Installation
Slide the adapter into the UPS BestDock
1
0
Set both DIP switches to the 0 (off) position
Figure 2. Installing the Internal BestLink Adapter
4.Set both DIP switches on the adapter to the 0 (off) position.
5.Connect an active 10BaseT cable to the network connector on the BestLink Adapter.
NOTE For an internal BestLink Adapter in a FERRUPS 0800, Axxium Pro, or Powerware 9170 UPS, you MUST change the Config BestDock parameter for that UPS to BestDock 1 or 2 as applicable. Refer to the UPS user’s guide for detailed instructions on how to change the parameter through the UPS front panel configuration menu.
6.Continue to “Configuration” on page 6.
Installing the External BestLink Adapter
To install the external BestLink SNMP/WEB Adapter, perform the following steps:
1.Verify that the UPS is turned off.
2.Use the supplied serial cable labeled “UPS” to connect the UPS port on the BestLink Adapter to the UPS communication port.
If connecting to a FERRUPS model with a
3.Set both DIP switches on the adapter to the 0 (off) position.
4 | BestLink SNMP/WEB Adapter User’s Guide : |