Sharp JW-21MN manual JW30H address ME-NET address Capacity Remarks

Page 32

8

(2) Memory address map (against JW30H)

 

 

JW30H address (8)

ME-NET address (8)

Capacity

Remarks

Relay

 

00000 to 15777

SEG0 00000.0 to 1577.7

7168 points

 

Extension relay

20000 to 75777

SEG0 30000.0 to 35577.7

23552 points

Bit

TMR/CNT contact points

T-C0000 to T-C0777

SEG0 01600.0 to 01777.7

512 points

address

T-C1000 to T-C1777

SEG0 35600.0 to 35777.7

512 points

 

 

 

 

Relay

 

0000 to 1577

SEG0 00000 to 01577

896 bytes

 

Extension relay

2000 to 7577

SEG0 30000 to 35577

2944 bytes

 

TMR/CNT current value

b2000 to b3777

SEG0 26000 to 27777

1024 bytes

 

 

 

 

 

 

 

 

 

09000 to 09777

SEG0 04000 to 04777

512 bytes

 

 

 

 

 

 

 

 

 

19000 to 19777

SEG0 05000 to 05777

512 bytes

 

 

 

 

 

 

 

 

 

29000 to 29777

SEG0 06000 to 06777

512 bytes

 

 

 

 

 

 

 

 

 

39000 to 39777

SEG0 07000 to 07777

512 bytes

 

 

 

 

 

 

 

 

 

49000 to 49777

SEG0 10000 to 10777

512 bytes

Byte

 

 

 

 

 

address

Register

 

59000 to 59777

SEG0 11000 to 11777

512 bytes

 

 

69000 to 69777

SEG0 12000 to 12777

512 bytes

 

 

 

 

 

 

 

 

 

79000 to 79777

SEG0 13000 to 13777

512 bytes

 

 

 

 

 

 

 

 

 

89000 to 89777

SEG0 14000 to 14777

512 bytes

 

 

 

 

 

 

 

 

 

99000 to 99777

SEG0 15000 to 15777

512 bytes

 

 

 

 

 

 

 

 

 

E0000 to E5777

SEG0 16000 to 23777

3072 bytes

 

 

 

 

 

 

 

 

Register (storable error

E6000 to E7777

SEG0 24000 to 25777

1024 bytes

 

history)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

TMR/CNT number

 

0000 to 1777

0000 to 1777

1024 pcs.

-----

 

 

 

 

 

 

 

File 1

000000 to 037777

SEG1 000000 to 037777

16 K bytes

 

 

 

 

 

 

 

 

File 2

000000 to 177777

SEG2 000000 to 177777

64 K bytes

 

 

 

 

 

 

 

 

File 3

000000 to 177777

SEG3 000000 to 177777

64 K bytes

 

 

 

 

 

 

 

 

File 10(H)

000000 to 177777

SEG10 000000 to 177777

64 K bytes

 

File

File 10(H)

000000 to 177777

SEG11 000000 to 177777

64 K bytes

Byte

:

 

:

:

:

register

 

address

 

 

 

 

 

*

File 1F(H)

000000 to 177777

SEG1F 000000 to 177777

64 K bytes

 

File 20(H)

000000 to 177777

SEG20 000000 to 177777

64 K bytes

 

 

File 21(H)

000000 to 177777

SEG21 000000 to 177777

64 K bytes

 

 

:

 

:

:

:

 

 

 

 

 

 

 

 

File 2C(H)

000000 to 177777

SEG2C 000000 to 177777

64 K bytes

 

 

JW-31CUH/H1

000000 to 016777

SEG8 000000 to 016777

7680 steps

 

 

 

 

 

 

 

 

JW-32CUH

000000 to 036777

SEG8 000000 to 036777

15872 steps

 

 

 

 

 

 

 

Program

JW-32CUH1

000000 to 036777

SEG8 000000 to 036777

15872 steps

-----

 

 

 

 

address

 

000000 to 076777

SEG8 000000 to 076777

32256 steps

 

 

 

JW-33CUH/H1

000000 to 076777

SEG8 000000 to 076777

32256 steps

 

 

 

 

 

 

 

 

JW-33CUH2/H3

000000 to 076777,

SEG8 000000 to 076777,

64512 steps

 

 

100000 to 176777

SEG9 000000 to 076777

 

 

 

 

 

 

 

 

 

 

 

 

*ME-NET addresses (SEG10 to 2C) of file 10 to 2C(H) are out of ranges of the ME-NET specification. These are special addresses for the JW-21MN.

-Available addresses vary with PC model on which the JW-21MN is installed and its capacity. For details, see an instruction manual for each PC.

