APC AP9606 UPS PowerChute network shutdown Option, Snmp Management Card utility CD, Parameters

Page 48

Device Manager Menus

UPS PowerChute network shutdown Option

Overview

A PowerChute option in the Web interface’s UPS menu allows you to

 

use the APC PowerChute network shutdown utility to shut down servers

 

on your network that are using any client-version of PowerChute

 

network shutdown.

 

 

For more information about PowerChute network shutdown, see the

 

following documents provided in the .\pcns directory on the APC Web/

 

SNMP Management Card utility CD:

 

PowerChute network shutdown Installation Guide (Install.htm)

 

PowerChute network shutdown Release Notes (Relnotes.htm)

 

PowerChute Network Shutdown with more than 50 Computers

 

on One UPS (50.pdf)

Parameters

The following table describes the PowerChute network shutdown

 

parameters.

 

 

 

 

 

 

Parameter

 

Definition

 

 

 

 

 

Event

 

Identifies the port on which the PowerChute network shutdown

 

Notification Port

 

clients will listen for asynchronous events. This value is not

 

 

 

configurable.

 

 

 

 

 

Shutdown

 

Defines how the UPS will be turned off after the PowerChute

 

Behavior

 

network shutdown clients finish shutting down their computer

 

 

 

systems.

 

 

 

 

 

Add Client IP

 

Allows you to add up to 50 PowerChute network shutdown

 

 

 

clients to the list of Configured Client IP Addresses. A

 

 

 

PowerChute network shutdown client is also added to the list

 

 

 

automatically when that client is installed on your network.

 

 

 

Note: For information about how you can shut down more

 

 

 

than 50 PowerChute network shutdown clients that

 

 

 

connect to a single UPS, see PowerChute Network

 

 

 

Shutdown with more than 50 Computers on One UPS

 

 

 

(50.pdf) in the .\pcns directory on the APC Web/SNMP

 

 

 

Management Card utility CD

 

 

 

 

 

Configured

 

Allows you to view the list of PowerChute network shutdown

 

Client IP

 

clients, and remove PowerChute network shutdown clients

 

Addresses

 

from the list. A PowerChute network shutdown client is also

 

 

 

removed from the list automatically when that client is

 

 

 

uninstalled.

 

 

 

 

