Appendix C Cabinet and Rack Installation
Cabinet and Rack Requirements
Se n d d o c u m e n t a t i o n c o m m e n t s t o m d s f e e d b a ck - d o c @ c i s c o . c o m .
•A recommended cabinet depth of 36 to 42 inches (91.4 to 106.7 cm) to allow the doors to close and adequate airflow.
•Bottom of cabinet should be open to enhance airflow.
•The lowest piece of equipment should be installed a minimum of 1.75 inches (4.4 cm) above the floor openings to prevent blocking the floor intake.
The
•A
•Nonperforated (solid and sealed) front and back doors and side panels so that air travels predictably from bottom to top.
•A recommended cabinet depth of 36 to 42 inches (91.4 to 106.7 cm) to allow the doors to close and adequate airflow.
•A minimum of 150 square inches (968 sq. cm) of open area at the floor air intake of the cabinet.
•The lowest piece of equipment should be installed a minimum of 1.75 inches (4.4 cm) above the floor openings to prevent blocking the floor intake.
Requirements Specific to Standard Open Racks
In addition to the requirements listed in the “General Requirements for Cabinets and Racks” section on page
•The minimum width between two front mounting rails must be 17.75 inches (45.1 cm).
•The minimum vertical rack space per chassis:
–Cisco MDS 9513 chassis: 24.5 inches (62.2 cm) or 14 RU.
–Cisco MDS 9509 chassis: 24.5 inches (62.2 cm) or 14 RU.
–Cisco MDS 9506 chassis: 12.25 inches (31.1 cm) or 7 RU.
Note The
Note The side
Note The Cisco MDS 9506 Director does not require shelf brackets.
Cisco MDS 9500 Series Hardware Installation Guide
|
| |
|