APC AP9606 manual Example, to configure the UPS on battery event, as follows, Ter to

Page 60

Events Menu

How to Configure Individual Events continued

Event mask

Use the codes identified in the following table to configure an event. For

 

example, to configure the UPS on battery event, as follows:

 

• To configure it as a severe event, change the 1st character to 3.

 

• To log the event, and send traps to trap receivers 1 and 2,

 

change the 2nd character to B.

 

• To disable traps to receivers 3 and 4, and disable Email recipi-

 

ents 1 and 2, change the 3rd character to 0.

 

• To send Email only to Email recipient 3, change the 4th charac-

 

ter to 8.

 

 

Note: The result would be a code of 3B0800.

 

 

 

 

 

Character

 

Event Mask Code Format

 

 

 

 

1st (Left-

Defines the severity code for the event.

 

Most)

0

(0000): No severity

 

 

 

 

1

(0001): Informational

 

 

2

(0010): Warning

 

 

3

(0011): Severe

 

 

 

 

2nd

Defines whether the event is logged, and whether SNMP traps are

 

 

sent to trap receivers 1 and 2.

 

 

0

(0000): Disable logging and SNMP traps

 

 

1

(0001): Disable logging, send traps to receiver 2

 

 

2

(0010): Disable logging, send traps to receiver 1

 

 

3

(0011): Disable logging, send traps to both receivers

 

 

8

(1000): Enable logging, disable SNMP traps

 

 

9

(1001): Enable logging, send traps to receiver 2

 

 

A (1010): Enable logging, send traps to receiver 1

 

 

B (1011): Enable logging, send traps to both receivers

 

 

 

 

3rd

Controls the sending of SNMP traps to trap receivers 3 and 4, and

 

 

Email notifications to Email recipients 1 and 2.

 

 

0

(0000): Disable traps and Email

 

 

1

(0001): Disable traps, send Email to recipient 2

 

 

2

(0010): Disable traps, send Email to recipient 1

 

 

3

(0011): Disable traps, send Email to both recipients

 

 

4

(0100): Send traps to receiver 3, disable Email

 

 

5

(0101): Send traps to receiver 3, Email to recipient 2

 

 

6

(0110): Send traps to receiver 3, Email to recipient 1

 

 

7

(0111): Send traps to receiver 3, Email to both recipients

 

 

8

(1000): Send traps to receiver 4, disable Email

 

 

9

(1001): Send traps to receiver 4, Email to recipient 2

 

 

A (1010): Send traps to receiver 4, Email to recipient 1

 

 

B (1011): Send traps to receiver 4, Email to both recipients

 

 

C (1100): Send traps to both receivers, disable Email

 

 

D (1101): Send traps to both receivers, Email to recipient 2

 

 

E (1110): Send traps to both receivers, Email to recipient 1

 

 

F (1111): Send traps to both receivers, Email to both recipients

 

 

 

 

4th

Defines whether the event sends Email notifications to Email

 

 

recipients 3 and 4.

 

 

0

(0000): Disable Email

 

 

4

(0100): Send Email to recipient 4

 

 

8

(1000): Send Email to recipient 3

 

 

C (1100): Send Email to both recipients

 

 

 

 

5th and 6th

Reserved for future use. Always map as 00.

 

 

 

 

Web/SNMP Management SmartSlot Card User’s Guide

60

Image 60
Contents Title Thank You Contents Web/SNMP Management SmartSlot CardContents System Menu Events Menu Index American Power Conversion’s Web/SNMP Management SmartSlot Product DescriptionCard APC part number AP9606 is a web-based UPS Management Snmp Management SmartSlot Card, which is referred to asIntroduction Figure below identifies and describes the network management Through a Management CardInternal Management Features Password and User Name settings, see User Manager onFront Panel Watchdog Features Control Console IntroductionHow to Log See How to Recover from a Lost Password onControl Console Console, see Main Screen onHow to Recover from a Lost Password Main Screen Into the Control ConsoleTwo fields identify when you logged in, by Date and Time Status field reports the Management Card statusUPS model and name field reports the status of the UPS Control Console Menu Menus onWeb Interface You can use a supported Web browser to manage a UPS, anServer, Telnet, and Web on Netscape Navigator 3.0 or laterWeb Interface Web interface, see Status Summary Page onTion, see Email on Status Summary Menu Frame Device Manager Menus onUser-definable links on Being powered by the UPS AccessPages at the APC Web site Click on Links in the System menuNetwork Menu Option Settings Gateway plays, see The role of the Default GatewayResetting the network timer on page 13 for infor Network MenuDownload configuration files 0.0.0.0, by default Used to protect FTP accessSettings are 21 FTP, 23 Telnet, and 80 Web interface APC Web/SNMP Management Card utility CD ./docSetting Definition System Menu System Menu Web interfaceHhmmss format used by the Management Card For file transfers, do the followingDefine the file name in the Filename field, and click Apply Screen instructionsThree User Links, the URL address used by the APC logo, URL address used by the various Interactive Assistant linksDevice Manager Menus Environment Menu Options onDevice Manager Menus UPS Status OptionsStatus for a Symmetra Power Array or Silcon DP300E series VoltageStatus Field Definition Load Power Output VoltageOutput FrequencyOutput Power PercentagePeak Output CurrentRemaining is shared by all UPS models Displayed above the UPS MenuUPS Diagnostics Options UPS Control Options Action DefinitionTest UPS Alarm options, see UPS Diagnostics Options on Table in Shutdown parameters onUPS Configuration Options Utility line settings on thisAlarm thresholds Symmetra Power Array on General settings onThreshold Definition Option to access the Return Battery Capacity setting Last Battery ReplacementAudible Alarm UPS NameModule Status Option Symmetra Power Array UPS PowerChute network shutdown Option For more information about PowerChute network shutdown, seeFollowing table describes the PowerChute network shutdown Snmp Management Card utility CDSee Probe settings below Environment Menu OptionsDescribed in How to Configure Individual Events Events MenuEvents Menu Event LogActions Web Interface only on FTP Or disabled for events with a specified severity level Event Actions Web Interface onlyEvents are recorded Assigned will still be loggedBy their specific IP addresses Recipients onEvent Recipients As described in Event Actions Web Interface only onTo which traps will be sent Snmp option in the Network menu See Email on the nextTing in Email recipients on Option. See Optimal Email Configuration Issues on Events Menu How to Configure Individual Events Example, to configure the UPS on battery event, as follows To log the event, and send traps to trap receivers 1Change the 2nd character to B Ents 1 and 2, change the 3rd character toManagement Card and Device Events Actions associated with an event, see Event Actions WebInterface only on System events in the table’s descriptionsEvents are generated by all UPS models Events Menu Events Menu Events Menu Environmental Monitoring SmartSlot Card events Security Features SecurityAuthentication SecurityInterface Security Access MethodsTroubleshooting Problem SolutionManagement Card Troubleshooting Following table describes known Snmp problemsHow to Correct Communication Lost Problems Technical Support on page 74 for information about how toIf Problems Persist APC Worldwide Technical Support Warranty Information Product InformationPersist on Product Information Life-Support PolicySpecifications Following table identifies the electrical specificationsFollowing table identifies the physical specifications Following table identifies the environmental specificationsAccept Changes option, 14 Access IndexIndex Device Manager menu optionsFTP Events, 23 24, 51, 53 Snmp UPS events, listed and described W. a p c c . c o m