![](/images/new-backgrounds/1172963/172963459x1.webp)
Appendix D Technical Specifications
Power Specifications for the Cisco MDS 9506 Director
Se n d d o c u m e n t a t i o n c o m m e n t s t o m d s f e e d b a ck - d o c @ c i s c o . c o m .
Table | Power Requirements and Heat Dissipation for the | ||||||
|
|
|
|
|
|
| |
|
|
| Power | Heat | Input Current |
| |
Module Type/ |
|
| Required | Dissipation |
|
| |
|
|
|
| ||||
Product Number | (watts) | (BTU/hr) | 48 VDC (amps) | 60 VDC (amps) | |||
|
|
|
|
|
| ||
Supervisor/fabric 1 | 3.x | 210 | 956 | 5.83 | 4.67 | ||
|
|
|
|
|
| ||
| 2.x and 1.x | 220 | 1000 | 6.10 | 4.88 | ||
|
| ||||||
|
|
|
|
|
| ||
3.x | 191 | 869 | 5.31 | 4.24 | |||
Fibre Channel module |
|
|
|
|
| ||
2.x and 1.x | 200 | 911 | 5.56 | 4.45 | |||
| |||||||
|
|
|
|
|
| ||
|
|
|
|
|
| ||
3.x | 210 | 956 | 5.83 | 4.67 | |||
Fibre Channel module |
|
|
|
|
| ||
2.x and 1.x | 220 | 1000 | 6.10 | 4.88 | |||
| |||||||
|
|
|
|
|
| ||
|
|
|
|
|
| ||
18/4 Multiservice | 3.2.(1) | 200 | 855 | 2.78 | 2.08 | ||
module, |
|
|
|
|
|
| |
|
|
|
|
| |||
|
|
|
|
|
| ||
3.x | 200 | 910 | 5.56 | 4.44 | |||
|
|
|
|
| |||
2.x and 1.x | 227 | 970 | 3.15 | 2.37 | |||
|
| ||||||
|
|
|
|
|
| ||
3.x | 200 | 910 | 5.56 | 4.44 | |||
|
|
|
|
|
| ||
2.x and 1.x | 220 | 1000 | 6.10 | 4.88 | |||
|
| ||||||
|
|
|
|
|
| ||
| 3.x | 160 | 728 | 4.44 | 3.56 | ||
|
|
|
|
|
| ||
2.x and 1.x | 185 | 841 | 5.14 | 4.11 | |||
|
| ||||||
|
|
|
|
|
|
| |
| 3.x | 281 | 1279 | 7.81 | 6.24 | ||
|
|
|
|
| |||
2.x and 1.x | 295 | 1342 | 8.19 | 6.56 | |||
|
| ||||||
|
|
|
|
|
|
| |
| 3.x | 281 | 1279 | 7.81 | 6.24 | ||
|
|
|
|
| |||
2.x and 1.x | 295 | 1342 | 8.19 | 6.56 | |||
|
| ||||||
|
|
|
|
|
|
| |
CSM |
| 3.x | 200 | 910 | 5.56 | 4.44 | |
|
|
|
|
|
| ||
2.x and 1.x | 210 | 955 | 5.83 | 4.66 | |||
|
| ||||||
|
|
|
|
|
|
|
| Cisco MDS 9500 Series Hardware Installation Guide |