Powerware 8 - 10 kVA, 8 - 15 kVA Planning before installation, Equipment Weight Point Distributed

Page 8

3. Planning before installation

The equipment must be installed in upright position. The equipment requires space to front and back to enable cooling airflow, service and maintenance. All cooling air enters at front and exits at unit rear. The required min. clearance from unit rear to an obstruction is 150 mm.

Figure 3. Ventilation space around the equipment.

It is required to arrange ventilation of the UPS room. Sufficient amount of air cooling is needed to keep the max. room temperature rise at desired level:

Temperature rise of max. +5°C requires the airflow of 600 m3 per 1 kW of losses.

Temperature rise of max. +10°C requires the airflow of 300 m3 per 1 kW of losses.

An ambient temperature of 15 to 25 Celsius degrees is recommended to achieve a long life of the UPS and batteries. The cooling air entering the UPS must not exceed +40 °C. Avoid high ambient temperature, moisture and humidity.

The floor material should be non-flammable and strong enough to support the heavy load. The UPS has (4) leveling feet that should be used when finalising the installation. The diameter of a single leveling foot is 1 inch (25.4 mm).

Equipment

Weight

Point

Distributed

Note

UPS+1BAT

155 kg

7.75 kg/cm2

738 kg/m2

Batteries installed.

 

 

 

 

 

UPS+2BAT

265 kg

13.25 kg/cm2

1262 kg/m2

Batteries installed.

UPS

50 kg

2.50 kg/cm2

238 kg/m2

No Batteries.

 

 

 

 

 

UPS+1BAT

65 kg

3.25 kg/cm2

310 kg/m2

No Batteries installed.

 

 

 

 

 

UPS+2BAT

80 kg

3.95 kg/cm2

382 kg/m2

No Batteries installed.

 

 

 

 

 

2BAT

195 kg

9.75 kg/cm2

929 kg/m2

Batteries installed.

 

 

 

 

 

3BAT

310 kg

15.50 kg/cm2

1476 kg/m2

Batteries installed.

Table 4. The floor surface must tolerate these loading.

8

UPS 8 – 15 kVA, 230V 50/60 Hz output

1022403

 

User’s Guide

Revision B1

Image 8
Contents Page Copyright Contents Safety instructions User precautionsAudience CE markingEnvironment InquiriesUnpacking and visual inspection Mechanical installationDelivery check Type designation label Planning before installation Equipment Weight Point DistributedCabinet installation Mechanical bypass switchMechanical bypass switch MBS when installed in the backside Transformer option External battery cabinet option Battery racksElectrical installation Location of the power terminalsPower cables and protective fuses Power terminals found in UPS unitsWiring procedure Installation procedureWiring diagram of UPS N-model 3-ph rectifier Wiring diagram of UPS NT-model 3-ph rectifier Wiring diagram of UPS S-model 1-ph rectifier Wiring diagram of UPS ST-model 1-ph rectifier Wiring diagram of UPS S-model 1-ph rectifier, Norway External Battery Cabinet EBC installation procedure Do not place EBC on the UPS unitUser Settings Number of Battery Strings SPM tie cabinet Dimensions of the SPM SPM9155 wiring diagram with three UPSs connected Connection to the standard RS-232 port Software and connectivityCommunication cables External control connections LanSafe softwareEmergency Power Off EPO External control cable connections to the UPSProgrammable signal inputs Relay outputsSlot communication option SNMP/Web Module optionalModus/Jbus Module optional AS400 Relay Module optionalSingle Serial Port Module optional User operations Display functionsUser Settings Description Available settings Default setting GeneralConfiguring user settings Using relay outputsChanging language Changing charging currentBattery start-up Normal start-upShutdown CheckMaintenance Regular service/intervalsScrapping BatteriesCooling fan LED IndicatorsMaintenance bypass switch MBS operation Turn UPS from normal mode to mechanical bypass No break transfer from normal mode to Service BypassTurn UPS from mechanical bypass to normal mode No break transfer from Mechanical Bypass to normal modeTurn on S3 switch to connect UPS output to load Dimensional drawings UPS models with no battery sectionsExternal battery cabinet models with 2 and 3 sections Technical data Mechanical configurationCharacteristics StandardsAC output AC inputDC circuit Warranty

8 - 15 kVA, 8 - 10 kVA specifications

Powerware 8 - 10 kVA and 8 - 15 kVA are robust uninterruptible power supply (UPS) systems designed to provide reliable power protection and enhanced performance for critical applications. These UPS systems are ideal for various business environments, including data centers, server rooms, and industrial settings.

A primary feature of the Powerware series is its modular design, which allows for easy scalability and adaptability to meet the growing power requirements of modern IT infrastructure. The systems can be configured to provide redundancy, ensuring increased reliability and uptime while delivering high-efficiency performance.

One of the standout characteristics of the Powerware 8 - 10 kVA and 8 - 15 kVA models is their advanced double-conversion technology, which offers consistent power conditioning and isolation from utility issues like voltage surges, frequency variations, and power outages. This technology ensures that connected devices receive clean, stable power, minimizing the risk of downtime caused by electrical disturbances.

Another key feature is the availability of an intuitive LCD display that provides users with real-time information about the UPS status, critical alarms, and event logs, enabling proactive management of power demands and potential issues. The systems also support remote monitoring and management through advanced communication options, allowing IT administrators to maintain oversight of the power environment from any location.

The Powerware series incorporates high-efficiency designs that help reduce energy consumption, ultimately lowering operational costs. With an input power factor of up to 0.99 and a typical efficiency exceeding 94%, these UPS units not only contribute to environmental sustainability but also enhance the overall performance of the power infrastructure.

In addition to these practical features, the Powerware 8 - 10 kVA and 8 - 15 kVA models are equipped with multiple output options, including configurable outlets and hardwire connections, offering flexibility in deployment. They also come with advanced battery management systems, which optimize battery performance, extending their lifespan and reducing maintenance efforts.

Overall, Powerware 8 - 10 kVA and 8 - 15 kVA systems are reliable choices for businesses seeking efficient and adaptable power protection solutions to support their critical operations. Their innovative technologies and comprehensive features ensure that companies can maintain productivity while safeguarding their valuable equipment and data against power disruptions.