Sharp JW-21MN manual 11-22, Setting item, Contents

Page 75

11

11-4 Setting slave station parameters (common for all slave stations)

When the JW-21MN is used as a slave station, set the following items for parameters.

[1] Setting contents

 

 

 

 

Setting item

 

 

Initial

Contents

Corresponding

 

 

 

 

 

Address(8)

signs on pages

 

 

 

 

 

value (H)

 

 

 

 

 

11-7 to 11-9

 

 

 

 

Number of receiving bytes of

 

 

Set the number of bytes by decimals. (0 to 256)

 

 

 

 

 

 

relay link in save memory

 

007720

00

- If 0 is set, the number of bytes will be the same

h1 to hn

 

 

 

function

 

007721

as the number of the sending bytes which is set

 

 

 

 

 

V2

 

in the master station

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

*1

 

 

 

 

 

 

 

 

 

 

 

 

Number of receiving bytes of

 

 

Set the number of bytes by decimals. (0 to 2048)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

register link in save memory

007722

00

- If 0 is set, the number of bytes will be the same

i1 to in

 

 

 

function

 

007723

as the number of the sending bytes which is set

 

 

 

 

 

V2

 

 

in the master station

 

 

 

 

*2

Whether the station number

 

00

Store the number of own statin in the data memory

 

 

 

information should be output

007763

when setting on 01(H). (storage area of 1 byte follows

 

 

 

 

 

 

 

 

 

 

or not

V2

 

 

flag area of 24 bytes, valid when 007767(8) is 80(H))

 

 

 

 

 

 

 

 

 

007764

E0

Lower of file address

 

Initial value: 01E0(H)

 

 

 

 

 

 

 

Top address of flag area

 

007765

01

 

 

 

 

 

 

 

 

 

Upper of file address

 

000740(8) (0740)

e1 to en

 

 

 

(communication and PC

 

 

 

 

 

 

 

00

 

 

 

 

 

 

 

operation condition monitor

007766

File number

 

 

 

 

 

 

 

 

flag)

 

007767

80

Flag output (Yes: 80(H) No: 00(H))

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

00(H): Stop operation

 

 

 

 

 

 

 

 

- Start/stop operation of the

 

 

01(H): Start operation

 

 

 

 

 

 

 

JW-21MN

 

007777

01

80(H): Writing to the EEPROM, stop operation

 

 

 

 

 

 

- Writing to EEPROM of the

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

JW-21MN

 

 

 

81(H): Writing to the EEPROM, start operation

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

08(H): Parameter initializing

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

*1: Set only when the memory capacity save function is used.

*2: "Whether the station number information should be output or not" is a unique function of the JW-21MN.

-Parameter addresses other than above mentioned are reserved areas and prohibited to be changed.

-When any slave stations are except JW-21MN, see the instruction manual of each device.

