3.9.6Connecting the SEG-M to a Max 3 System (RS-485)

You can connect your Max 3 to your LAN/WAN by using the SEG-M, Secured Ethernet Gateway. Follow the instructions below and refer to the diagram.

The connection from the SEG-M to the Max 3 requires you to plug the module onto the backplane connector S1 to power the unit. You must also use the six-conductor wire harness from J1 on the SEG-M to P5 on the module and J1 on the backplane. If you have more than one module on the backplane, you must connect each module to the corresponding RS-485 connector (J2, J3 or J4) underneath the module as described in the Max 3 Installation Manual.

To connect additional backplanes to the system, simply connect TS3 on the first backplane to TS3 on the next backplane as shown below. The SEG-M is only required on the first backplane of the system (up to 64 doors Max; if you require more doors an additional SEG-M is required).

Note: The maximum distance between the first backplane with the SEG-M and the next backplane is 4000 feet using 24AWG, shielded, two twisted-pair telephone cable with a shunt capacitance of 16 pF/Ft.

Document Number: 6066005, Rev 3.2

Page 15 of 34

Image 15
Contents Ordering Information Secure Ethernet Gateway SEG-1 and SEG-MTable of Contents LED Status Product SpecificationsSEG-1 Diagrams Hardware InstallationSEG-1 to HubMax/Hub MiniMax Connection Method Connection the SEG-1 to a HubMax or Hub MiniMax RS-232SEG-1 to HC500P Connection Method Connecting the SEG-1 to HC500P RS-232Connecting Multiple HubMax/Hub MiniMax Networks SEG-1 to prox.pad plus Connection Method Connecting the SEG-1 to a prox.pad plus RS-485Connecting Multiple prox.pad plus Networks Connecting the SEG-1 to a Max 3 System RS-485 Connecting the SEG-1 to a MiniMax 3 System RS-485 SEG-M Diagram SEG-M Installation Plug On ModulePin Label Description SEG-M ConnectorsSEG-M LED Indicators Connector Description Pin Configuration LabelConnecting the SEG-M to a Hub MiniMax System RS-232 Connecting the SEG-M to a HubMax System RS-232Connecting the SEG-M to a Max 3 System RS-485 Connecting the SEG-M to a MiniMax 3 System RS-485 MAC Address Description SEG ConfigurationNo SEG parameters defined Found SEGs are displayed in grid Generate Security Key Dynamic IP Address, non-expiring leaseStatic IP Address Document Number 6066005, Rev Document Number 6066005, Rev SEG Setup Menu Sever Configuration Channel 1 Configuration Settings of the RS-232 PortChannel 2 Configuration Settings of the RS-485 Port Save and Exit Factory DefaultsSecurity Exit Without SaveSEG Parameters Generate Random Security Key Defaulting the SEG SettingsGenerate Default Security Key Reset the Security Key in the SEG to all 0sReset the Security Key in the PC to all 0s Trouble Shooting Document Number 6066005, Rev Document Number 6066005, Rev FCC Compliance Statement