To calculate the AXlink wiring distance formula for data and power:

1.<Total current consumption of all device's on AXlink cable> *<wire resistance per foot> * 2 = <voltage drop per foot>. See tables below for the Wire Resistance/Foot values.

2.<Power supply voltage> - 12 VDC = <surplus voltage dissipation for cable run>.

3.<Surplus voltage dissipation for cable run> / < voltage drop per foot > = Maximum distance in feet.

The following table lists the resistance factors used in the formula.

Gauge/resistance factors - Solid Copper Wiring

Wire gauge

Wire Resistance/foot

 

 

18 AWG

.00639

 

 

20 AWG

.0101

 

 

22 AWG

.0162

 

 

24 AWG

.0257

 

 

For further details on AxLink Wiring, refer to the AXlink Wiring Considerations Instruction Manual (available online at www.amx.com).

Assigning the ANT-RDR Device Address

The ANT-RDR sets its AXLink address via the 8-position DEVICE DIP switch located on the rear panel (FIG. 13).

FIG. 13 Device DIP Switch

The AXLink address distinguishes a device on the AXLink bus from other devices. Care should be taken by the system integrator not to assign duplicate AXLink addresses to multiple devices.

AXLink addresses must be in the range of 1 to 255 (address 0 belongs to the Master).

As indicated on the device, flip each switch down for the ON position.

Device DIP Switch Settings

Position

1

2

3

4

5

6

7

8

 

 

 

 

 

 

 

 

 

Value

1

2

4

8

16

32

64

128

 

 

 

 

 

 

 

 

 

For example, the DIP switch shown in FIG. 13 defines Device 96 (switches 6 and 7 = ON).

The device number takes effect only upon power-up. If you later change the device number, remove and reconnect the AXlink connector to enter the new device number into memory.

Anterus RFID Solution

13

 

 

Image 17
Contents Anterus AMX Limited Warranty and Disclaimer Table of Contents Anterus Configuration Manager Overview Anterus Rfid SolutionAnterus Rfid Group ANT-RDR Rfid ReaderANT-RDR Specifications ANT-RDR Product SpecificationsANT-RDR Mounting/Installation Anterus Rfid Tags Rfid Tags Internal BatteryANT-TAG Device/Asset Tag ANT-TAG Product SpecificationsANT-TAG Specifications ANT-TAG Antenna Orientation ANT-TAG Mounting/InstallationANT-BDG ID Badge Tag ANT-BDG Mounting/Installation ANT-BDG Product SpecificationsANT-BDG Specifications ANT-BDG Antenna OrientationEnvironmental Factors Signal Strength Behavior of AMX Rfid Tags and ReadersNon-Ideal Antenna Gain Antenna ElevationPeople and Objects AnalysisMultipath Fading Measured DataConclusions Signal Strength Count BehaviorConnecting Additional ANT-RDRs Connecting the ANT-RDR To a NetLinx MasterPower Distribution Wiring GuidelinesCalculating AXlink wiring distances Cable Types and Maximum DistancesDevice DIP Switch Settings Gauge/resistance factors Solid Copper WiringWire gauge Wire Resistance/foot Assigning the ANT-RDR Device AddressInstallation Anterus Rfid Solution Accessing the Rfid Configuration Manager Anterus Configuration ManagerOpen the Manage Devices tab FIG Rfid Configuration Manager page FIG Rfid Configuration Manager MainRfid Configuration Manager Global Register Global RegisterGlobal Register page Global Reader Configuration Options Global Reader Configuration OptionsRemoving a Tag from the System Adding a Tag to the SystemTag Configuration Options Global Register Anterus Tags Configuration OptionsTag Details Popup Viewing Tag DetailsReader Configuration Page with Reader 205 selected Reader Configuration PagesReader Configuration Reader Configuration OptionsStatus Acquired/Offline Tag Configuration Options Reader ConfigurationImplementing the Anterus Duet Module Anterus Duet Module OverviewSend Commands NetLinx Send CommandsAxLink Programming Overview Port Mapping?AP Channel Type Function Description AXLink ChannelsAXLink Channels Type Function Description AXLink LevelsAXLink Levels Programming Anterus Rfid Solution Programming Anterus Rfid Solution It’s Your World Take Control