Rackmount Solutions XRT Series manual Remote Direct Communications, Lbw

Page 39

REMOTE DIRECT COMMUNICATIONS

Pin 1:

 

Not Used

Pin 2:

LBW

Output signal from UPS (RS232 levels)

 

 

High signal (+3 to +12 volts)= Low

 

 

Battery Warning

Pin 3:

UPS Shutdown

Input signal to UPS, Shuts down

 

 

UPS (RS232 levels)

 

 

High signal (+3 to +12 volts) = UPS OFF

Pin 4:

AC Fail NO.

Output signal from UPS, open

 

 

collector, High impedance = AC OK

 

 

Low impedance to ground = AC Failed

Pin 5:

Ground

Common Return

Pin 6:

Low Battery Warning

Output signal from UPS, open

 

 

collector

 

 

High impedance = OK

 

 

Low impedance to ground = Low

 

Battery Warning

Pin 7:

AC Fail NC

Output signal from UPS, open

 

 

collector High impedance = AC Failed

 

 

Low impedance to ground = AC OK

Pin 8:

AC Fail Logic Signal

Output signal from UPS, logic level

 

 

Logic High (+3 to +12 volts) =

 

 

AC failed

 

 

Logic Low (0 volts) = AC OK

Pin 9:

Remote Shutdown

Input signal to UPS, pulled to 5

 

 

VDC through 10 K ohms

 

 

>2.4 VDC = Normal output

 

 

<0.8 VDC = Output off

38

Image 39
Contents Page Page XRT Series User’s Manual Para Systems Life Support Policy IntroductionPage Receiving Inspection Please Save the Packing MaterialsRadio Frequency Interference This Manual Contains Important Safety Instructions Important Safety InstructionsInstructions Importantes Concernant LA Sécurité System Description Features Built in Self Test Installation Installation PlacementProtection Strategies Page Battery Pack Connection Diagram INSTALLATION, Step by StepXRT600, XRT1000, XRT1500 and XRT2000 Back panels XRT600 Front Panel Showing Load LED’s Front Panel Load Menu on LCD Screen Second bottom row of LED’s provide status information OperationFront Panels LED Front Panel Top four LED’s Green provide 3 functionsSwitches Test/Alarm Silence ButtonStartup Menu Flow Status Menu Test Menu Setup Menu Config Menu Alarms and Warnings Options Storage Instructions System BatteriesBattery Replacement Symptom Possible Cause Action to Take TroubleshootingInitial Error Messages LCD Display Possible Cause Action to Take Model XRT1000 and above error messagesOperating Faults Self Test Mark the RMA # on the outside of all packages. The factory Obtaining ServicePage General Product Specifications Cetl CSA Remote Communications LBW Remote Direct CommunicationsXRT600 Battery Pack and Runtime SpecificationsLoad TWO R E E XRTBP1 XRTBP3 Limited Product Warranty