Powerware IPK-0318, IPK-0320 Performing a Manual UPS Battery Test, Scheduling a UPS Battery Test

Page 28

UPS Power Management

3.If you entered a host name for the Mail Server, you must enter the IP address of your network DNS Server in the DNS Address block.

4.To receive a daily status report, enter the time of day to send the e-mail (in 24-hour format).

5.Enter the Mail Account, Description, Mail Type, Event Level, and Event Type for each recipient. Refer to the online help file for more details on each of these fields.

6.Select Set Values to save your changes.

Performing a Manual UPS Battery Test

You can use the BestLink Adapter to manually perform a UPS battery test. The ability to test the UPS is model dependent, so consult your UPS documentation for more information.

1.To manually start a battery test on a specific UPS, select Control from the menu at the top of the home page.

2.Become a Superuser and then select Initiate Battery Test, followed by Set Values to start the process.

3.To stop the test while in progress, you can select Cancel Battery Test followed by Set Values.

Scheduling a UPS Battery Test

You can use the BestLink Adapter to perform a UPS battery test on a user-defined schedule.

1.To schedule a battery test on a specific UPS, select Control from the menu at the top of the home page.

2.Select Battery Test Schedule.

3.Become a Superuser and then select the Test Day and Test Time (in

24-hour format) for the test to be initiated by the BestLink Adapter. The test is performed each week on the specified day and time until the Test Day is changed to Disabled.

4.Set Set Values to update the adapter with the schedule information.

22

BestLink SNMP/WEB Adapter User’s Guide : LTM-1343 B Draft 10/03/2001

Image 28
Contents Bestlink SNMP/WEB Adapter Class a EMC Statements Requesting a Declaration of ConformityFCC Part EN50091-2 Page Page Table of Contents Appendix Introduction BestLink SNMP/WEB Adapter System Application Diagram System ApplicationInstallation Installing the Internal BestLink AdapterInstalling the External BestLink Adapter Installing the Internal BestLink AdapterInstalling the External BestLink Adapter Configuring the Adapter Locally ConfigurationConfiguring the Adapter Remotely Local Configuration Before You StartConnecting the BestLink SNMP/WEB Adapter Cable Connection with External BestLink AdapterBestLink SNMP/WEB Adapter Main Menu Screen Configuring the Adapter SNMP/WEB Adapter Settings ScreenExiting the Configuration Program Set the IP Address, Gateway Address and MIB System Group Set Write Access ManagersSet SNMP/WEB Card Control Group Set UPS Information Set Trap ReceiversSet IP Addresses of Primary and Secondary Date Server UPS Event ActionsMail Notification Set Superuser Name and PasswordBack to Main Menu Add a Routing Condition in the PC Remote ConfigurationRoute add 192.168.7.18 Running the Web Browser BestLink Adapter HomeSetup Network Configuration Remote Configuration UPS Management from a Web Browser UPS Power ManagementBecoming a Superuser Turning the UPS On and Off Forcing the UPS to Shut DownConfiguring E-mail Notification Planning a Scheduled UPS Shutdown and RestartUPS Shutdown Schedule Mail NotificationScheduling a UPS Battery Test Performing a Manual UPS Battery TestSelect Battery Test Schedule Viewing the UPS History Logs UPS Management from an Snmp NMSViewing the UPS Status with CheckUPS-like Applet Viewing UPS Monitoring Parameters Receiving Event TrapsAutomatic Shutdown of UPS-Protected Computers UPS Power Management Technical Specifications AppendixAdapter Components External BestLink Adapter Rear PanelDIP Switch Description DIP Switch ModesLED Description LED DefinitionsPin Assignments External BestLink Adapter to UPS Serial Connection Serial Cable DefinitionExternal BestLink Adapter to PC Serial Connection Upgrading the BestLink Adapter Firmware Service and Support 852-2830-3030Two-Year Limited Warranty US and Canada Only Extended Service CoverageInternational Limited Warranty Force MajeureAppendix Page LTM-1343 B