Appendix D Technical Specifications

Power Specifications for the Cisco MDS 9506 Director

Se n d d o c u m e n t a t i o n c o m m e n t s t o m d s f e e d b a ck - d o c @ c i s c o . c o m .

Specifications for the Cisco MDS 9506 Power Supplies

Caution The following applies to AC power supplies on the Cisco MDS 9506 only:

The DS-C9506 equipment is suitable for use on TN power systems and the IT-power system connection of Norway (max 230 v phase-phase). If connected to a 230/400-V IT power system, beware of high-leakage current. Earth connection is essential before connecting the supply.

The 1900-W AC power supply provides power based upon the input voltage:

Maximum of 1050 W at input of 100 to 120 VAC

Maximum of 1900 W at input of 200 to 240 VAC

A 110-VAC power cord (CAB-7513AC=)must be ordered separately.

Table D-15lists the specifications for the Cisco MDS 9506 power supplies.

Table D-15 Specifications for Cisco MDS 9506 Power Supplies

Description

Specification

1900-W AC Power Supply

 

 

Type

Autoranging input with power factor corrector.

 

 

 

 

 

 

 

 

Voltage

100 to 240 VAC (±10%).

 

 

 

 

 

 

 

Current rating

12 A maximum at 100 to 120 VAC and 1050-W

 

 

 

output.

 

 

 

12 A maximum at 200 to 240 VAC and 1900-W

 

 

 

output.

 

 

 

Note For current ratings of plugs, see Figure E-5

 

 

 

on page E-9.

 

 

 

 

 

 

 

Frequency

50/60 Hz (nominal) (±3 Hz for full range).

 

 

 

 

 

 

 

Output capacity

1050 W maximum (at input of 100 to 120 VAC).

 

 

 

1900 W maximum (at input of 200 to 240 VAC).

 

 

 

 

 

 

 

Output voltage at 110/120

3.3 V at 2.5 A; 1.5 V at 15 A; 50 V at 20.4 A.

 

 

 

 

 

 

 

Output voltage at 200/240

3.3 V at 2.5 A; 1.5 V at 15 A; 50 V at 37.4 A.

 

 

 

 

 

 

 

 

 

 

1900-W DC Power Supply

 

 

 

 

 

 

 

 

 

 

 

 

Voltage

-48 to -60 VDC continuous.

 

 

 

 

 

 

 

Current rating

50 A at -48 VDC, 40 A at -60 VDC, 60 A at -40.5

 

 

 

VDC.

 

 

 

 

 

 

 

Terminal block

Accommodates 2 to 14 AWG copper conductors.

 

 

 

Use 90°C copper conductors for North American

 

 

 

installations.

 

 

 

Note Actual size of the wire required is

 

 

 

determined by the installer or local

 

 

 

electrician. Terminal block material is rated

 

 

 

at 302°F (150°C).

 

 

 

 

 

 

 

Output capacity

1900 W maximum (at input of -48 to -60 VDC).

 

 

 

 

 

 

 

Output voltage

3.3 V at 2.5 A; 1.5 V at 15 A; 50 V at 37.4 A.

 

 

 

 

 

 

 

 

 

 

 