Send documentation comments to mdsfeedback-doc@cisco.com.
D-8
Cisco MDS 9500 Series Hardware Installation Guide
OL-17467-02
Appendix D Technical Specifications
Power Specifications for the Cisco MDS 9513 Director
AC Power Consumption for the Cisco MDS 9513 Director
Table D-10 shows the typical AC power consumption for a Cisco MDS 9513 Director.
Tab l e D-9 Requirements and Heat Dissipation for 6000-W AC Power Supplies
Module Type/
Product Number
NX-OS
Release
SAN-OS
Release
Power
Required
(watts)
Heat
Dissipation
(BTU/hr)
Input Current
90 VAC
(amps)
120 VAC
(amps)
180 VAC
(amps)
240 VAC
(amps)
Fan tray 1 (front panel),
DS-13SLT-FAN-F
3.x 248 1059 3.44 2.58 1.72 1.29
Fan tray 2 (rear panel),
DS-13SLT-FAN-R
3.x 70 299 0.97 0.73 0.49 0.36
Cisco MDS 9513 chassis,
DS-C9513, with front
(DS-13SLT-FAN-F) and rear
(DS-13SLT-FAN-R) fan trays
3.x 318 1358 4.41 3.31 2.21 1.65
Supervisor-2, DS-X9530-SF2-K9 3.x 126 538 1.75 1.31 0.88 0.66
48-port 4-Gbps switching module,
DS-X9148
3.x 185 790 2.57 1.93 1.28 0.96
24-port 4-Gbps switching module,
DS-X9124
3.x 147 628 2.04 1.53 1.02 0.77
12-port 4-Gbps switching module,
DS-X9112
3.x 132 564 1.83 1.38 0.92 0.69
4-Port 10-Gbps switching module,
DS-X9704
3.x 172 734 2.39 1.79 1.19 0.90
18/4 Multiservice module,
DS-X9304-18K9
3.2.(1) 200 855 2.78 2.08 1.39 1.04
Crossbar module, DS-13SLT-FAB1,
DS-13SLT-FAB2
3.x 63 269 0.88 0.66 0.44 0.33
48-port 8-Gbps switching module,
DS-X9248-96K9
4.x 298 1273 4.14 3.11 2.07 1.55
24-port 8-Gbps switching module,
DS-X9224-96K
4.x 273 1163 3.79 2.84 1.90 1.42
4/44-port 8-Gbps Host-Optimized
switching module,
DS-X9248-48K9
4.x 214 915 2.98 2.23 1.49 1.12