Relay outputs

The UPS incorporates a programmable relay output with potential free contacts at X57 for remote alarm indications. It is rated for max. 30 VAC 1 A or 60 VDC 0,2 A nominal values. Additional

(4) relay outputs can be obtained with the X-slot compatible AS/400 Relay Module (optional).

Warning!

The relay contacts must not be directly connected to mains related circuits. Reinforced insulation to the mains is required.

Programmable signal inputs

The UPS incorporates two programmable inputs (X44, X45). Use of a non-polar (relay) control input is recommended. The pins must be shorted with maximum resistance of 10 ohm in order to activate the specific input.

Note!

Please note the polarity of the inputs as indicated in the external control connections if used with a polarity control.

The default and programmable settings for the signal inputs are

a)Disable Bypass Operation

If active the automatic transfer to the static bypass is prevented.

b)Charger off

If active the batteries charging is disabled. In case of mains power outage the discharge of batteries is supported.

c)Remote ON/OFF

If active the UPS output turns off regardless of mode of operation. Auxiliary power, fan, communications and rectifier/battery charger shall remain functional. Restart initiated immediately when inactive.

d)Request Bypass

If active the UPS transfers to bypass if bypass voltage, frequency and synchronisation are ok.

e)Request Normal

If active the UPS transfers to inverter operation if not prohibited by EPO or alarm condition.

f)Force Bypass

If active the UPS is forced to static bypass operation regardless of the bypass status.

g)External Battery Breaker Status

If active the UPS knows that the batteries are disconnected.

h)Building alarm 1-6

These can be activated separately or at the same time with other building alarms.

i)Not in use (default)

j)Shutdown

If active the UPS will shutdown immediately.

k)Delayed Shutdown

If active the UPS will shutdown after user configurable delay time. Restart initiated immediately when inactive.

l)Normal/Bypass

If active the UPS transfers to bypass if ok. If inactive the UPS transfers to inverter when possible.

1022403

UPS 8 – 15 kVA, 230V 50/60 Hz output

29

Revision B1

User’s Guide

 

Image 29
Contents Page Copyright Contents User precautions Safety instructionsAudience CE markingInquiries EnvironmentUnpacking and visual inspection Mechanical installationDelivery check Type designation label Equipment Weight Point Distributed Planning before installationMechanical bypass switch Cabinet installationMechanical bypass switch MBS when installed in the backside Transformer option Battery racks External battery cabinet optionLocation of the power terminals Electrical installationPower terminals found in UPS units Power cables and protective fusesInstallation procedure Wiring procedureWiring diagram of UPS N-model 3-ph rectifier Wiring diagram of UPS NT-model 3-ph rectifier Wiring diagram of UPS S-model 1-ph rectifier Wiring diagram of UPS ST-model 1-ph rectifier Wiring diagram of UPS S-model 1-ph rectifier, Norway Do not place EBC on the UPS unit External Battery Cabinet EBC installation procedureUser Settings Number of Battery Strings SPM tie cabinet Dimensions of the SPM SPM9155 wiring diagram with three UPSs connected Connection to the standard RS-232 port Software and connectivity Communication cables LanSafe software External control connectionsExternal control cable connections to the UPS Emergency Power Off EPORelay outputs Programmable signal inputsSNMP/Web Module optional Slot communication optionModus/Jbus Module optional AS400 Relay Module optionalSingle Serial Port Module optional Display functions User operationsDescription Available settings Default setting General User SettingsUsing relay outputs Configuring user settingsChanging language Changing charging currentNormal start-up Battery start-upShutdown CheckRegular service/intervals MaintenanceScrapping BatteriesCooling fan LED IndicatorsMaintenance bypass switch MBS operation No break transfer from normal mode to Service Bypass Turn UPS from normal mode to mechanical bypassNo break transfer from Mechanical Bypass to normal mode Turn UPS from mechanical bypass to normal modeTurn on S3 switch to connect UPS output to load UPS models with no battery sections Dimensional drawingsExternal battery cabinet models with 2 and 3 sections Mechanical configuration Technical dataCharacteristics StandardsAC output AC inputDC circuit Warranty