise filter | Normal and common mode EMI /RFI suppression, 100 kHz to 10 MHz | |||||||
Battery type |
|
| Spill proof, sealed, maintenance free, |
| ||||
Typical battery |
|
|
| 5 years |
|
| ||
life |
|
|
|
|
|
|
|
|
Typical recharge |
|
| 4 hours for a single battery pack |
|
| |||
time |
|
|
|
|
|
|
|
|
Operating temp |
|
|
| 0 to 40°C (+32 to 104°F) |
|
| ||
Operating & |
|
|
| 0 to 95% |
|
| ||
storage relative |
|
|
|
|
|
|
|
|
humidity |
|
|
|
|
|
|
|
|
Storage |
|
|
|
|
| |||
temperature |
|
|
|
|
|
|
|
|
Operating |
|
| 0 to 3000 meters ( 0 to 10,000 ft. ) |
|
| |||
elevation |
|
|
|
|
|
|
|
|
Electromagnetic |
|
| IEC |
| ||||
immunity |
|
|
|
|
|
|
|
|
Audible noise |
|
|
| <45 dB @ 1 meter |
|
| ||
Audible Alarm |
|
| On overload, On battery, Low battery warning, check fan |
| ||||
Communication |
|
|
|
|
| |||
s port |
|
|
|
|
|
|
|
|
35