9.Disconnect the positive (red) wire from the battery positve terminal.

English

9.Disconnect the positive (red) wire from the battery positve terminal.

10.Disconnect the battery negative (black) wire from the battery negative terminal.

NOTE: Use CAUTION, do not touch the battery positive wire to the battery negative wire.

11.Remove the battery bracket retaining screw and slide the battery bracket upwards.

12.Using the pull tab, pull the batteries out completely. DO NOT pull the batteries out by pulling the battery jumper wires.

13.Remove the battery jumper wires.

14.Verify proper polarity. Re-install the battery jumper wires on the new batteries.

15.Slide the new batteries into the battery compartment.

16.Re-install the battery bracket and the battery bracket retaining screw.

17.Verify proper polarity. Reconnect the battery negative (black) wire to the battery negative terminal.

18.Verify proper polarity. Reconnect the battery positive (red) wire to the battery positive terminal. Some sparking may occur, this is normal.

19.Re-install the front panel of the UPS.

20.Re-install the retaining screws for the front panel of the UPS.

21.Dispose of the old batteries properly at an appropriate recycling facility or return them to the supplier in the packing material for the new batteries.

22.The UPS is now ready for the normal start-up operation.

NOTE: If the UPS has a Weak/Bad Battery Alarm after replacing the batteries, the user must initiate a self test to clear the Weak/Bad Battery Alarm. To initiate a self test see section 4 "SELF TEST".

15

Image 16
Contents Page PRO-E Series Users Manual IMPORTANT SAFETY INSTRUCTIONS SAVE THESE INSTRUCTIONS This symbol indicates ATTENTIONThis symbol indicates Risk of Electrical Shock This symbol indicates Direct Current SupplyAUTHORIZED SERVICE PERSONNEL ONLY Receiving Inspection Para Systems Life Support PolicyOn-Line/On-Battery/Boost/Buck LED Fault LED Overload LED REAR PANEL 120V ModelsWARNING The 230V models are NETWORK PROTECTION ONLY 230V ModelsINSTALLATION INSTALLATION PLACEMENTCONNECTING YOUR EQUIPMENT CONNECTING THE UPS TO AN AC SOURCE CHECKING THE SITE WIRING FAULTCHARGING THE BATTERY COMMUNICATIONS PORT CONNECTION OPTIONALDIP SWITCH SETTINGS TURNING THE UNIT ON/OFFON / OFF / Test Button SELF TESTALARMS ON BATTERY LOW BATTERY WARNINGWEAK/BAD BATTERY UPS FAULTCOMMUNICATIONS PORTS RS232 and USB Check the specifications see EnglishPress and release the On/Off even though there isREPLACING THE BATTERY BATTERY REPLACEMENT PROCEDURE Yuasa9. Disconnect the positive red wire from the battery positve terminal IF THE UPS REQUIRES SERVICE MODEL NUMBER PRO500EPRO700E PRO1100EDefault These items may require optional software or hardwareFunction FactoryPara Systems Inc. Para Systems warrants this equipment, when properly applied and operated within specified conditions, against faulty materials or workmanship for a period of three years from the date of purchase. For equip- ment sites within the United States and Canada, this warranty covers repair or replacement of defective equipment at the discretion of Para Systems. Repair will be from the nearest authorized service center. Replacement parts and warranty labor will be borne by Para Systems. For equipment located outside of the United States and Canada, Para Systems only covers faulty parts. Para Systems products repaired or replaced pursuant to this warranty shall be war- ranted for the unexpired portion of the warranty applying to the original product. This warranty applies only to the original purchaser who must have properly registered the product within 10 days of purchase LIMITED PRODUCT WARRANTY ContinuedRobert Calhoun DECLARATION OF CONFORMITYEnglish