Rackmount Solutions PRO1100E, PRO700iE, PRO1500E Battery Replacement Procedure, English, Yuasa

Page 15
Yuasa Part #

English

CAUTION: Replace batteries with the same number and type as originally installed in the UPS. These batteries have pressure operated vents. These UPSs contain sealed non-spillable lead acid batteries.

PRO-E

PRO500E

PRO700E

PRO1100E

PRO1500E

Model #

PRO500iE

PRO700iE

PRO1100iE

PRO1500iE

 

 

 

 

 

Battery

1-12V9Ah

2-12V7Ah

3-12V7Ah

3-12V9Ah

Model #

 

 

 

 

Panasonic

LC-R129

LC-R127

LC-R127

LC-R129

Part #

 

 

 

 

Yuasa Part #

REW45-12

NP 7-12

NP 7-12

REW45-12

 

 

 

 

 

BATTERY REPLACEMENT PROCEDURE

PLEASE READ THE CAUTIONS AND WARNINGS BEFORE ATTEMPTING TO REPLACE THE BATTERIES

Hot-swappable batteries mean that the batteries can be replaced without powering down the whole UPS system.

NOTE: If there is a power interruption while replacing the hot-swappable batteries, with the UPS on, the load will not be backed up. To hot-swap the batteries start with step number 6.

1.Turn off the equipment that is plugged into the output receptacles of the UPS.

2.Press and release the On/Off/Test button on the front panel to turn the UPS OFF.

3.Unplug the UPS's AC power cord from the AC wall outlet.

4.Unplug the equipment from the output receptacles of the UPS.

5.Unplug the computer interface cable from the rear panel of the UPS.

6.Remove the retaining screws from the bottom of the front panel of the UPS.

7.Grasp the bottom of the front panel and gently pull the front panel off the UPS.

8.Lay the front panel on top of the UPS.

14

Image 15
Contents Page PRO-E Series Users Manual This symbol indicates Direct Current Supply IMPORTANT SAFETY INSTRUCTIONS SAVE THESE INSTRUCTIONSThis symbol indicates ATTENTION This symbol indicates Risk of Electrical ShockAUTHORIZED SERVICE PERSONNEL ONLY Para Systems Life Support Policy Receiving InspectionOn-Line/On-Battery/Boost/Buck LED Fault LED Overload LED 230V Models REAR PANEL120V Models WARNING The 230V models are NETWORK PROTECTION ONLYINSTALLATION PLACEMENT INSTALLATIONCONNECTING YOUR EQUIPMENT COMMUNICATIONS PORT CONNECTION OPTIONAL CONNECTING THE UPS TO AN AC SOURCECHECKING THE SITE WIRING FAULT CHARGING THE BATTERYSELF TEST DIP SWITCH SETTINGSTURNING THE UNIT ON/OFF ON / OFF / Test ButtonUPS FAULT ALARMS ON BATTERYLOW BATTERY WARNING WEAK/BAD BATTERYCOMMUNICATIONS PORTS RS232 and USB even though there is Check the specifications seeEnglish Press and release the On/OffREPLACING THE BATTERY Yuasa BATTERY REPLACEMENT PROCEDURE9. Disconnect the positive red wire from the battery positve terminal IF THE UPS REQUIRES SERVICE PRO1100E MODEL NUMBERPRO500E PRO700EFactory DefaultThese items may require optional software or hardware FunctionPara Systems Inc. Para Systems warrants this equipment, when properly applied and operated within specified conditions, against faulty materials or workmanship for a period of three years from the date of purchase. For equip- ment sites within the United States and Canada, this warranty covers repair or replacement of defective equipment at the discretion of Para Systems. Repair will be from the nearest authorized service center. Replacement parts and warranty labor will be borne by Para Systems. For equipment located outside of the United States and Canada, Para Systems only covers faulty parts. Para Systems products repaired or replaced pursuant to this warranty shall be war- ranted for the unexpired portion of the warranty applying to the original product. This warranty applies only to the original purchaser who must have properly registered the product within 10 days of purchase Continued LIMITED PRODUCT WARRANTYDECLARATION OF CONFORMITY Robert CalhounEnglish