American International Electric SEG-1 Defaulting the SEG Settings, Generate Random Security Key

Page 28

4.4.5Generate Random Security Key

This button will generate a new 128 bit security key and will then display the hexadecimal representation in the 'Current Security Key' field (see below)

4.4.6Generate Default Security Key

After selecting this option, you will receive a warning message explaining that setting the security key back to defaults should only be done if you are installing a new SEG or if you have defaulted an existing SEG. Once you agree to this, you must then choose the button labeled 'Set This Security Key into the Gateway'. You will then receive a confirmation message that explains that this option will just save the defaulted security key into the Hub Manager Pro database. You can now install your new or defaulted SEG onto the LAN and attempt to communicate with it. Don't forget to change the security key once you have established communications with the new (or defaulted) SEG.

4.4.7Set This Security Key into the SEG

Use this option if you wish to set a new random security key into the SEG. The encryption key displayed in the 'Current Security Key' field is what is sent during this procedure.

NOTE: In order to change a security key in a SEG, Hub Manager Pro must already know the existing security key that is stored in the SEG. If you think there has been a mix up, and you think Hub Manager Pro may not know the SEG's security key, then you should perform the steps to 'Default the Gateway to Factory Settings' noted below, and when that process is complete, you can then attempt to change the security key.

4.5Defaulting the SEG Settings

The following section describes how to reset the default settings in the SEG.

4.5.1Reset the Security Key in the SEG to all 0's

NOTE: This method must be followed if the firmware version of the SEG is less than v1.30.

The SEG must be removed from the LAN and brought back to the PC (or bring a laptop with a serial com port to the SEG) . You will then enter the configuration menu through the serial connection. The configuration utility cannot be entered into though the Ethernet port. This is done so that not just anyone on the LAN could change the settings of the SEG without having physical access to the SEG itself.

NOTE: This process may also be necessary if you have used the Restore Database function of Hub Manager Pro and the Security Key stored in the database that you just restored does not match the security key currently stored in the SEG.

To default the encryption security key in the SEG, you must perform the following in order:

1.Connect the supplied DB9 adapter labeled 'Gateway Config' to your PC's com port.

2.Remove the Gateway from the LAN (and power supply) and bring it back to the PC.

3.Use the 6' modular cord (supplied with the SEG) and plug it into the port on the SEG labeled 'RS232'.

4.Select the button labeled Launch SEG Serial Port Setup Utility and set the Com Port the SEG is connected to when asked.

5.Disconnect power to the SEG.

6.Press and hold down the x key (lowercase) on the PC keyboard, while the HyperTerminal program is running.

7.Power up the SEG.

8.In a few seconds you should get a response from the SEG and a menu will be displayed.

9.Choose the option labeled 'factory defaults'. The SEG will then be set back to Out-Of-Box factory defaults. You can now configure the SEG as if you are installing it for the first time.

10.In order to speak to this SEG again , you will now need follow the directions above to Default the Security Key in Hub Manager Pro. Be sure to set a new security key into the SEG before you attempt to send sensitive user data to the door controllers.

Page 28 of 34

Document Number: 6066005, Rev 3.2

Image 28
Contents Secure Ethernet Gateway SEG-1 and SEG-M Ordering InformationTable of Contents Product Specifications LED StatusHardware Installation SEG-1 DiagramsConnection the SEG-1 to a HubMax or Hub MiniMax RS-232 SEG-1 to HubMax/Hub MiniMax Connection MethodConnecting the SEG-1 to HC500P RS-232 SEG-1 to HC500P Connection MethodConnecting Multiple HubMax/Hub MiniMax Networks Connecting the SEG-1 to a prox.pad plus RS-485 SEG-1 to prox.pad plus Connection MethodConnecting Multiple prox.pad plus Networks Connecting the SEG-1 to a Max 3 System RS-485 Connecting the SEG-1 to a MiniMax 3 System RS-485 SEG-M Installation Plug On Module SEG-M DiagramSEG-M Connectors SEG-M LED IndicatorsConnector Description Pin Configuration Label Pin Label DescriptionConnecting the SEG-M to a HubMax System RS-232 Connecting the SEG-M to a Hub MiniMax System RS-232Connecting the SEG-M to a Max 3 System RS-485 Connecting the SEG-M to a MiniMax 3 System RS-485 SEG Configuration MAC Address DescriptionNo SEG parameters defined Found SEGs are displayed in grid Dynamic IP Address, non-expiring lease Generate Security KeyStatic IP Address Document Number 6066005, Rev Document Number 6066005, Rev SEG Setup Menu Channel 1 Configuration Settings of the RS-232 Port Sever ConfigurationChannel 2 Configuration Settings of the RS-485 Port Factory Defaults SecurityExit Without Save Save and ExitSEG Parameters Defaulting the SEG Settings Generate Default Security KeyReset the Security Key in the SEG to all 0s Generate Random Security KeyReset the Security Key in the PC to all 0s Trouble Shooting Document Number 6066005, Rev Document Number 6066005, Rev FCC Compliance Statement