Cisco Systems MDS 9500 Series manual Starting Up the Switch, Connecting the Power Supplies

Models: MDS 9500 Series

1 288
Download 288 pages 59.22 Kb
Page 108
Image 108

Chapter 2 Installing the Cisco MDS 9500 Series

Starting Up the Switch

Se n d d o c u m e n t a t i o n c o m m e n t s t o m d s f e e d b a ck - d o c @ c i s c o . c o m .

Starting Up the Switch

This section provides the following information:

Connecting the Power Supplies, page 2-28

Powering Up the Switch and Verifying Component Installation, page 2-36

Warning Hazardous voltage or energy is present on the backplane when the system is operating. Use caution when servicing. Statement 1034

Caution During this procedure, wear grounding wrist straps to avoid ESD damage to the switch.

Note The 2500-W (DS-CAC-2500W) power supplies provide power according to the input voltage. If they are in redundant rather than combined mode at 110 VAC, they may be unable to provide adequate power to all modules present in the system. See Appendix D, “Technical Specifications.”

Connecting the Power Supplies

The Cisco MDS 9513 Director uses a 6000-W power supply. The 6000-W AC power supplies for the Cisco MDS 9513 Director are designed to provide an output power for the modules and fans. Each power supply has two AC power connections and will provide power as follows:

One AC power connection @110 VAC = No output

Two AC power connection @110 VAC = 2900-W output

One AC power connection @ 220 VAC = 2900-W output

Two AC power connection @ 220 VAC = 6000-W output

Note Power output does not include the power used by the individual modules used in the chassis.

The Cisco MDS 9509 Director and Cisco MDS 9506 Director support both AC and DC power supplies.

The Cisco MDS 9506 Director uses power entry modules (PEMs) to provide power to its power supplies, whether they are AC or DC (there is no power connector on the power supplies). The left PEM (as viewed from the front of the switch) provides power to the upper power supply in the back of the Cisco MDS 9506 Director, and the right PEM provides power to the lower power supply.

This section provides the following topics:

Providing Power to an AC Power Supply for the Cisco MDS 9513 Director, page 2-29

Providing Power to an AC Power Supply for the Cisco MDS 9509 and Cisco MDS 9506 Directors, page 2-30

Providing Power to a DC Power Supply in the Cisco MDS 9509 Director, page 2-33

Providing Power to a DC Power Supply in the Cisco MDS 9506 Director, page 2-34

 

Cisco MDS 9500 Series Hardware Installation Guide

2-28

OL-17467-02

Page 108
Image 108
Cisco Systems MDS 9500 Series manual Starting Up the Switch, Connecting the Power Supplies