American International Electric SEG-M, SEG-1 Reset the Security Key in the PC to all 0s

Page 29

4.5.2Reset the Security Key in the SEG to all 0's

NOTE: This requires SEG firmware v1.30 or higher.

This feature is provided to allow you to reset the Security Key in the SEG back to all 0's, which is the default out-of-box state. Resetting the Security Key in the SEG would be required if you are replacing a SEG with a previously used SEG that already has a Security Key set into it and you don't know what the Security Key is, or if you are setting up a new site and want to communicate with an existing SEG that is already installed and already has a Security Key set. NOTE: This feature can only be used with SEG devices with v1.30 or greater firmware.

1.Go to the SEG and either cycle power to it or press the little black reset button on the SEG.

2.Within 10 minutes, go back to the PC and select the button in the Site Edit screen that is labeled 'Reset the Security Key in the SEG to all 0's'.

3.You will see a warning message specifying the requirements of using this feature. If you have met all the requirements then press the OK button.

4.If the Key was reset properly then you will see a confirmation message (Fig. 8).

5.As a security measure, you must now go back to the SEG and once again cycle power or press the reset button on the SEG. This will set the new Security Key into non-volatile memory. Failure to reset the SEG after the Security Key is reset using this method will result in not being able to communicate with the SEG.

6.Reset Complete. The Security Key has now been reset to all 0's in both the SEG and PC. Communications with this SEG should now be possible.

4.5.3Reset the Security Key in the PC to all 0's

This feature is typically used if you have replaced an existing SEG with a new SEG or a SEG that has a Security of all 0's.

NOTE: If you use this feature and the SEG does not have a Security Key of all 0's then you will have to set the Security Key back to all 0's also.

Document Number: 6066005, Rev 3.2

Page 29 of 34

Image 29
Contents Ordering Information Secure Ethernet Gateway SEG-1 and SEG-MTable of Contents LED Status Product SpecificationsSEG-1 Diagrams Hardware InstallationSEG-1 to HubMax/Hub MiniMax Connection Method Connection the SEG-1 to a HubMax or Hub MiniMax RS-232SEG-1 to HC500P Connection Method Connecting the SEG-1 to HC500P RS-232Connecting Multiple HubMax/Hub MiniMax Networks SEG-1 to prox.pad plus Connection Method Connecting the SEG-1 to a prox.pad plus RS-485Connecting Multiple prox.pad plus Networks Connecting the SEG-1 to a Max 3 System RS-485 Connecting the SEG-1 to a MiniMax 3 System RS-485 SEG-M Diagram SEG-M Installation Plug On ModuleSEG-M LED Indicators SEG-M ConnectorsConnector Description Pin Configuration Label Pin Label DescriptionConnecting the SEG-M to a Hub MiniMax System RS-232 Connecting the SEG-M to a HubMax System RS-232Connecting the SEG-M to a Max 3 System RS-485 Connecting the SEG-M to a MiniMax 3 System RS-485 MAC Address Description SEG ConfigurationNo SEG parameters defined Found SEGs are displayed in grid Generate Security Key Dynamic IP Address, non-expiring leaseStatic IP Address Document Number 6066005, Rev Document Number 6066005, Rev SEG Setup Menu Channel 2 Configuration Settings of the RS-485 Port Sever ConfigurationChannel 1 Configuration Settings of the RS-232 Port Security Factory DefaultsExit Without Save Save and ExitSEG Parameters Generate Default Security Key Defaulting the SEG SettingsReset the Security Key in the SEG to all 0s Generate Random Security KeyReset the Security Key in the PC to all 0s Trouble Shooting Document Number 6066005, Rev Document Number 6066005, Rev FCC Compliance Statement