Sharp JW-21MN manual Table of parameter memory, 16-8, Master station

Page 103

16-3 Table of parameter memory

(1)Master station

The set contents of the parameter addresses 004004 to 004377(8) and 004404 to 004777(8) shown below are in the case that a JW-21MN is used for a slave station.

Address(8)

Set contents

 

 

 

Setting method (value, example) (1 / 5)

 

 

 

 

 

 

 

 

 

 

 

000000

Store the mis-setting slave station number in the master station

 

 

 

 

004000

Top address of relay link area in the master

(Octal, word)

 

 

 

When 1000, set to 001000(8) by file

004001

station

 

 

 

 

 

address

 

 

 

 

 

 

 

004002

Set function (relay/register link)

 

 

01(H)

 

 

 

Fixed to 01(H)

004003

Amount of connectable stations (2 to 64 stations)

(Decimal, byte)

 

 

 

When 12 stations, set to 012(D)

 

- When slave station 01(8) is set to data

004004

(Octal, word)

 

 

 

When 1200, set to 001200(8)

 

004005

 

 

 

 

(Set by file address)

 

link (the standard function), top

 

 

 

 

 

 

 

 

 

 

 

 

 

 

*

004004

address of the relay link area on slave

004006

00(H)

 

 

 

 

 

 

00(H): In this case the same as the master station

 

 

 

 

 

 

to

station 01(8) are as shown at right.

 

004007

 

 

 

 

 

 

80(H): In this case different from the master station

 

 

 

 

 

 

 

 

- When slave station 01(8) is set to data

004004

(Decimal, word)

 

 

When 100 bytes, set to 00100(D)

 

 

004007

 

 

link (the save memory function),

004005

 

 

 

 

 

 

 

 

 

 

number of offset bytes of relay link

 

 

 

 

 

 

 

 

 

 

004006

00(H)

 

 

 

 

 

 

 

 

 

 

 

 

area on slave station 01(8) are shown

 

 

 

 

 

 

at right.

004007

80(H)

 

 

 

 

 

*When 00(H) is set, the value becomes the same top address of the master station regardless of the setting value of 004004 to 004005(8).

16

Address(8)

Set contents

 

 

Top address or number of offset

004010 to 004013 bytes on slave station 02(8) (same as 004004 to 004007).

004014 to 004017 03(8) (same as 004004 to 004007)

004020 to 004023 04(8) (same as 004004 to 004007)

004024 to 004027 05(8) (same as 004004 to 004007)

004030 to 004033 06(8) (same as 004004 to 004007)

004034 to 004037 07(8) (same as 004004 to 004007)

004040 to 004043 10(8) (same as 004004 to 004007)

004044 to 004047 11(8) (same as 004004 to 004007)

004050 to 004053 12(8) (same as 004004 to 004007)

004054 to 004057 13(8) (same as 004004 to 004007)

004060 to 004063 14(8) (same as 004004 to 004007)

004064 to 004067 15(8) (same as 004004 to 004007)

004070 to 004073 16(8) (same as 004004 to 004007)

004074 to 004077 17(8) (same as 004004 to 004007)

004100 to 004103 20(8) (same as 004004 to 004007)

004104 to 004107 21(8) (same as 004004 to 004007)

004110 to 004113 22(8) (same as 004004 to 004007)

004114 to 004117 23(8) (same as 004004 to 004007)

004120 to 004123 24(8) (same as 004004 to 004007)

004124 to 004127 25(8) (same as 004004 to 004007)

004130 to 004133 26(8) (same as 004004 to 004007)

004134 to 004137 27(8) (same as 004004 to 004007)

004140 to 004143 30(8) (same as 004004 to 004007)

004144 to 004147 31(8) (same as 004004 to 004007)

004150 to 004153 32(8) (same as 004004 to 004007)

004154 to 004157 33(8) (same as 004004 to 004007)

004160 to 004163 34(8) (same as 004004 to 004007)

004164 to 004167 35(8) (same as 004004 to 004007)

004170 to 004173 36(8) (same as 004004 to 004007)

004174 to 004177 37(8) (same as 004004 to 004007)

Address(8)

Set contents

 

 

Top address or number of offset

004200 to 004203 bytes on slave station 40(8) (same as 004004 to 004007).

