ALARMS

English

ALARMS

ON BATTERY

When the UPS is operating on the batteries, the On-Battery LED will blink and the audible alarm will sound once every 10-seconds. The alarm will stop once the UPS returns to the On-Line operation.

LOW BATTERY WARNING

The UPS will sound two beeps every five-seconds when the battery reserve runs low. This condition will continue until AC returns or the UPS shuts down from battery exhaustion.

WEAK/BAD BATTERY

The UPS automatically tests the battery’s condition and will illuminate the Weak/ Bad Battery LED and sound the alarm. This alarm will be repeated until the batteries pass a self test. If the battery is bad or disconnected, the Weak/Bad Battery LED will illuminate and the alarm will beep three times every five-min- utes until the battery is reconnected or replaced. If the battery is weak, the Weak/Bad Battery LED will illuminate and the alarm will beep one time every ten-minutes until the battery is recharged or replaced. It is recommended that the UPS be allowed to charge overnight before performing a battery test to confirm a Weak/Bad Battery condition.

NOTE: If the UPS has a Weak/Bad Battery Alarm after reconnecting of replac- ing the batteries, the user must initiate a self test to clear the Weak/Bad Bat- tery Alarm. To initiate a self test see section 4 "SELF TEST".

OVERLOAD

When the amount of load attached to the UPS exceeds its power rating, the Overload LED will illuminate and the UPS will sound a constant alarm. This alarm will remain on until the excess load is removed or the UPS’s self protec- tion circuit shuts the UPS down.

UPS FAULT

When the UPS detects a hardware fault, the Fault LED will illuminate and the UPS will sound a constant alarm. The fault condition, in some instances, may be reset by turning the UPS OFF and then ON. (see section 5 Troubleshooting)

FAN LOCK

AC Mode: If the fan becomes locked, the alarm will beep one time every two- seconds until the fan is unlocked.

Battery Mode: If the fan becomes locked, the alarm will beep one time every two-seconds for thirty-seconds, then the output will turn off, the alarm will sound continuously and the Fault LED will illuminate. The UPS must be turned off and the fan unlocked to clear the Fan lock Alarm.

10

Image 11
Contents Page PRO-E Series Users Manual This symbol indicates Direct Current Supply IMPORTANT SAFETY INSTRUCTIONS SAVE THESE INSTRUCTIONSThis symbol indicates ATTENTION This symbol indicates Risk of Electrical ShockAUTHORIZED SERVICE PERSONNEL ONLY Para Systems Life Support Policy Receiving InspectionOn-Line/On-Battery/Boost/Buck LED Fault LED Overload LED 230V Models REAR PANEL120V Models WARNING The 230V models are NETWORK PROTECTION ONLYCONNECTING YOUR EQUIPMENT INSTALLATION PLACEMENTINSTALLATION COMMUNICATIONS PORT CONNECTION OPTIONAL CONNECTING THE UPS TO AN AC SOURCECHECKING THE SITE WIRING FAULT CHARGING THE BATTERYSELF TEST DIP SWITCH SETTINGSTURNING THE UNIT ON/OFF ON / OFF / Test ButtonUPS FAULT ALARMS ON BATTERYLOW BATTERY WARNING WEAK/BAD BATTERYCOMMUNICATIONS PORTS RS232 and USB even though there is Check the specifications seeEnglish Press and release the On/OffREPLACING THE BATTERY Yuasa BATTERY REPLACEMENT PROCEDURE9. Disconnect the positive red wire from the battery positve terminal IF THE UPS REQUIRES SERVICE PRO1100E MODEL NUMBERPRO500E PRO700EFactory DefaultThese items may require optional software or hardware FunctionPara Systems Inc. Para Systems warrants this equipment, when properly applied and operated within specified conditions, against faulty materials or workmanship for a period of three years from the date of purchase. For equip- ment sites within the United States and Canada, this warranty covers repair or replacement of defective equipment at the discretion of Para Systems. Repair will be from the nearest authorized service center. Replacement parts and warranty labor will be borne by Para Systems. For equipment located outside of the United States and Canada, Para Systems only covers faulty parts. Para Systems products repaired or replaced pursuant to this warranty shall be war- ranted for the unexpired portion of the warranty applying to the original product. This warranty applies only to the original purchaser who must have properly registered the product within 10 days of purchase Continued LIMITED PRODUCT WARRANTYDECLARATION OF CONFORMITY Robert CalhounEnglish