3.7 IEEE 1613 Type Tests

 

IEEE Test

 

IEEE 1613

 

 

Description

 

 

Test Levels

 

 

 

 

Clause

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

C37.90.3

9

 

 

ESD

Enclosure Contact

 

+/- 8kV

 

 

 

Enclosure Air

 

+/- 15kV

 

 

 

 

 

 

 

 

 

C37.90.2

8

 

 

Radiated RFI

Enclosure ports

 

35 V/m

 

 

 

 

 

 

 

Signal ports

 

+/- 4kV @ 2.5kHz

 

C37.90.1

7

 

 

Fast Transient

D.C. Power ports

 

+/- 4kV

 

 

 

A.C. Power ports

 

+/- 4kV

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Earth ground ports

 

+/- 4kV

 

 

 

 

 

 

 

Signal ports

 

2.5kV common mode @ 1MHz

 

C37.90.1

7

 

 

Oscillatory

D.C. Power ports

 

2.5kV common & differential mode @ 1MHz

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A.C. Power ports

 

2.5kV common & differential mode @ 1MHz

 

 

 

 

 

 

 

Signal ports

 

5 kV (Failsafe Relay)

 

C37.90

6

 

 

H.V. Impulse

D.C. Power ports

 

5 kV

 

 

 

 

 

 

 

A.C. Power ports

 

5 kV

 

 

 

 

 

 

 

Signal ports

 

2kV AC(Failsafe Relay)

 

C37.90

6

 

 

Dielectric Strength

D.C. Power ports

 

2kV AC

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A.C. Power ports

 

2kV AC

 

 

 

 

 

 

 

 

 

 

 

 

NOTES:

If the unit contains copper ports the IEEE 1613 conformance is Class 1 (During disturbance errors may occur but recovery is automatic).

If the unit contains all fiber ports the IEEE 1613 conformance is Class 2 (During disturbance no errors will occur).

3.8 IEC Environmental Type Tests

 

Test

 

Description

 

Test Levels

 

 

 

 

 

 

 

 

IEC 60068-2-1

 

Cold Temperature

Test Ad

 

-40 deg. C, 16 Hours

 

IEC 60068-2-2

 

Dry Heat

Test Bd

 

+85 deg. C, 16 Hours

 

IEC 60068-2-30

 

Humidity (Damp Heat,

Test Db

 

95% (non-condensing), 55°C, 6 cycles

 

 

Cyclic)

 

 

 

 

 

 

 

 

IEC 60255-21-1

 

Vibration

Tests Fc

 

2g @ (10-150) Hz

 

IEC 60255-21-2

 

Shock

Tests Ea

 

30g @ 11 ms

 

IEC 60529 (IPx6)

 

Ingress Protection

Water Jet

 

100l/m @ 2.5m as per 14.2.6

 

 

 

 

 

 

 

 

IEC 60529 (IPx7)

 

Ingress Protection

Water Submersion

 

30 min @ 1m as per 14.2.7

 

IEC 60529 (IP6x)

 

Ingress Protection

Dust Talcum

 

2kg/m3 for 8h as per 13.4

 

 

 

 

 

 

 

Severity

Levels

N/A

N/A

N/A

Class 2

Class 2

N/A

N/A

Cat. 1&2

23

2008 RuggedCom Inc. All rights reserved

Rev104

Image 23
Contents RuggedSwitch RS969  2008 RuggedCom Inc. All rights reserved Rev104 TrademarksTable of Contents Ethernet Ports Product Overview1 RS969-M12 with Mini-Change Power Connector RS969 Family Ports/Connectors Description2 RS969-RJ45 with M23 Power Connector Activity Comments DIN Rail Mounting InstallationIngress of water Ingress Protection IP67Mini power supply connector M23 power supply connector Power Supply Wiring and GroundingChassis ground screw and the chassis ground connects to Both power supply surge grounds via a removable jumperPS1 Live / + is connected to the positive + terminal if Terminal for AC inputs or the equipment ground bus for DCTerminal # Description Usage Single AC Power Supply Wiring Examples Single DC Power Supply Wiring Examples Dual Power Supplies DC and AC Inputs DC And AC power supply wiring examples Dielectric Strength Testing Failsafe Alarm Relay Wiring and Specifications RS232 over M12 console cable pin-out Console Port WiringPin Signal Fast Ethernet Ports Signal DescriptionOperating Environment Technical SpecificationsPower Supply Specifications Failsafe Relay SpecificationsFiber Optical Port Specifications Twisted Pair Data Port SpecificationsIEC 61850-3 Type Tests IEC Environmental Type Tests Ieee 1613 Type TestsMechanical Specifications Parameter Value Comments Agency Standards Comments Agency ApprovalsConsole 1/unit AccessoriesPower 1/unit Failsafe 1/unit Ethernet 8/unit LC Fiber Optic 2/unit Warranty