004204 to 004207 41(8) (same as 004004 to 004007)

004210 to 004213 42(8) (same as 004004 to 004007)

004214 to 004217 43(8) (same as 004004 to 004007)

004220 to 004223 44(8) (same as 004004 to 004007)

004224 to 004227 45(8) (same as 004004 to 004007)

004230 to 004233 46(8) (same as 004004 to 004007)

004234 to 004237 47(8) (same as 004004 to 004007)

004240 to 004243 50(8) (same as 004004 to 004007)

004244 to 004247 51(8) (same as 004004 to 004007)

004250 to 004253 52(8) (same as 004004 to 004007)

004254 to 004257 53(8) (same as 004004 to 004007)

004260 to 004263 54(8) (same as 004004 to 004007)

004264 to 004267 55(8) (same as 004004 to 004007)

004270 to 004273 56(8) (same as 004004 to 004007)

004274 to 004277 57(8) (same as 004004 to 004007)

004300 to 004303 60(8) (same as 004004 to 004007)

004304 to 004307 61(8) (same as 004004 to 004007)

004310 to 004313 62(8) (same as 004004 to 004007)

004314 to 004317 63(8) (same as 004004 to 004007)

004320 to 004323 64(8) (same as 004004 to 004007)

004324 to 004327 65(8) (same as 004004 to 004007)

004330 to 004333 66(8) (same as 004004 to 004007)

004334 to 004337 67(8) (same as 004004 to 004007)

004340 to 004343 70(8) (same as 004004 to 004007)

004344 to 004347 71(8) (same as 004004 to 004007)

004350 to 004353 72(8) (same as 004004 to 004007)

004354 to 004357 73(8) (same as 004004 to 004007)

004360 to 004363 74(8) (same as 004004 to 004007)

004364 to 004367 75(8) (same as 004004 to 004007)

004370 to 004373 76(8) (same as 004004 to 004007)

004374 to 004377 77(8) (same as 004004 to 004007)

- Initial value of the address 004000 to 004377(8) are all 00(H).