Web/SNMP Management SmartSlot Card User’s Guide

48

Image 48
Contents Title Thank You Contents Web/SNMP Management SmartSlot CardContents System Menu Events Menu Index American Power Conversion’s Web/SNMP Management SmartSlot Product DescriptionCard APC part number AP9606 is a web-based UPS Management Snmp Management SmartSlot Card, which is referred to asIntroduction Figure below identifies and describes the network management Through a Management CardInternal Management Features Password and User Name settings, see User Manager onFront Panel Watchdog Features Control Console IntroductionHow to Log See How to Recover from a Lost Password onControl Console Console, see Main Screen onHow to Recover from a Lost Password Main Screen Into the Control ConsoleTwo fields identify when you logged in, by Date and Time Status field reports the Management Card statusUPS model and name field reports the status of the UPS Control Console Menu Menus onWeb Interface You can use a supported Web browser to manage a UPS, anServer, Telnet, and Web on Netscape Navigator 3.0 or laterWeb Interface Web interface, see Status Summary Page onTion, see Email on Status Summary Menu Frame Device Manager Menus onUser-definable links on Being powered by the UPS AccessPages at the APC Web site Click on Links in the System menuNetwork Menu Option Settings Gateway plays, see The role of the Default GatewayResetting the network timer on page 13 for infor Network MenuDownload configuration files 0.0.0.0, by default Used to protect FTP accessSettings are 21 FTP, 23 Telnet, and 80 Web interface APC Web/SNMP Management Card utility CD ./docSetting Definition System Menu System Menu Web interfaceHhmmss format used by the Management Card For file transfers, do the followingDefine the file name in the Filename field, and click Apply Screen instructionsThree User Links, the URL address used by the APC logo, URL address used by the various Interactive Assistant linksDevice Manager Menus Environment Menu Options onDevice Manager Menus UPS Status OptionsStatus for a Symmetra Power Array or Silcon DP300E series VoltageStatus Field Definition Load Power Output VoltageOutput FrequencyOutput Power PercentagePeak Output CurrentRemaining is shared by all UPS models Displayed above the UPS MenuUPS Diagnostics Options UPS Control Options Action DefinitionTest UPS Alarm options, see UPS Diagnostics Options on Table in Shutdown parameters onUPS Configuration Options Utility line settings on thisAlarm thresholds Symmetra Power Array on General settings onThreshold Definition Option to access the Return Battery Capacity setting Last Battery ReplacementAudible Alarm UPS NameModule Status Option Symmetra Power Array UPS PowerChute network shutdown Option For more information about PowerChute network shutdown, seeFollowing table describes the PowerChute network shutdown Snmp Management Card utility CDSee Probe settings below Environment Menu OptionsDescribed in How to Configure Individual Events Events MenuEvents Menu Event LogActions Web Interface only on FTP Or disabled for events with a specified severity level Event Actions Web Interface onlyEvents are recorded Assigned will still be loggedBy their specific IP addresses Recipients onEvent Recipients As described in Event Actions Web Interface only onTo which traps will be sent Snmp option in the Network menu See Email on the nextTing in Email recipients on Option. See Optimal Email Configuration Issues on Events Menu How to Configure Individual Events Example, to configure the UPS on battery event, as follows To log the event, and send traps to trap receivers 1Change the 2nd character to B Ents 1 and 2, change the 3rd character toManagement Card and Device Events Actions associated with an event, see Event Actions WebInterface only on System events in the table’s descriptionsEvents are generated by all UPS models Events Menu Events Menu Events Menu Environmental Monitoring SmartSlot Card events Security Features SecurityAuthentication SecurityInterface Security Access MethodsTroubleshooting Problem SolutionManagement Card Troubleshooting Following table describes known Snmp problemsHow to Correct Communication Lost Problems Technical Support on page 74 for information about how toIf Problems Persist APC Worldwide Technical Support Warranty Information Product InformationPersist on Product Information Life-Support PolicySpecifications Following table identifies the electrical specificationsFollowing table identifies the physical specifications Following table identifies the environmental specificationsAccept Changes option, 14 Access IndexIndex Device Manager menu optionsFTP Events, 23 24, 51, 53 Snmp UPS events, listed and described W. a p c c . c o m

AP9606 specifications

The APC AP9606 is a sophisticated environmental monitoring device designed to enhance the functionality and efficiency of data centers and critical IT environments. As part of APC’s suite of infrastructure solutions, the AP9606 is primarily aimed at monitoring conditions in rack-mounted and remote locations. By implementing advanced features and technologies, it ensures that environmental conditions remain optimal to prevent equipment failure and provide high availability for business operations.

One of the main features of the AP9606 is its ability to monitor and report various environmental factors including temperature, humidity, and other critical conditions. This real-time monitoring capability allows IT managers to react promptly to changing environmental variables which can significantly impact server and equipment performance. The device can be connected to a multitude of sensors, enabling users to customize their monitoring setups depending on specific requirements.

The AP9606 utilizes SNMP (Simple Network Management Protocol) for seamless integration with existing network management systems. This protocol allows easy communication between the device and other network elements, further enabling IT departments to consolidate and manage their infrastructure efficiently. Additionally, support for web-based interfaces gives users the flexibility to access real-time data from virtually anywhere, facilitating remote management capabilities which are crucial for businesses with multiple locations.

In terms of connectivity, the AP9606 is equipped with multiple ports, including an Ethernet port for network connection and optional serial ports for connecting with compatible devices. The inclusion of both wired and wireless options ensures that the device can adapt to various network environments, making it particularly versatile.

One of the standout characteristics of the APC AP9606 is its scalability. As businesses evolve, so do their monitoring needs. The AP9606 can be easily expanded with additional sensor modules, allowing businesses to grow their monitoring capabilities without needing entirely new systems. This flexibility makes it a cost-effective solution in the long run.

In summary, the APC AP9606 environmental monitoring device stands out due to its comprehensive monitoring features, robust connectivity options, and scalability. It is particularly well-suited for data centers and critical infrastructure environments where maintaining optimal conditions is essential. By investing in the AP9606, businesses can ensure they are proactively managing their IT assets, ultimately leading to improved operational performance and reduced risk of equipment failure.