11-22

Image 75
Contents JW-21MN JW-21MN Safety Precautions InstallationWiring Compel Use Maintenance ProhibitME-NET Module JW-21MN Table of contents Setting of Switches and Parameter 11-1 to Errors and Countermeasures 12-1 toDescription for Computer Link Operation 10-1 to Support Tools 14-1 to Specifications 15-1 to 13-1Appendix 16-1 to Features and Functions Data link functionComputer link function Wiring InstallationConnector Allocation of relay number MaintenanceTreatment Static electricityJW20H JW-21MN JW-21MN JW30H System ConfigurationFront view Name and Function of Each PartInstallation Installation procedureRemarks Name Model Maker Processing of CablesProcessing cable end Fine adjustment of blade cutting depth Cutting of coating, external conductor, and insulatorRemoval of coating, external conductor, and insulator Processing of cable end Display of blade settingCrimping contact Connector crimping procedureConnector ME-GP-01 Processing procedure Insert a sleeve Required tools Hand-held crimping toolFixing the connector Insulation testConductivity test Wiring Method Cable trunk and branch linesRelaying of trunk cables Cable wiring procedure in control panel Page Remarks Waterproof and insulation processing of connectorsBranch connector Straight connectorCheck after wiring Wiring of cables at outside control panelsStation number of the additional station Branching methodReason Memory Address on the ME-NET Memory address for data linksMemory address map against JW20/JW20H JW30H address ME-NET address Memory address map against JW30HJW20/20H ME-NET address Capacity Memory addresses for computer linksJW30H address ME-NET address Capacity Remarks Relay link Description for Data Link OperationCommunication method Data link Standard functionSetting item Set location Data link Save memory functionRegister link Required transmission time Required transmission time and communication delay timeCommunication delay time An example of synchronized transfer by OUT instruction Data transmission between master PC and slave PCMultiple installation of the JW-21MN Expansion of networkCase of mounting 4 sets of JW-21MN Hierarchical link Computer link function Basic commandsOptional commands Description for Computer Link Operation10-2 Basic commandsOptional commands 10-3Communication format, basic pattern 10-4 Write mode assignment None Communication formatRead free memory size Monitor TMR, CNT, and MDReading PC mode Setting PC mode10-5 Reading system memory Writing system memory10-6 10-7 Setting dateWrite mode assignment 1 or Communication format Reading dateSetting time Reading time10-8 Correct clock time Monitor step status JW20/JW20H only10-9 10-10 Write mode assignmentRead the optional parameters Set the optional parametersRead the special I/O parameters Set the special I/O parameters10-11 Release the secret function, register password JW30H only Set the secret function JW30H only10-12 10-13 Check the secret function JW30H only10-14 Response on errorSetting of Switches and Parameter Operation procedure11-1 11-2 Switch setting of master station and slave stationMode switch Mode Module No. switch Unit noReference Need for the termination resistance Station number switch STA noTermination resistance switch LT 11-311-4 Shield ground switch LGSetting contents of master station parameters Value H 11-611-7 Parameter for setting in master stationParameter for setting in slave station Communication area map11-8 11-9 + hExample for setting 11-10Maser station Slave station Standard Save memory 11-11 When master station PC is JW20/JW20H11-12 When master station PC is JW30H11-13 Setting procedure11-14 Example Stop operation of data link HEX hexadecimal, byteStop operation of data link HEX hexadecimal, byte Data link function setting HEX hexadecimal, byte Set number of connecting stations DCM decimal, byte11-15 Set top address of register link area on the master station 11-16Set in parameter addresses 005000 to 11-1711-18 Set connection status of slave station Bit pattern, byte 11-1911-20 PC operation 11-21Setting item Contents11-22 11-23 Setting range of flag areaWhen PC is JW20/JW20H When PC is JW30H11-24 11-25 Turn on the power of slave station PC Connect support tools11-26 11-27 11-28 Details Measure Errors and CountermeasuresIndication lamps 12-1Remark FlagOperation condition monitor flag Case of a master station12-3 Communication monitor flag12-4 Case of slave station 01 to12-5 Monitor operation condition by each station PC12-6 Storage of error code12-7 System memory #170 to 177 option module error codeSystem memory #160 to 167 self diagnosis error code System memory #150 monitor error switch number12-8 Error history13-1 Replacement of the JW-21MNSupport Tools Record and load by ladder software JW-92SP, JW-50SP Record14-1 Stop operation of the JW-21MN Load14-2 Load to the personal computerSpecification SpecificationsGeneral specifications Communication specifications15-2 Data link specificationsStandard function Specifications Save memory function SpecificationsComputer link specifications Outside dimensional drawings15-3 Maintenance and check Appendix16-1 Recovery method at communication errors Check flow chart16-2 16-3 Check cable/connectorCause Countermeasure 16-4007764 to 16-5Other cases Switches required check in the JW-21MNCheck items of cables and connectors 16-616-7 Check the errors timingIdentify the error station When identification of the cause is difficultTable of parameter memory 16-8Master station 16-9 Set contents Setting method value, example16-10 16-11 Slave station 01 to 16-12Support tool Opposite module Connection module Special functions unique to the JW-21MN16-13 Remote programming and remote monitorOperation example 16-14Function Standard network connection Expansion network connection16-15 Network settingParameter setting by remote function When used with a computer link16-16 Alphabetical Index Operation procedure Waterproof and insulation processing of connectors