8-4

Image 32
Contents JW-21MN JW-21MN Wiring Compel Safety PrecautionsInstallation Maintenance Prohibit UseME-NET Module JW-21MN Table of contents Description for Computer Link Operation 10-1 to Setting of Switches and Parameter 11-1 toErrors and Countermeasures 12-1 to Appendix 16-1 to Support Tools 14-1 to Specifications 15-1 to13-1 Computer link function Features and FunctionsData link function Installation WiringConnector Maintenance TreatmentStatic electricity Allocation of relay numberSystem Configuration JW20H JW-21MN JW-21MN JW30HName and Function of Each Part Front viewRemarks InstallationInstallation procedure Processing of Cables Name Model MakerProcessing cable end Removal of coating, external conductor, and insulator Fine adjustment of blade cutting depthCutting of coating, external conductor, and insulator Display of blade setting Processing of cable endConnector crimping procedure Connector ME-GP-01 Processing procedure Insert a sleeveRequired tools Hand-held crimping tool Crimping contactConductivity test Fixing the connectorInsulation test Relaying of trunk cables Wiring MethodCable trunk and branch lines Cable wiring procedure in control panel Page Waterproof and insulation processing of connectors Branch connectorStraight connector RemarksWiring of cables at outside control panels Check after wiringBranching method Station number of the additional stationReason Memory address map against JW20/JW20H Memory Address on the ME-NETMemory address for data links Memory address map against JW30H JW30H address ME-NET addressMemory addresses for computer links JW20/20H ME-NET address CapacityJW30H address ME-NET address Capacity Remarks Description for Data Link Operation Communication methodData link Standard function Relay linkRegister link Setting item Set locationData link Save memory function Required transmission time and communication delay time Required transmission timeCommunication delay time Data transmission between master PC and slave PC An example of synchronized transfer by OUT instructionCase of mounting 4 sets of JW-21MN Multiple installation of the JW-21MNExpansion of network Hierarchical link Basic commands Optional commandsDescription for Computer Link Operation Computer link functionBasic commands 10-2Communication format, basic pattern Optional commands10-3 Write mode assignment None Communication format Read free memory sizeMonitor TMR, CNT, and MD 10-410-5 Reading PC modeSetting PC mode 10-6 Reading system memoryWriting system memory Setting date Write mode assignment 1 or Communication formatReading date 10-710-8 Setting timeReading time 10-9 Correct clock timeMonitor step status JW20/JW20H only Write mode assignment Read the optional parametersSet the optional parameters 10-1010-11 Read the special I/O parametersSet the special I/O parameters 10-12 Release the secret function, register password JW30H onlySet the secret function JW30H only Check the secret function JW30H only 10-13Response on error 10-1411-1 Setting of Switches and ParameterOperation procedure Switch setting of master station and slave station Mode switch ModeModule No. switch Unit no 11-2Station number switch STA no Termination resistance switch LT11-3 Reference Need for the termination resistanceShield ground switch LG 11-4Setting contents of master station parameters 11-6 Value HParameter for setting in master station Parameter for setting in slave stationCommunication area map 11-711-8 + h 11-9Maser station Slave station Standard Save memory Example for setting11-10 When master station PC is JW20/JW20H 11-11When master station PC is JW30H 11-12Setting procedure 11-13Stop operation of data link HEX hexadecimal, byte 11-14Example Stop operation of data link HEX hexadecimal, byte 11-15 Data link function setting HEX hexadecimal, byteSet number of connecting stations DCM decimal, byte 11-16 Set top address of register link area on the master station11-17 Set in parameter addresses 005000 to11-18 11-19 Set connection status of slave station Bit pattern, byte11-20 11-21 PC operation11-22 Setting itemContents Setting range of flag area When PC is JW20/JW20HWhen PC is JW30H 11-2311-24 Turn on the power of slave station PC Connect support tools 11-2511-26 11-27 11-28 Errors and Countermeasures Indication lamps12-1 Details MeasureFlag RemarkCase of a master station 12-3Communication monitor flag Operation condition monitor flagCase of slave station 01 to 12-4Monitor operation condition by each station PC 12-5Storage of error code 12-6System memory #170 to 177 option module error code System memory #160 to 167 self diagnosis error codeSystem memory #150 monitor error switch number 12-7Error history 12-8Replacement of the JW-21MN 13-114-1 Support ToolsRecord and load by ladder software JW-92SP, JW-50SP Record Load 14-2Load to the personal computer Stop operation of the JW-21MNSpecifications General specificationsCommunication specifications SpecificationData link specifications Standard function SpecificationsSave memory function Specifications 15-215-3 Computer link specificationsOutside dimensional drawings 16-1 Maintenance and checkAppendix 16-2 Recovery method at communication errorsCheck flow chart Check cable/connector 16-316-4 Cause Countermeasure16-5 007764 toSwitches required check in the JW-21MN Check items of cables and connectors16-6 Other casesCheck the errors timing Identify the error stationWhen identification of the cause is difficult 16-7Master station Table of parameter memory16-8 Set contents Setting method value, example 16-916-10 16-11 16-12 Slave station 01 toSpecial functions unique to the JW-21MN 16-13Remote programming and remote monitor Support tool Opposite module Connection module16-14 Function Standard network connectionExpansion network connection Operation exampleNetwork setting 16-1516-16 Parameter setting by remote functionWhen used with a computer link Alphabetical Index Operation procedure Waterproof and insulation processing of connectors