INITIAL ERROR MESSAGES

As soon as the UPS is first turned on, it performs a series of self tests. If the self tests fail then the UPS will report the failure and display the fault. If the self test passes, but the UPS was shut down previously due to a fault, the previous fault code or message will be displayed. This feature allows you to determine why the UPS shut down. The LCD screen will display the words “Error Detected” on the top line of the screen, and one of the messages in the Error Code list is shown on the second line.

Model XRT600 LED Display Error Codes

Displayed in binary code

LED

 

 

DISPLAY

POSSIBLE CAUSE

ACTION TO TAKE

ooox

Low ac input

Verify incoming ac

ooxo

Input ac to high

Verify incoming ac

ooxx

Input AC frequency out of

Verify incoming freq. for this

 

range for unit.

model.

oxoo

Excessive output current

Verify output load

 

being drawn

matches unit.

oxox

Fan not running

Verify nothing has

 

 

gotten into the fan

oxxo

Fan or air

Clear air passages

 

passages blocked

 

oxxx

Battery pack is bad or

Check battery voltage

 

disconnected

and connections

xooo

UPS has had a

Call for service

 

hardware fault

 

xoox

Output voltage

Call for service

 

is too high

 

xoxo

Output voltage

Call for service

 

is too low

 

On the XRT600, these messages can be cleared by pressing the Test/Alarm Silence button.

29

Image 30
Contents Page Page XRT Series User’s Manual Introduction Para Systems Life Support PolicyPage Receiving Inspection Please Save the Packing MaterialsRadio Frequency Interference Important Safety Instructions This Manual Contains Important Safety InstructionsInstructions Importantes Concernant LA Sécurité System Description Features Built in Self Test Installation Installation PlacementProtection Strategies Page INSTALLATION, Step by Step Battery Pack Connection DiagramXRT600, XRT1000, XRT1500 and XRT2000 Back panels XRT600 Front Panel Showing Load LED’s Front Panel Load Menu on LCD Screen LED Front Panel Top four LED’s Green provide 3 functions OperationFront Panels Second bottom row of LED’s provide status informationSwitches Test/Alarm Silence ButtonStartup Menu Flow Status Menu Test Menu Setup Menu Config Menu Alarms and Warnings Options System Batteries Storage InstructionsBattery Replacement Troubleshooting Symptom Possible Cause Action to TakeInitial Error Messages Model XRT1000 and above error messages LCD Display Possible Cause Action to TakeOperating Faults Self Test Obtaining Service Mark the RMA # on the outside of all packages. The factoryPage General Product Specifications Cetl CSA Remote Communications Remote Direct Communications LBWBattery Pack and Runtime Specifications XRT600Load TWO R E E XRTBP1 XRTBP3 Limited Product Warranty