16-8

Image 103
Contents JW-21MN JW-21MN Installation Safety PrecautionsWiring Compel Use Maintenance ProhibitME-NET Module JW-21MN Table of contents Errors and Countermeasures 12-1 to Setting of Switches and Parameter 11-1 toDescription for Computer Link Operation 10-1 to 13-1 Support Tools 14-1 to Specifications 15-1 toAppendix 16-1 to Data link function Features and FunctionsComputer link function Wiring InstallationConnector Allocation of relay number MaintenanceTreatment Static electricityJW20H JW-21MN JW-21MN JW30H System ConfigurationFront view Name and Function of Each PartInstallation procedure InstallationRemarks Name Model Maker Processing of CablesProcessing cable end Cutting of coating, external conductor, and insulator Fine adjustment of blade cutting depthRemoval of coating, external conductor, and insulator Processing of cable end Display of blade settingCrimping contact Connector crimping procedureConnector ME-GP-01 Processing procedure Insert a sleeve Required tools Hand-held crimping toolInsulation test Fixing the connectorConductivity test Cable trunk and branch lines Wiring MethodRelaying of trunk cables Cable wiring procedure in control panel Page Remarks Waterproof and insulation processing of connectorsBranch connector Straight connectorCheck after wiring Wiring of cables at outside control panelsStation number of the additional station Branching methodReason Memory address for data links Memory Address on the ME-NETMemory address map against JW20/JW20H JW30H address ME-NET address Memory address map against JW30HJW20/20H ME-NET address Capacity Memory addresses for computer linksJW30H address ME-NET address Capacity Remarks Relay link Description for Data Link OperationCommunication method Data link Standard functionData link Save memory function Setting item Set locationRegister link Required transmission time Required transmission time and communication delay timeCommunication delay time An example of synchronized transfer by OUT instruction Data transmission between master PC and slave PCExpansion of network Multiple installation of the JW-21MNCase of mounting 4 sets of JW-21MN Hierarchical link Computer link function Basic commandsOptional commands Description for Computer Link Operation10-2 Basic commands10-3 Optional commandsCommunication format, basic pattern 10-4 Write mode assignment None Communication formatRead free memory size Monitor TMR, CNT, and MDSetting PC mode Reading PC mode10-5 Writing system memory Reading system memory10-6 10-7 Setting dateWrite mode assignment 1 or Communication format Reading dateReading time Setting time10-8 Monitor step status JW20/JW20H only Correct clock time10-9 10-10 Write mode assignmentRead the optional parameters Set the optional parametersSet the special I/O parameters Read the special I/O parameters10-11 Set the secret function JW30H only Release the secret function, register password JW30H only10-12 10-13 Check the secret function JW30H only10-14 Response on errorOperation procedure Setting of Switches and Parameter11-1 11-2 Switch setting of master station and slave stationMode switch Mode Module No. switch Unit noReference Need for the termination resistance Station number switch STA noTermination resistance switch LT 11-311-4 Shield ground switch LGSetting contents of master station parameters Value H 11-611-7 Parameter for setting in master stationParameter for setting in slave station Communication area map11-8 11-9 + h11-10 Example for settingMaser station Slave station Standard Save memory 11-11 When master station PC is JW20/JW20H11-12 When master station PC is JW30H11-13 Setting procedureExample Stop operation of data link HEX hexadecimal, byte 11-14Stop operation of data link HEX hexadecimal, byte Set number of connecting stations DCM decimal, byte Data link function setting HEX hexadecimal, byte11-15 Set top address of register link area on the master station 11-16Set in parameter addresses 005000 to 11-1711-18 Set connection status of slave station Bit pattern, byte 11-1911-20 PC operation 11-21Contents Setting item11-22 11-23 Setting range of flag areaWhen PC is JW20/JW20H When PC is JW30H11-24 11-25 Turn on the power of slave station PC Connect support tools11-26 11-27 11-28 Details Measure Errors and CountermeasuresIndication lamps 12-1Remark FlagOperation condition monitor flag Case of a master station12-3 Communication monitor flag12-4 Case of slave station 01 to12-5 Monitor operation condition by each station PC12-6 Storage of error code12-7 System memory #170 to 177 option module error codeSystem memory #160 to 167 self diagnosis error code System memory #150 monitor error switch number12-8 Error history13-1 Replacement of the JW-21MNRecord and load by ladder software JW-92SP, JW-50SP Record Support Tools14-1 Stop operation of the JW-21MN Load14-2 Load to the personal computerSpecification SpecificationsGeneral specifications Communication specifications15-2 Data link specificationsStandard function Specifications Save memory function SpecificationsOutside dimensional drawings Computer link specifications15-3 Appendix Maintenance and check16-1 Check flow chart Recovery method at communication errors16-2 16-3 Check cable/connectorCause Countermeasure 16-4 007764 to 16-5Other cases Switches required check in the JW-21MNCheck items of cables and connectors 16-616-7 Check the errors timingIdentify the error station When identification of the cause is difficult16-8 Table of parameter memoryMaster station 16-9 Set contents Setting method value, example16-10 16-11 Slave station 01 to 16-12Support tool Opposite module Connection module Special functions unique to the JW-21MN16-13 Remote programming and remote monitorOperation example 16-14Function Standard network connection Expansion network connection16-15 Network settingWhen used with a computer link Parameter setting by remote function16-16 Alphabetical Index Operation procedure Waterproof and insulation processing of connectors